Vega VEGAMIP R61 Operating Instructions Manual

Manual is about: Receiving unit

Summary of VEGAMIP R61

  • Page 1

    Operating instructions vegamip r61 receiving unit - relay document id: 35786 radar.

  • Page 2: Contents

    Contents 1 about this document 1.1 function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 symbolism used. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 for your safety 2.1 authorised...

  • Page 3

    Safety instructions for ex areas please note the ex-specific safety information for installation and operation in ex areas. These safety instructions are part of the operating instructions manual and come with the ex-approved instruments. Vegamip r 61 • - relay 3 contents 35786 - en -100531.

  • Page 4: About This Document

    1 about this document 1 .1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep...

  • Page 5: For Your Safety

    2 for your safety 2 .1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2 ....

  • Page 6

    The emitting frequencies of the sensors depend on the model, but are all in the k band range. The low transmitting power lies far below the internationally permitted limit value. When the instrument is used correctly, it presents no danger to human health. It may be operated without restriction outs...

  • Page 7: Product Description

    3 product description 3 .1 configuration the type label contains the most important data for identification and use of the instrument: l article number l serial number l technical data l article numbers, documentation with the serial number, you can access the delivery data of the instrument via www.V...

  • Page 8

    It works even under extremely difficult conditons, such as different granulation sizes, contamination, extreme filling noise, high temper- atures, strong dust generation or abrasive products. The vegamip 61 consists of the following components. 3 3 5 4 5 2 1 fig. 1: vegamip 61 with plastic housing 1 emi...

  • Page 9

    Several antenna versions are available for different applications. 1 2 3 4 fig. 2: antenna versions 1 encapsulated horn antenna with ptfe cover 2 plastic encapsulated antenna with pp cover 3 horn antenna 4 vegamip 61 with angled antenna extension the emitting unit transmits a focused microwave signal...

  • Page 10

    Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside. Unless otherwise indicated, the packages must be stored only under the following conditions: l not in the open l dry and dust free l not exposed to corrosive ...

  • Page 11

    With high process temperatures exceeding 80 °c, you have to use a mounting adapter for the emitting and receiving unit. The mounting adapter can be only used with the encapsulated horn antenna with ptfe cover. Fig. 3: vegamip 61 with high temperature mounting adapter mounting adapter vegamip r 61 • ...

  • Page 12: Mounting

    4 mounting 4 .1 general instructions with instruments with threaded process fitting, suitable tools must be applied for tightening the hexagon. Warning: the housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing. Make sure that all part...

  • Page 13

    Avoid mounting the instrument too close to the vessel wall. Reflections from the vessel wall or from vessel installation can influence the switching accuracy. Fig. 4: installation position (top view) if vegamip 61 is mounted in the filling stream, unwanted false measurement signals can be generated. Fo...

  • Page 14

    1 fig. 6: installation in front of a vessel window 1 window of non-conductive material, for example, glass, plastic, etc. In general, the same as for metal vessels applies to concrete vessels due to the steel braining. In general, the same as for metal vessels applies to wood vessels due to the liqu...

  • Page 15

    1 2 3 4 fig. 8: vegamip 61 - threaded version g1½ a 1 polarisation marking 2 instrument hexagon 3 locknut 4 process seal 1 insert the supplied process seal (1) before screwing it in 2 to screw vegamip 61 in, use the instrument hexagon (3) below the housing. Screw the instrument in and hand-screw it ...

  • Page 16

    2 1 fig. 9: front-flush installation 1 unfavourable installation - bulk solid can settle in front of the sensor 2 correct front flush installation in very abrasive products, vegamip 61 should be installed with a mounting adapter or in front of a suitable window. In this case, you have to use a window ...

  • Page 17

    5° + - fig. 10: orientation of the sensors the emitting unit emits electromagnetic waves. The polarisation plane is the direction of the electrical wave component. Its position is marked on the instrument hexagon by polarisation markings. For a reliable function, the emitting and receiving unit must...

  • Page 18

    In tight mounting spaces or spaces subject to high temperatures, the signal of vegamip 61 can be guided via a deflector. You can use a metal plate for this or an angled antenna extension on the side of the emitting unit. In products with low dielectric value, we recommend using an instrument version ...

  • Page 19

    5 connecting to power supply 5 .1 preparing the connection always keep in mind the following safety instructions: l connect only in the complete absence of line voltage l if overvoltages are expected, install overvoltage arresters connect the operating voltage according to the following diagrams. Th...

  • Page 20

    4 insert the cable into the sensor through the cable entry fig. 13: connection steps 4 and 5 5 insert the wire ends into the terminals according to the wiring plan information: solid cores as well as flexible (stranded) cores with wire end sleeves are inserted directly into the terminal openings. If ...

  • Page 21

    5 .3 wiring plan, single chamber housing we recommend connecting vegamip 61 in such a way that the switching circuit is open when there is a level signal, line break or failure (safe condition). Information: the relays are always shown in non-operative condition. 3 2 1 fig. 14: wiring plan receiving...

  • Page 22: Setup

    6 setup 6 .1 adjustment elements the figures in brackets refer to the following illustration. 6 7 9 8 4 5 1 2 3 1 l n 3 (-) ( ) 4 5 6 7 8 2 + 3 4 5 6 7 8 fig. 15: electronics module mpe60r receiver unit - relay output 1 mode switch for selecting the switching behaviour (min./max.) 2 control lamp (led...

  • Page 23

    With the mode adjustment (max./min.) you can change the switching condition of the relay. You can set the required mode according to the "f unction chart" (max. - max. Detection or overflow protection, min. - min. Detection or dry run protection). With these keys (7 and 8) you can adjust the switchin...

  • Page 24

    Level switching status signal lamp - re- lay (yellow) mode min. Dry run protection 5 3 4 (8) (6) (7) relay deenergized failure of the supply voltage (max./min. Mode) any 5 3 4 (8) (6) (7) relay deenergized failure any 5 3 4 (8) (6) (7) relay deenergized red failure led lights depending on the switch...

  • Page 25

    Press the respective key until the indication is within the led indication strip. This means one or two leds on the led indication strip light up. 1 c b a 2 3 fig. 29: indication board 1 indication (led indication board) 2 more sensitive - key to the left 3 less sensitive - key to the right a medium...

  • Page 26

    1 l n 3 (-) ( ) 4 5 6 7 8 2 + 3 4 5 6 7 8 fig. 30: led indication strip - setting for products with good signal damping in applications with products having a low signal damping (for example plastic granules, cereals), you should adjust the instrument more sensitive. Hence, the vegamip 61 switches v...

  • Page 27

    By means of the led indicating board, you can adjust the switching delay. Push the two keys (7) and (8) simultaneously for approximately 2 s until the led indication flashes. With the two keys you can select the requested switching delay according to the following illustration. The switching delay ca...

  • Page 28

    7 maintenance and fault rectification 7 .1 maintenance when the device is used correctly, no maintenance is required in normal operation. 7 .2 rectify malfunctions the operator of the system is responsible for taking suitable measures to remove interferences. The first measure to be taken is to check ...

  • Page 29

    Depending on the failure reason and measures taken, the steps described in chapter "set up" must be carried out again, if necessary. However, should these measures not be successful, call the vega service hotline in urgent cases under the phone no. +49 1805 858550. The hotline is available to you 7 ...

  • Page 30: Dismounting

    8 dismounting 8 .1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "mounting" and "connecting to power supply" and carry out the listed steps in reve...

  • Page 31: Supplement

    9 supplement 9 .1 technical data general data material 316l corresponds to 1.4404 or 1.4435 materials, wetted parts - process fitting - thread 316l - process fitting - flange 316l - process seal klingersil c-4400 - instrument seal fkm (viton) - antenna cover pp, ptfe - cover - mounting adapter (optiona...

  • Page 32

    Relay data - ac 5 a, 253 v ac - dc 4 a, 30 v dc; 0.2 a, 125 v dc breaking capacity if inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be permanently damaged. The contact is then no longer suitable for switching low-level signal circuits. ...

  • Page 33

    L 1 x cable entry ½ npt, 1 x blind stopper ½ npt, 1 x cable entry ½ npt or: l 1 x plug m12 x 1; 1 x blind stopper m20 x 1.5 screw terminals for wire cross-section up to 1.5 mm² (awg 16) voltage supply operating voltage 20 … 253 v ac, 50/60 hz, 20 … 72 v dc (at u > 60 v dc, the ambient temperature ca...

  • Page 34

    9 .2 dimensions vegamip 61 - housing versions ~ 69 mm (2 23 / 32 ") ø 77 mm (3 1 / 32 ") 1 1 2 mm (4 1 3 / 3 2 ") m20x1,5/ ½ npt ~ 69 mm (2 23 / 32 ") ø 77 mm (3 1 / 32 ") 1 1 7 mm (4 3 9 / 6 4 ") m20x1,5/ ½ npt ~ 116 mm (4 9 / 16 ") ø 84 mm (3 5 / 16 ") 1 1 6 mm (4 9 / 1 6 ") m20x1,5 m20x1,5/ ½ npt...

  • Page 35

    Vegamip 61 2 2 mm (0 .8 7 ") 8 3 mm (3 .2 7 ") sw 46 mm (1.42") sw 60 mm (1.42") g1½ a 2 1 4 3 1 5 mm (0 .5 9 ") 9 8 mm (3 .8 6 ") 1 7 0 mm / 3 0 0 mm (6 .6 9 ") / (1 1 .8 1 ") 1 9 mm (0 .7 5 ") ø 75 mm (2.95") ø 115 mm (4.53") fig. 35: vegamip 61 1 threaded version - encapsulated horn antenna with ...

  • Page 36

    9 .3 industrial property rights vega product lines are global protected by industrial property rights. Further information see http://www.Vega.Com . Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte...

  • Page 37: Index

    Index a abrasion 16 accessory - flanges 10 - protective cover 10 application area 7 b bending 18 buildup 15 c cable 19 cable screening 19 e electronics module 10, 29 emitting unit 8 f fault rectification 28 filling opening 13 functional principle 9 m mode 23 moisture 12 mounting adapter 11 o orientat...

  • Page 38

    38 vegamip r 61 • - relay index 35786 -en -100531.

  • Page 39

    Vegamip r 61 • - relay 39 index 35786 - en -100531.

  • Page 40

    Vega grieshaber kg am hohenstein 113 77761 schiltach germany phone +49 7836 50-0 fax +49 7836 50-201 e-mail: info@de.Vega.Com www.Vega.Com printing date: iso 9001 all statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems co...