5 Connect to the signal circuit
VEGADIS 176 • External indicating and adjustment display without external energy for front panel mounting
47916-EN-170801
5 Connect to the signal circuit
5.1 Preparing the connection
Always keep in mind the following safety instructions:
•
Connect only in the complete absence of line voltage
•
Only connect to a 4 … 20 mA signal circuit with sensor or the
4 … 20 mA signal output of a signal conditioning instrument
The instrument must only be powered by an energy-limited circuit
according to IEC 61010-1.
Caution:
Never connect the VEGADIS 176 directly to a voltage source without
current limitation. Otherwise the instrument can be destroyed by a too
high current.
5.2 Connection technology and steps
The voltage supply and signal output are connected via the spring-
loaded terminals in the housing.
Proceed as follows:
1. Removeapprox.10cm(4in)ofthecablemantle,stripapprox.
1cm(0.4in)ofinsulationfromtheendsoftheindividualwires
2
3
Fig. 4: Connection steps 2 and 3
2. Solidcoresaswellasflexiblecoreswithcableendsleevesare
inserted directly into the terminal openings.
3. Incaseofflexiblecoreswithoutendsleeves,presstheterminal
from above with a small screwdriver, the terminal opening is then
free. When the screwdriver is released, the terminal closes again.
Information:
Youcanfindfurtherinformationonthemax.wirecross-sectionunder
"Technical data - Electromechanical data".
4. Check the hold of the wires in the terminals by lightly pulling on
them
5. Connect screen to the potential equalisation terminal.
5.3 Wiring plan
The terminals are on the rear of the housing.
Safety instructions
Voltage supply
Connection technology
Connection procedure
Terminal assignment