INSTALLATION
1. When deciding on the location of your heater
and vent pipe, try to minimize the alteration and
reframing of structural components of the
building. Vent pipe must be installed so that
access is provided for inspection and cleaning.
2. Avoid installing heater in high-traffic areas.
Keep children well away from heater when in
operation.
3. A 3-inch clearance to combustibles must be
maintained for horizontal and vertical
venting. When passing through ceilings or
walls, you must use a listed wall thimble,
making sure all combustible materials and
insulation products are a minimum of 3 inches
away from the pellet vent pipe.
4. A non-combustible hearth pad must be used if
installed on a carpet, wood floor, or other
combustible material (see Figure 4).
5. Keep front door of appliance thirty-six (36)
inches from combustibles (drapery, furniture).
6. When installing the exhaust vent into an
existing chimney, a clean out tee must be
installed behind the heater before going up into
the chimney. This is necessary in order to
remove the fly ash accumulation.
7. Exit termination (distance to openings):
a) 3 feet minimum above any forced air
inlet located within 10 feet.
b) 4 feet minimum below and horizontally
or 1 foot minimum above any door,
window, or gravity air inlet into any
building.
c) 2 feet minimum to an adjacent building
and 7 feet minimum above grade when
located adjacent to public walkways.