Wattstopper InteliSwitch AS-100 Installation Instruction - page 5
SETUP
The AS-100 Automatic Control Switch comes factory preset and ready to install
in conjunction with a lighting control panel. The default operation is manual-ON/
OFF along with automatic-OFF when signalled by the lighting control panel.
If an audible beep warning or automatic-ON features are desired, use the
following procedure:
• Setup for the switch options is accomplished with the ON/OFF button and LED
display. There is no need to remove the cover plate.
1. To enter Setup Mode: Press and hold down the ON/OFF button until the LEDs
fl ash every second from left to right (approximately 7 seconds).
2. When in Setup Mode, the confi guration LEDs fl ash to indicate the current
confi guration settings. Press the ON/OFF button to sequence through the
option selections until the desired options are displayed.
3. To exit Setup Mode and save the selected options: Press and hold the ON/OFF
button until the LEDs fl ash every second from right to left (approximately 3
seconds). If the lights controlled by this switch are ON, the lighting fi xtures will
turn OFF. Setup is now complete and the option selections are saved.
If the ON/OFF button is not pressed to exit Setup Mode, the AS-100 will time
out of Setup Mode after approximately 30 seconds, and new option selections
will not be saved.
Factory Settings:
• Lighting
control
panel automatic-
OFF capable.
• No Setup Mode
options are
selected.
• See
Operation
(next page) for
other available
functions.
Automatic-ON
Audible beep (during Automatic Delayed-off)
Setup Mode Options:
LED display
(Option is on when LED flashes in display )
= Setup Mode options off (factory setting)
= Audible beep (option on)
= Automatic-ON (option on)
= Automatic-ON & Audible beep (options on)
= Unused