4 Mounting
VEGAWAVE 62 • Relay (DPDT)
32252-EN-170315
4 Mounting
4.1 General instructions
Make sure that all parts of the instrument coming in direct contact
with the process, especially the sensor element, process seal and
processfitting,aresuitablefortheexistingprocessconditions,such
as process pressure, process temperature as well as the chemical
properties of the medium.
Youcanfindthespecificationsinchapter"Technical data" and on the
nameplate.
In general, VEGAWAVE 62 must be mounted vertically. The instru-
ment must be mounted in such a way that the vibrating element is at
the height of the requested switching point.
Use the recommended cables (see chapter "Connecting to power
supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cableentry.Rainandcondensationwatercanthusdrainoff.Thisap-
plies mainly to outdoor mounting as well as installation in areas where
high humidity is expected (e.g. through cleaning processes) or on
cooled or heated vessels.
Fig. 2: Measures against moisture ingress
Do not hold VEGAWAVE 62 on the vibrating element. Especially with
flangeandtubeversions,thesensorcanbedamagedbytheweight
of the instrument.
Remove the protective cover just before mounting
Theprocessfittingmustbesealedifthereisgaugeorlowpressurein
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
Themax.permissiblepressureisspecifiedinchapter"Technical
data" or on the type label of the sensor.
The vibrating level switch is a measuring instrument and must be
treated accordingly. Bending the vibrating element will destroy the
instrument.
Suitability for the process
conditions
Switching point
Moisture
Transport
Pressure/Vacuum
Handling