Vaillant ecoTEC plus SERIES Installation And Maintenance Instructions Manual - page 27
Start-up 7
0020209593_01 ecoTEC plus Installation and maintenance instructions
27
Settings
Unit
G20
natural
gas
G31 liquid
gas
CO₂ after 5 minutes
in full load mode with
front casing closed
Vol.–%
9.2 ± 1.0
10.4 ± 0.5
CO₂ after 5 minutes
in full load mode with
front casing removed
Vol.–%
9.0 ± 1.0
10.2 ± 0.5
Set for Wobbe index
W₀
kWh/m³
14.09
21.34
O₂ after 5 minutes in
full load mode with
front casing closed
Vol.–%
4.5 ± 1.8
5.1 ± 0.8
CO value with full load
ppm
≤ 250
≤ 250
CO/CO₂
≤ 0.0031
≤ 0.0026
Conditions: The CO₂ content must be adjusted
2
1
▶
Pierce the covering cap (1) at the mark using a small
flat-blade screwdriver and unscrew it.
▶
After performing the adjustments, tilt the air intake pipe
back up.
▶
Check the CO₂ content again.
▶
If necessary, repeat the setting process.
▶
Set the CO₂ content (value with front casing removed)
by turning the screw (2).
– Higher CO₂ content: Turn anti-clockwise
– Lower CO₂ content: Turn clockwise
▶
For natural gas only: Only perform the adjustment in in-
crements of 1 turn and wait approx. 1 minute after each
adjustment until the value stabilises.
▶
For liquid gas only: Only perform the adjustment in small
increments (approx. 1/2 turn), and wait approx. 1 minute
after each adjustment until the value stabilises.
▶
Check the CO₂ content again.
▶
If necessary, repeat the setting process.
▶
Press
(Cancel) once the adjustments have been
made.
▶
If an adjustment is not possible in the specified adjust-
ment range, you must not start up the product.
▶
If this is the case, inform Customer Service.
▶
Screw the covering cap back in.
▶
Install the front casing.
7.16
Checking function and leak-tightness
Before you hand the product over to the operator:
▶
Check the gas line, the flue gas installation, the heating
installation and the hot water pipes for leaks.
▶
Check that the air/flue pipe and condensate drain pipe-
work have been installed correctly.
▶
Check that the front casing has been installed correctly.
7.16.1 Checking the heating mode
1.
Make sure that there is a heat requirement.
2.
Call up the Live Monitor.
◁
If the product is working correctly, the display shows
S.04.
7.16.2 Checking the hot water generation
1.
Open a hot water valve all the way.
2.
Call up the Live Monitor.
◁
If the hot water generation is working correctly, S.14
appears in the display.
7.16.3 Checking the cylinder charging
Note
Cylinder charging is deactivated ex-works and
must be activated during initial start-up.
The cylinder charging of the shift-load cylinder is only active
if Comfort mode is switched on. If Comfort mode is activated,
the symbol "C" appears in the display ( Operating instruc-
tions).
When cylinder charging is switched on, the following temper-
atures can be set for the hot water temperature (see operat-
ing instructions):
– Minimum temperature 50 °C
Maximum temperature 65 °C
When cylinder charging is switched off, the following temper-
atures can be set for the hot water temperature:
– Minimum temperature 35 °C
Maximum temperature 65 °C
If cylinder charging is switched off, the cylinder is not held
at temperature. If you draw off water, the boiler switches on
and, in this case, only operates on the through-flow principle.
▶
The product is equipped with an automatic Anti-legionella
function; if the temperature in the domestic hot water
cylinder falls below 50 °C, the cylinder is heated up to
70 °C once every 24 hours. If required, in consultation
with the operator, switch the Anti-legionella function off
using diagnostics code D.074.