Vega VEGAFLEX FX-E.80A Operating Instructions Manual - page 12
12
5 Setup
Electronics module • VEGAFLEX 80 series
43656-EN-170531
5.2 Setup steps
Aftertransmissionofthesensordata,allapplication-specificsettings
must be entered again. Carry out a fresh setup after exchanging the
electronics or load the stored data of the setup.
Ifyousavedtheparametersettingsduringthefirstsetupofthesen-
sor, you can transfer them to the replacement electronics module. To
do this, use the import function of the adjustment software PACTware
with the device DTMs or the copy function of the display and adjust-
ment module. A fresh setup is then not necessary.
Youcanfindinformationonhowtocopysavedparameteradjustment
data to the new electronics module under "Additional settings - Copy
instrument settings".
OnSILqualifiedinstruments,thesettingsoftheelectronicsmustbe
checkedandverifiedaftertheelectronicsexchange.Onlythenisthe
instrument again ready for operation.
Youcanfindinformationaboutthetestandverificationintheoperat-
ing instructions corresponding to your sensor as well as in the Safety
Manual.
Information:
If a false signal suppression already existed, we recommend creating
a new one. If this is not possible, for example, because the vessel
isfilled,thefalsesignalsuppressioncanbeimportedviatheDTM.
However, the false signal suppression should be updated or created
anew next time the vessel is empty.
During setup, take note of the operating instructions corresponding to
your sensor.
Parameter data