Vega VEGAWAVE 61 Operating instructions manual

Summary of VEGAWAVE 61

  • Page 1

    Operating instructions vibrating level switch with suspension cable for powders vegawave 62 relay (dpdt) document id: 32252.

  • Page 2: Contents

    2 contents vegawave 62 • relay (dpdt) 32252-en-170315 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group ..............................................................

  • Page 3

    3 contents vegawave 62 • relay (dpdt) 32252-en-170315 safety instructions for ex areas takenoteoftheexspecificsafetyinstructionsforexapplications. These instructions are attached as documents to each instrument with ex approval and are part of the operating instructions manual. Editing status: 2017-...

  • Page 4: 1  About This Document

    4 1 about this document vegawave 62 • relay (dpdt) 32252-en-170315 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification.Pleasereadthisinfor...

  • Page 5: 2  For Your Safety

    5 2 for your safety vegawave 62 • relay (dpdt) 32252-en-170315 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the r...

  • Page 6

    6 2 for your safety vegawave 62 • relay (dpdt) 32252-en-170315 2.5 safety label on the instrument the safety approval markings and safety tips on the device must be observed. 2.6 eu conformity thedevicefulfilsthelegalrequirementsoftheapplicableeuguide- lines.Byaffixingthecemarking,weconfirmsuccessfu...

  • Page 7: 3  Product Description

    7 3 product description vegawave 62 • relay (dpdt) 32252-en-170315 3 product description 3.1 configuration the scope of delivery encompasses: • vegawave 62 point level switch • documentation – this operating instructions manual – safety manual "functional safety (sil)" (optional) – supplementary ins...

  • Page 8

    8 3 product description vegawave 62 • relay (dpdt) 32252-en-170315 youcanfindtheserialnumberontheinsideoftheinstrumentaswell as on the type label on the outside. 3.2 principle of operation vegawave 62 is a point level sensor with tuning fork for point level detection. It is designed for industrial u...

  • Page 9

    9 3 product description vegawave 62 • relay (dpdt) 32252-en-170315 • signal lamp for indication of the switching condition (green/red) • potentiometer for adaptation to the product density • mode switch for selecting the switching condition (min./max.) 3.4 storage and transport your instrument was p...

  • Page 10: 4 Mounting

    10 4 mounting vegawave 62 • relay (dpdt) 32252-en-170315 4 mounting 4.1 general instructions make sure that all parts of the instrument coming in direct contact with the process, especially the sensor element, process seal and processfitting,aresuitablefortheexistingprocessconditions,such as process...

  • Page 11

    11 4 mounting vegawave 62 • relay (dpdt) 32252-en-170315 warning: the housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing. Use the hexagon above the thread for screwing in. Metric threads in the case of instrument housings with metr...

  • Page 12

    12 4 mounting vegawave 62 • relay (dpdt) 32252-en-170315 d d d 6 d 6 fig. 3: filling and emptying centred d d 6 1 2 3 fig. 4: filling in the centre, emptying laterally 1 vegawave 62 2 discharge opening 3 filling opening.

  • Page 13

    13 4 mounting vegawave 62 • relay (dpdt) 32252-en-170315 the vibrating element should protrude into the vessel to avoid buildup.Forthatreason,avoidusingmountingbossesforflanges andscrewedfittings.Thisappliesparticularlytousewithadhesive products. Ifvegawave62ismountedinthefillingstream,unwantedfalse...

  • Page 14

    14 4 mounting vegawave 62 • relay (dpdt) 32252-en-170315 1 2 fig. 6: flow orientation of the tuning fork 1 marking with screwed version 2 directionofflow in applications such as grit chambers or settling basins for coarse sediments, the vibrating element must be protected against damage withasuitabl...

  • Page 15

    15 5 connecting to power supply vegawave 62 • relay (dpdt) 32252-en-170315 5 connecting to power supply 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. • the electrical connection must only be carried ...

  • Page 16

    16 5 connecting to power supply vegawave 62 • relay (dpdt) 32252-en-170315 1. Unscrew the housing lid 2. Loosen compression nut of the cable gland and remove blind plug 3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) of insulation from the ends of the individual wires...

  • Page 17

    17 5 connecting to power supply vegawave 62 • relay (dpdt) 32252-en-170315 5 5 5 5 1 2 4 3 fig. 9: material versions, single chamber housing 1 plastic (not with ex d) 2 aluminium 3 stainless steel (not with ex d) 4 stainless steel, electropolished (not with ex d) 5 filter element for pressure compen...

  • Page 18: 6 Setup

    18 6 setup vegawave 62 • relay (dpdt) 32252-en-170315 6 setup 6.1 general information thefiguresinbracketsrefertothefollowingillustrations. Ontheelectronicsmoduleyouwillfindthefollowingdisplayand adjustment elements: • potentiometer for adjustment of the density range (1) • dil switch for mode adjus...

  • Page 19

    19 6 setup vegawave 62 • relay (dpdt) 32252-en-170315 for instruments detecting solids in water, these settings are not ap- plicable. The density range is preset and must not be changed. With the mode setting (min./max.) you can change the switching condition of the relay. You can set the required m...

  • Page 20

    20 6 setup vegawave 62 • relay (dpdt) 32252-en-170315 level switching status control lamp fault any 5 3 4 (8) (6) (7) relaydeenergized flashesred.

  • Page 21

    21 7maintenanceandfaultrectification vegawave 62 • relay (dpdt) 32252-en-170315 7 maintenanceandfaultrectification 7.1 maintenance if the device is used properly, no special maintenance is required in normal operation. 7.2 rectify faults the operator of the system is responsible for taking suitable ...

  • Page 22

    22 7maintenanceandfaultrectification vegawave 62 • relay (dpdt) 32252-en-170315 error reason rectification signallampflashesred error on the vibrating el- ement check if the vibrating element is damaged or extreme- ly corroded. Interference on the elec- tronics module exchanging the electronics modu...

  • Page 23

    23 7maintenanceandfaultrectification vegawave 62 • relay (dpdt) 32252-en-170315 8. Compare the settings of the two electronics modules. Set the adjustment elements of the new electronics module to the same setting of the old one. Information: make sure that the housing is not rotated during the elec...

  • Page 24: 8 Dismount

    24 8 dismount vegawave 62 • relay (dpdt) 32252-en-170315 8 dismount 8.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "mounting" and "connecting to...

  • Page 25: 9 Supplement

    25 9 supplement vegawave 62 • relay (dpdt) 32252-en-170315 9 supplement 9.1 technical data note for approved instruments the technical data in the respective safety instructions are valid for approved instruments (e.G. With exapproval).Thesedatacandifferfromthedatalistedherein,forexampleregardingthe...

  • Page 26

    26 9 supplement vegawave 62 • relay (dpdt) 32252-en-170315 Ʋ suspension cable (-40 … +150 °c/- 40 … +302 °f) optionally 200g/m(2.15oz/ft) max. Permissible tensile load 3000 n (675 lbs) sensor length (l) - suspension cable pur (-20 … +80 °c/-4 … +176 °f) 0.48 … 80 m (1.575 … 262.47 ft) sensor length ...

  • Page 27

    27 9 supplement vegawave 62 • relay (dpdt) 32252-en-170315 process temperature with pur suspen- sion cable -20 … +80 °c (-4 … +176 °f) process temperature with fep suspen- sion cable -40 … +150 °c (-40 … +302 °f) product density Ʋ standard sensitivity > 0.02 g/cm³ (0.0007 lbs/in³) Ʋ high sensitivity...

  • Page 28

    28 9 supplement vegawave 62 • relay (dpdt) 32252-en-170315 9.2 dimensions vegawave 62, housing 3 2 1 4 ~ 69 mm (2.72") ø 79 mm (3.11") 11 7 mm (4.61") m20x1,5/ ½ npt ~ 59 mm (2.32") ø 80 mm (3.15") 11 2 mm (4.41") m20x1,5/ ½ npt ~ 69 mm (2.72") ø 79 mm (3.03") 112 mm (4.41") m20x1,5/ ½ npt ~ 116 mm ...

  • Page 29

    29 9 supplement vegawave 62 • relay (dpdt) 32252-en-170315 g1½ ø 43 mm (1.69") l 33 mm (1.30") 22 mm (0.87") 160 mm (6.30") 150 mm (5.91") ø 43 mm (1.69") ø 11 mm (0.43") 40 mm (1.57") fig. 30: vegawave 62 with pur suspension cable, threaded version g1½ (din iso 228/1) l sensor length, see chapter "...

  • Page 30

    30 9 supplement vegawave 62 • relay (dpdt) 32252-en-170315 l g1½ ø 43 mm (1.69") 33 mm (1.30") 22 mm (0.87") 160 mm (6.30") 150 mm (5.91") ø 43 mm (1.69") ø 10 mm (0.39") 40 mm (1.57") fig. 31: vegawave 62 with fep suspension cable, threaded version g1½ (din iso 228/1) l sensor length, see chapter "...

  • Page 31

    31 9 supplement vegawave 62 • relay (dpdt) 32252-en-170315 9.3 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nähere informationen unt...

  • Page 32

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 32252-en-170315 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...