TDK-Lambda Z+ series User manual - page 9
8
4.3 SCPI Subsystem Commands
Subsystem commands control all Z
+
functions. For a full command description refer to section
7.12 in Z
+
series User Manual. Short list of Z
+
series commands:
OUTPut
[:STATe]
Enable/Disable output
[:STATe]?
Enable/Disable output query
:PON
[:STATe]
Set power-on state in Safe or Auto start
[:STATe]?
Power-on state in Safe or Auto start query
:PROTection
:CLEar
Reset latched protection
:FOLDback
[:MODE]
Protection at transition CCCV modes
[:MODE]?
Protection at transition CCCV modes query
:DELay
Delay before protection activated
:DELay?
Delay before protection activated query
:ILC
:MODE
Set remote inhibit input (ENAble|DISable)
:MODE?
Set remote inhibit input query
:TTLTrg
:MODE
Set or disable Function Strobe Mode
:MODE?
Function Strobe Mode query
:RELay
[:STATe]
Set programming pin status
[:STATe]?
Programming pin status query
:MODE?
Replay operation mode CV/CC/OFF
INSTrument
:COUPle
Couple for all
Z
+
power supplies
:NSELect
Select the Power Supply to remote operation
:NSELect?
Selected Power Supply
VOLTage
[:LEVel]
[:IMMediate]
[:AMPLitude]
Set output voltage
[:AMPLitude]?
Set output voltage query
:TRIGger
Set current value for trigger pending
:TRIGger?
Set current value for trigger pending query