Sentrol ZX400 Manual - page 53
53
INSTALLER LEVEL PROGRAMMING
signals the Listen-In operator by momentarily seiz-
ing the phone line and producing a tone. This in-
terrupts the Listen-In Module connection for about
one second but it does not hang-up the phone line.
The panel also starts a two minute timer. It will not
try to call out to the Central Station until either the
Line-Seized signal from the Listen-In zone is removed
or the two minute timer expires, whichever comes
first. If the timer expires before the Line-Seized sig-
nal is removed, the panel seizes the line to dial out
to the Central Station, disconnecting and hanging
up the Listen-In Module’s connection.
If an alarm is silenced through a Control Station dur-
ing a Listen-In session, it has no impact on the Lis-
ten-In operation.
If a Holdup Alarm event is re-
ported to the Central Station, it is
the Listen-In operator’s responsi-
bility to NOT activate the speak-
ers on the Listen-In Module.
Note 12: Delay Before Dial Time
The Delay Before Dial Time is used as the time that
a user has after a Burglar, Holdup, or Auxiliary Alarm
from a zone has occurred to silence the alarm with a
disarm and abort the Alarm event.
If the Delay Before Dial Time is not zero and the alarm
is silenced before the Delay Before Dial Time expires,
then no Alarm events are posted to be reported. If this
occurs and Log Alarm Aborted Events is enabled, then
Alarm Aborted events are posted for each zone that
went into alarm, but they are not reported.
If the Delay Before Dial Time is zero or if the Delay
Before Dial Time expires before the alarm is silenced
with a disarm, then the Alarm events are posted to
be reported. If the alarm is a Burglar Alarm and the
alarm is silenced with a disarm before the Burglar
Bell Cutoff Timer expires, then a “Cancel Alarm”
event is logged to be reported.
If an alarm in a Control Station’s Primary or Second-
ary area is in Delay Before Dial Time, then when
the OFF CANCEL key is pressed on the Control Sta-
tion, all alarms in the Control Station’s Primary and
Secondary areas are muted until the Delay Before
Dial Time expires. While an alarm is muted, the
Control Stations do not produce the alarm tone for
the alarm and the Bell Output(s) are silent. The
muting of an alarm does not affect the operation of
programmed outputs. If the Delay Before Dial Time
expires without the alarm being silenced, then the
Control Stations resume the alarm tone and the Bell
Output(s) re-activate. The alarm cut-off timer(s) con-
tinue to count while the alarm is muted.
Note 13: Fire Delay Before Dial
The Fire Delay Before Dial Time is used as the time
that a user has after a Fire Alarm from a zone has oc-
curred to silence the alarm and abort the Alarm event.
If the Fire Delay Before Dial Time is not zero and
the alarm is silenced before the Fire Delay Before
Dial Time expires, then no Alarm events are posted
to be reported. If this occurs and Log Alarm Abort
Events is enabled, the Alarm Aborted events are
posted for each zone that went into alarm, but they
are not reported. If a Fire Alarm is silenced before
the Fire Delay Before Dial Time expires, the user
has 255 seconds to reset the smoke detectors, oth-
erwise a smoke reset will automatically occur when
255 seconds elapses.
If the Fire Delay Before Dial Time is zero or if Fire Delay
Before Dial Time expires before Fire Alarm is silenced,
then the Alarm events are posted to be reported.
If a Fire Alarm is in Fire Delay Before Dial Time
then when the Off Cancel key is pressed from a key-
pad, all alarms in the keypads Primary and Second-
ary area are muted until the Fire Delay Before Dial
Time expires. While an alarm is muted, the Control
Stations do not produce the alarm tone for the alarm
and the Bell Output(s) are silent. The muting of an
alarm does not affect the operation of programmed
outputs. If the Fire Delay Before Dial Time expires
without the alarm being silenced, then the Control
Stations resume the alarm tone and the Bell
Output(s) re-activate. The alarm cut-off timer(s)
continue to count while the alarm is muted.
Fire Delay Before Dial Time does not apply to Fire
Alarms from Water Flow zones.
Note 14: Transmission Formats
If the Data Format is “Pulsed 20 Baud - Non-Ex-
tended”, then the number of digits in the account
NOTE