Operating instructions external display and adjustment unit for 4 … 20 ma/hart sensors vegadis 82 4 … 20 ma/hart document id: 45300
2 contents vegadis 82 • 4 … 20 ma/hart 45300-en-170724 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group .............................................................
3 contents vegadis 82 • 4 … 20 ma/hart 45300-en-170724 8.1 maintenance .................................................................................................................. 51 8.2 asset management function ....................................................................................
4 1 about this document vegadis 82 • 4 … 20 ma/hart 45300-en-170724 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenance,faultrectification,theexchangeofpartsan...
5 2 for your safety vegadis 82 • 4 … 20 ma/hart 45300-en-170724 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the ...
6 2 for your safety vegadis 82 • 4 … 20 ma/hart 45300-en-170724 to avoid any danger, the safety approval markings and safety tips on the device must also be observed and their meaning looked up in this operating instructions manual. 2.5 eu conformity thedevicefulfilsthelegalrequirementsoftheapplicab...
7 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-170724 3 product description 3.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 3 1 5 6 4 12 11 10 9 8 7 fig. 1: layout of the type label (example) 1 instrument type 2 product code 3 fie...
8 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-170724 • hardware from 1.00.00 the scope of delivery encompasses: • vegadis 82 • display and adjustment module (optional) • mounting accessories (optional) • documentation – this operating instructions manual – ex-specific"safety instructi...
9 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-170724 4 5 3 1 2 fig. 2: connection of the vegadis 82 to the sensor, adjustment via the display and adjustment module 1 voltage supply/signal output sensor 2 vegadis 82 3 display and adjustment module 4 4 … 20 ma/hart signal cable 5 sensor...
10 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-170724 adjustment range: sensor adjustment, indication scaling vegadis 82 hart multidrop: the vegadis 82 can be also used as an indicating device for a bus participant in a hart multidrop system. Adjustment range: sensor adjustment for a ...
11 3 product description vegadis 82 • 4 … 20 ma/hart 45300-en-170724 the interface adapter vegaconnect enables the connection of communication-capable instruments to the usb interface of a pc. For parameter adjustment of these instruments, the adjustment software pactware with vega-dtm is required. ...
12 4 mounting vegadis 82 • 4 … 20 ma/hart 45300-en-170724 4 mounting 4.1 general instructions vegadis 82 functions in any installation position. Protect your instrument against moisture ingress through the following measures: • use the recommended cable (see chapter "connecting to power supply") • t...
13 4 mounting vegadis 82 • 4 … 20 ma/hart 45300-en-170724 1 2 fig. 5: vegadis 82 with plastic housing for carrier rail mounting 1 base 2 carrier rail the versions with aluminium or stainless steel housing for carrier rail mounting according to en 50022 are supplied with unassembled mounting accessor...
14 4 mounting vegadis 82 • 4 … 20 ma/hart 45300-en-170724 2 1 3 fig. 7: vegadis 82 for tube mounting 1 4 screws m6 x 100 2 mounting brackets 3 tube (diameter 1" to 2") the vegadis 82 is also available with a plastic housing for panel mounting. The housing is fastened to the rear of the panel by mean...
15 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-170724 5 connecting to power supply 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. • the electrical connection must only be carried...
16 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-170724 npt thread in the case of instrument housings with self-sealing npt threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust ...
17 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-170724 fig. 9: connection steps 5 and 6 6. Insert the wire ends into the terminals according to the wiring plan information: solidcoresaswellasflexiblecoreswithwireendsleevesareinsert- eddirectlyintotheterminalopenings.Incaseofflex...
18 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-170724 5.3 wiring plan sensor 1 2 + ( ) (-) power supply 3 4 + ( ) (-) r off on hart 1 4 2 3 fig. 10: wiring plan vegadis 82 4 … 20 ma/hart 1 to the sensor 2 switchforcommunicationresistor(on=activated,off=deactivated) 3 terminal f...
19 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-170724 ~ = 1 2 3 fig. 12: installation example vegadis 82 in conjunction with an individual sensor 1 sensor 2 vegadis 82 3 voltage supply/processing 5.5 connection hart multidrop thefollowingillustrationsshowinasimplifiedwaytheuseo...
20 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-170724 + - 1 2 3 4 18 17 16 15 1413 1211 10 9 8 7 6 5 n- l1+ + - on 1 2 1 2 % 1 2 3 fig. 14: connection of vegadis 82 as external display to a signal conditioning instrument 1 sensor 2 signal conditioning instrument 3 vegadis 82 th...
21 5 connecting to power supply vegadis 82 • 4 … 20 ma/hart 45300-en-170724 3 1 2 sensor 1 2 + ( ) (-) power supply 3 4 + ( ) (-) r + - off on hart fig. 16: bridge between terminals 1 and 4 on the vegadis 82 1 bridge 2 vegadis 82 3 active sensor 5.7 connection example 1 3 2 4 5 1 2 + ( ) (-) 6 7 8 4...
22 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 6 set up with the display and adjustment module 6.1 short description the display and adjustment module is used for measured value display, adjustment and diagnosis. It can be mounted in the following hous...
23 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 fig. 18: mounting of the display and adjustment module 6.3 adjustment system 1 2 fig. 19: display and adjustment elements 1 lc display 2 adjustment keys • [ok] key: – move to the menu overview – confirmsel...
24 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 • [->] key: – change measured value presentation – select list entry – select menu items in the quick setup menu – select editing position • [+] key: – change value of the parameter • [esc] key: – interrup...
25 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 with the "ok" key you move to the start menu. 6.5 start menu the start menu is divided into two sections with the following func- tions: the selection branches into the following menus for parameter adjust...
26 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 this menu item allows a change of the national language. The following languages are available: • german • english • french • spanish • russian • italian • dutch • portuguese • turkish • polish • czech int...
27 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 todampprocess-dependentmeasuredvaluefluctuations,setan integration time of 0 … 999 s in this menu item. The increment is 0.1 s. Theenteredintegrationtimeinfluencesthecurrentvalueandthe display.Thehartvalue...
28 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 in case of instrument failure, an error code with text message is dis- played.Youcanfindinformationoncauseandrectificationinchapter "diagnosis and service". After a reset, certain parameter adjustments mad...
29 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 the copied data are permanently saved in the display and adjustment module. They remain even in case of voltage loss. Note: before the data are stored in the instrument, they are checked to make sure they ...
30 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 in this menu item, instrument features such as approvals, electronics, housing as well as others are displayed. 6.7 parameter adjustment vegapuls wl 61 the main menu is divided into four areas with the fol...
31 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 – high accuracy – short reaction time of the sensor not required storage tank with product circulation: • setup: large-volumed, upright cylindrical, spherical • mediumspeed:slowfillingandemptying • vessel:...
32 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 – fastfillingandemptying – vesselisfilledandemptiedveryoften • vessel: tight installation situation • process/measurement conditions: – condensation, buildup on the antenna – foam generation • properties, ...
33 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 • process/measurement conditions: – condensation on the plastic ceiling – in outdoor facilities, water and snow on vessel top possible • properties, sensor: – false signals outside the vessel are not taken...
34 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 – stable and reliable measured values through frequent averag- ing – insensitive in the close range demonstration: • adjustment for all applications which are not typically level meas- urement – instrument...
35 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 indicate the actual level, an allocation of the measured distance to the percentage height must be carried out. To perform the adjustment, enter the distance with full and empty ves- sel, see the following...
36 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 3. Set the requested percentage value with [+] and save with [ok]. The cursor jumps now to the distance value. 4. Enter the appropriate distance value in m (corresponding to the percentage value) for the f...
37 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 the "echo curve" shows the signal strength of the echoes over the measuring range in db. The signal strength enables an evaluation of the quality of the measurement. The "false signal suppression" displays...
38 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 note: this should be done with the lowest possible level so that all potential interferingreflectionscanbedetected. Proceed as follows: 1. Select menu item "additional settings" with [->]andconfirmwith [ok...
39 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 tected. When selecting "extend", the distance to the product surface of the created false signal suppression is displayed. This value can now be changed and the false signal suppression can be extended to ...
40 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 false signal suppression: deletes a previously created false signal suppression. The false signal suppression created at the factory remains active. Peak values distance: resetting the measured min. And ma...
41 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 service: reset info: instrument type and serial number in this menu item, the adjustment units of the instrument are deter- mined. The selection determines the unit displayed in the menu items "min. Adjust...
42 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 2 1 100% 0% 2 m (78.74 ") fig. 21: parameter adjustment example "min./max. Adjustment, level measure- ment" 1 min. Level = 0 % corresponds to 0.0 mbar 2 max. Level = 100 % corresponds to 196.2 mbar ifthese...
43 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 5. Save settings with [ok] and move with [esc] and [->] to the max. Adjustment. Themin.Adjustmentisfinished. Foranadjustmentwithfilling,simplyentertheactualmeasuredvalue indicated at the bottom of the disp...
44 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 user especially when setting the switching point on the limit signal transmitter. In this menu item, the device status is displayed. The respective min. And max. Measured values are saved in the sensor. Th...
45 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 in this menu item, you read out the instrument type and the serial number: 6.9 parameter adjustment - sensors from other manufacturers via generic hart the main menu is divided into three areas with the fo...
46 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 proceed as follows: 1. Select with [->]themenuitem"upperrange"andconfirmwith [ok]. 2. Edit the percentage value with [ok] and set the cursor to the requested position with [->]. 3. Set the requested percen...
47 6 set up with the display and adjustment module vegadis 82 • 4 … 20 ma/hart 45300-en-170724 in this menu item, you can read out the instrument name and the instrument serial number: info - instrument name.
48 7 setup via pactware vegadis 82 • 4 … 20 ma/hart 45300-en-170724 7 setup via pactware 7.1 connect the pc the pc is connected via the interface adapter vegaconnect to vegadis 82. Parameter adjustment options: • vegadis 82 • sensor 3 1 2 fig. 22: connection of the pc via interface adapter 1 usb cab...
49 7 setup via pactware vegadis 82 • 4 … 20 ma/hart 45300-en-170724 1 3 6 5 2 4 sensor 1 2 + ( ) (-) power supply 3 4 + ( ) (-) r off on hart fig. 23: connecting the pc via hart to the signal cable 1 processing system/plc/voltage supply 2 vegadis 82 3 to the sensor 4 connection cable with 2 mm pins ...
50 7 setup via pactware vegadis 82 • 4 … 20 ma/hart 45300-en-170724 fig. 24: example of a dtm view all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assis...
51 8 diagnostics and servicing vegadis 82 • 4 … 20 ma/hart 45300-en-170724 8 diagnostics and servicing 8.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 8.2 asset management function the instrument supports the self-monitoring and diagnosis of the c...
52 8 diagnostics and servicing vegadis 82 • 4 … 20 ma/hart 45300-en-170724 code text message reason rectification f036 no executable software version • instrument software not executable (during software update or after failed update) • waituntilsoftwareupdateisfinished • carry out another software ...
53 8 diagnostics and servicing vegadis 82 • 4 … 20 ma/hart 45300-en-170724 8.4 exchanging the electronics module in case of a defect, the user can replace the electronics module with another one of identical type. In ex applications, only instruments and electronics modules with ap- propriate ex app...
54 9 dismount vegadis 82 • 4 … 20 ma/hart 45300-en-170724 9 dismount 9.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapters "mounting" and...
55 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 10 supplement 10.1 technical data materials and weights materials Ʋ plastic housing plastic pbt (polyester) Ʋ aluminium housing aluminium die-casting alsi10mg, powder-coated (basis: polyester) Ʋ stainless steel housing 316l precision casti...
56 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 torques max. Torque for npt cable glands and conduit tubes Ʋ plastic housing 10 nm (7.376 lbf ft) Ʋ aluminium/stainless steel housing 50 nm (36.88 lbf ft) signal and supply circuit operating voltage max. 35 v dc voltage drop with current v...
57 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 adjustment elements slide switch in the connection compart- ment activate/deactivate the integrated communication resist- ance for hart ambient conditions storage and transport temperature -40 … +80 °c (-40 … +176 °f) ambient temperature Ʋ...
58 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 Ʋ housing for panel mounting (mount- ed) iec 60529 ip 40, nema type 1 Ʋ aluminium/stainless steel housing iec 60529ip 66/ip 68 (0.2 bar), nema type 6p connection of the feeding power supply unit networks of overvoltage category iii altitud...
59 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 10.3 dimensions vegadis 82, plastic housing ø 79 mm (3.11") ~ 69 mm (2.72") 85 mm (3.35") 82 mm (3.23") 97 mm (3.82") 6,5 mm (0.26") 97 mm (3.82") fig. 25: vegadis 82 with plastic housing vegadis 82, plastic housing (panel mounting) 72,5 m...
60 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 vegadis 82, aluminium housing ø 86 mm (3.39") ~ 75,2 mm (2.95") 87 mm (3.43") 82 mm (3.23") 97 mm (3.82") 5 mm (0.2") 97 mm (3.82") fig. 27: vegadis 82 with aluminium housing vegadis 82, stainless steel housing (precision casting) ø 86 mm ...
61 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 mounting elements 82 mm (3.23") 97 mm (3.82") 7 mm (0.28") 11 mm (0.43") 82 mm (3.23") 97 mm (3.82") fig. 29: adapter plate for carrier rail mounting of vegadis 82 ø 29...60 mm (1.14"...2.36") 82 mm (3.23") 15 mm (0.59") 97 mm (3.82") 20 m...
62 10 supplement vegadis 82 • 4 … 20 ma/hart 45300-en-170724 10.4 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nähere informationen ...
63 index vegadis 82 • 4 … 20 ma/hart 45300-en-170724 index a adjustment 35, 36, 41 – lower range 46 – max. Adjustment 43 – min. Adjustment 42 – system 24 – unit 45 – upper range 46 adjustment menu 25, 40 application area 8 c change the language 26 check output signal 52 connection – cable 15 – steps...
Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 45300-en-170724 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...