ABB REG670 Product Manual

Manual is about: Relion 670 series 2.0 IEC Generator protection

Summary of REG670

  • Page 1

    Relion® 670 series — generator protection reg670 version 2.2 product guide.

  • Page 2

    Contents 1. Application..................................................................... 3 2. Available functions..........................................................8 3. Differential protection....................................................20 4. Impedance protection......................

  • Page 3

    1. Application semod155704-4 v7 the reg670 is used for protection, control and monitoring of generators and generator-transformer blocks from relatively small units up to the largest generating units. The ied has a comprehensive function library, covering the requirements for most generator applicat...

  • Page 4

    Description of configuration a20 semod175637-4 v5 g sa ptuf 81u f sa ptuf 81 f sa ptof 81o f> sa ptof 81 f> uv2 ptuv 27 2(3u ov2 ptov 59 2(3u>) vn mmxu met un v msqi met usqi cc rbrf 50bf 3i>bf gop pdop 32 p> gup pdup 37 p gs pttr 49 s θ> c mmxu met i gen pdif 87g 3id/i> zgv pdis 21 z cv gapc 64r re...

  • Page 5

    Description of configuration b30 semod175637-11 v6 auxiliary bus y unit step-up trafo aux ili ary traf o ex cit ati on t ra fo cc rbrf 50bf 3i>bf ef4 ptoc 51n_67n 4(in>) rov2 ptov 59n 2(u0>) sa ptuf 81u f sa ptuf 81 f sa ptof 81o f> sa ptof 81 f> uv2 ptuv 27 2(3u ov2 ptov 59 2(3u>) v msqi met usqi v...

  • Page 6

    Description of configuration c30 semod175637-18 v6 auxiliary bus y u ni t s te p-up t ra fo auxilia ry t ra fo cc rbrf 50bf 3i>bf rov2 ptov 59n 2(u0>) sa ptuf 81u f sa ptuf 81 f sa ptof 81o f> sa ptof 81 f> uv2 ptuv 27 2(3u ov2 ptov 59 2(3u>) v mmxu met u vn mmxu met un v msqi met usqi cc rbrf 50bf ...

  • Page 7

    The basic delivery includes one binary input module and one binary output module, which is sufficient for the default configured io to trip and close circuit breaker. All ieds can be reconfigured with the help of the application configuration tool in pcm600. The ied can be adapted to special applica...

  • Page 8

    2. Available functions guid-f5776dd1-bd04-4872-bb89-a0412b4b5cc3 v1 the following tables list all the functions available in the ied. Those functions that are not exposed to the user or do not need to be configured are not described in this manual. Main protection functions guid-66baad98-851d-4aac-b...

  • Page 9

    Back-up protection functions guid-a8d0852f-807f-4442-8730-e44808e194f0 v13 iec 61850 or function name ansi function description generator reg670 (customized) reg670 (a20) reg670 (b30) reg670 (c30) current protection phpioc 50 instantaneous phase overcurrent protection 0-4 1 2 2 oc4ptoc 51_67 1) dire...

  • Page 10

    Iec 61850 or function name ansi function description generator reg670 (customized) reg670 (a20) reg670 (b30) reg670 (c30) sapfrc 81 rate-of-change of frequency protection 0-6 1 3 3 ftaqfvr 81a frequency time accumulation protection 0-12 12-e03 12-e03 12-e03 multipurpose protection cvgapc general cur...

  • Page 11

    Control and monitoring functions guid-e3777f16-0b76-4157-a3bf-0b6b978863de v15 iec 61850 or function name ansi function description generator reg670 (customized) reg670 (a20) reg670 (b30) reg670 (c30) control sesrsyn 25 synchrocheck, energizing check and synchronizing 0-2 1 2 2 apc30 3 control funct...

  • Page 12

    Iec 61850 or function name ansi function description generator reg670 (customized) reg670 (a20) reg670 (b30) reg670 (c30) wrncalh logic for group warning 5 5 5 5 indcalh logic for group indication 5 5 5 5 and, gate, inv, lld, or, pulsetimer, rsmemory, srmemory, timerset, xor basic configurable logic...

  • Page 13

    Table 2. Total number of instances for basic configurable logic blocks basic configurable logic block total number of instances and 280 gate 40 inv 420 lld 40 or 298 pulsetimer 40 rsmemory 40 srmemory 40 timerset 60 xor 40 table 3. Number of function instances in apc30 function name function descrip...

  • Page 14

    Table 4. Total number of instances for configurable logic blocks q/t configurable logic blocks q/t total number of instances andqt 120 indcombspqt 20 indextspqt 20 invalidqt 22 inverterqt 120 orqt 120 pulsetimerqt 40 rsmemoryqt 40 srmemoryqt 40 timersetqt 40 xorqt 40 table 5. Total number of instanc...

  • Page 15

    Iec 61850 or function name ansi function description generator reg670 (customized) reg670 (a20) reg670 (b30) reg670 (c30) monitoring cvmmxn power system measurement 6 6 6 6 cmmxu current measurement 10 10 10 10 vmmxu voltage measurement phase-phase 6 6 6 6 cmsqi current sequence measurement 6 6 6 6 ...

  • Page 16

    Communication guid-5f144b53-b9a7-4173-80cf-cd4c84579cb5 v15 iec 61850 or function name ansi function description generator reg670 (customized) reg670 (a20) reg670 (b30) reg670 (c30) station communication lonspa, spa spa communication protocol 1 1 1 1 ade lon communication protocol 1 1 1 1 horzcomm n...

  • Page 17

    Iec 61850 or function name ansi function description generator reg670 (customized) reg670 (a20) reg670 (b30) reg670 (c30) fstaccs field service tool access 1 1 1 1 iec 61850-9-2 process bus communication, 8 merging units 0-1 1-p30 1-p30 1-p30 activlog activity logging 1 1 1 1 altrk service tracking ...

  • Page 18

    Table 6. Number of function instances in synchrophasor report, 16 phasors function name function description number of instances pmuconf configuration parameters for c37.118 2011 and ieee1344 protocol 1 pmureport protocol reporting via ieee 1344 and c37.118 2 phasorreport1 protocol reporting of phas...

  • Page 19

    Basic ied functions guid-c8f0e5d2-e305-4184-9627-f6b5864216ca v12 table 7. Basic ied functions iec 61850 or function name description interrsig self supervision with internal event list timesynchgen time synchronization module bininput, synchcan, synchgps, synchcmpps, synchlon, synchpph, synchpps, s...

  • Page 20

    Table 8. Local hmi functions iec 61850 or function name ansi description lhmictrl local hmi signals language local human machine language screen local hmi local human machine screen behavior fnkeyty1–fnkeyty5 fnkeymd1– fnkeymd5 parameter setting function for hmi in pcm600 ledgen general led indicati...

  • Page 21

    Two-winding applications xx05000048.Vsd iec05000048 v1 en-us two-winding power transformer xx05000049.Vsd iec05000049 v1 en-us two-winding power transformer with unconnected delta tertiary winding xx05000050.Vsd iec05000050 v1 en-us two-winding power transformer with two circuit breakers and two ct-...

  • Page 22

    The most typical application yndx d cb ct ct cb y ied cb cb cb cb autotransformer the most complicated application - autotransformer ct ct ct ct iec05000058-2-en.Vsd iec05000058-2 v1 en-us figure 5. Examples of applications of the refpdif 4. Impedance protection full-scheme distance measuring, mho c...

  • Page 23

    Pole slipping. The main purpose of the pole slip protection (pspppam) is to detect, evaluate, and take the required action for pole slipping occurrences in the power system. Out-of-step protection oosppam guid-bf2f7d4c-f579-4ebd-9afc-7c03296bd5d4 v8 the out-of-step protection (oosppam ) function in ...

  • Page 24

    Standard 95% stator earth-fault protection based on the neutral point fundamental frequency displacement voltage. The 100% stator earth fault protection requires the injection unit rex060 and optional shunt resistor unit rex062 for correct operation. Underimpedance protection for generators and tran...

  • Page 25

    Directional residual overcurrent protection, four steps ef4ptoc m13667-3 v19 directional residual overcurrent protection, four steps (ef4ptoc) can be used as main protection for phase-to- earth faults. It can also be used to provide a system back-up, for example, in the case of the primary protectio...

  • Page 26

    Tripping of surrounding breakers at an incorrect initiation due to mistakes during testing. Pole discordance protection ccpdsc m13269-3 v15 an open phase can cause negative and zero sequence currents which cause thermal stress on rotating machines and can cause unwanted operation of zero sequence or...

  • Page 27

    Side. Aegpvoc is enabled when the terminal voltage drops below the specified voltage level for the preset time. Stator overload protection gspttr guid-a416c856-e438-4ed4-a43d-d05f718d6a41 v6 the generator overload function, (gspttr) is used to protect the stator winding against excessive temperature...

  • Page 28

    Transformers and has one sensitive alarm step and one trip step. 100% stator earth fault protection, 3rd harmonic based stefphiz semod143258-4 v10 stator earth fault is a fault type having relatively high fault rate. The generator systems normally have high impedance earthing, that is, earthing via ...

  • Page 29

    8. Frequency protection underfrequency protection saptuf m13349-3 v13 underfrequency occurs as a result of a lack of generation in the network. Underfrequency protection (saptuf) measures frequency with high accuracy, and is used for load shedding systems, remedial action schemes, gas turbine startu...

  • Page 30

    Rotor earth fault protection using cvgapc semod151286-4 v8 the field winding, including the rotor winding and the non- rotating excitation equipment, is always insulated from the metallic parts of the rotor. The insulation resistance is high if the rotor is cooled by air or by hydrogen. The insulati...

  • Page 31

    12. Control synchrocheck, energizing check, and synchronizing sesrsyn m12480-3 v16 the synchronizing function allows closing of asynchronous networks at the correct moment including the breaker closing time, which improves the network stability. Synchrocheck, energizing check, and synchronizing (ses...

  • Page 32

    Reservation function qcrsv m13506-3 v4 the purpose of the reservation function is primarily to transfer interlocking information between ieds in a safe way and to prevent double operation in a bay, switchyard part, or complete substation. Reservation input resin m16501-3 v5 the reservation input (re...

  • Page 33

    13. Logic tripping logic smpptrc m12275-3 v12 a function block for protection tripping and general start indication is always provided as a basic function for each circuit breaker. It provides a settable pulse prolongation time to ensure a trip pulse of sufficient length, as well as all functionalit...

  • Page 34

    • andqt and function block. The function also propagates the time stamp and the quality of input signals. Each block has four inputs and two outputs where one is inverted. • indcombspqt combines single input signals to group signal. Single position input is copied to value part of sp_out output. Tim...

  • Page 35

    Integer to boolean 16 conversion with logic node representation itbgapc semod158421-5 v9 integer to boolean conversion with logic node representation function (itbgapc) is used to transform an integer which is transmitted over iec 61850 and received by the function to 16 boolean (logic) output signa...

  • Page 36

    Event recorder drprdre m12033-3 v8 quick, complete and reliable information about disturbances in the primary and/or in the secondary system is vital, for example, time-tagged events logged during disturbances. This information is used for different purposes in the short term (for example corrective...

  • Page 37

    The breaker requires maintenance when the number of operations reaches a predefined value. For a proper functioning of the circuit breaker, it is essential to monitor the circuit breaker operation, spring charge indication or breaker wear, travel time, number of operation cycles and estimate the acc...

  • Page 38

    Are updated every minute through output channels. The active and reactive maximum power demand values are calculated for both forward and reverse direction and these values can be reset with rstdmd input. 16. Human machine interface local hmi amu0600442 v14 iec13000239-3-en.Vsd iec13000239 v3 en-us ...

  • Page 39

    Available as an option when ordering ieds. Prp according to iec 62439-3 uses two optical ethernet ports. Iec 62439-3 high-availability seamless redundancy hsr redundant station bus communication according to iec 62439-3 edition 2 high-availability seamless redundancy (hsr) is available as an option ...

  • Page 40

    Private range, and the information number parameter for each block. Function status auto-recloser for iec 60870-5-103 i103ar i103ar is a function block with defined functions for autorecloser indications in monitor direction. This block includes the functiontype parameter, and the information number...

  • Page 41

    Binary signal transfer semod52522-4 v7 the remote end data communication is used for the transmission of analog values for line differential protection or for the transmission of only binary signals between ieds. The binary signals are freely configurable and can thus be used for any purpose, such a...

  • Page 42

    Line data communication module ldcm m16075-3 v5 each module has one optical port, one for each remote end to which the ied communicates. Alternative modules for long range (1550 nm single mode), medium range (1310 nm single mode) and short range (850 nm multi mode) are available. Galvanic rs485 seri...

  • Page 43

    Iec06000182-2-en.Vsd iec06000182 v2 en-us figure 12. A 1/2 x 19” size ied side-by-side with rhgs6. M15243-12 v9 case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8.81 242.1/ 9.53 255.8/ 10.07 205.7/ 8.10 190.5/ 7.50 203.7/ 8.02 - 228.6/ 9.00 - 6u, 3/4 x 19” 265.9/ 10.47 3...

  • Page 44

    Coupling capacitor unit rex061 guid-39a03c0f-44dc-47dd-9d7e-66c8292cd3a8 v1 rex061 isolates the injection circuit from the rotor exciter voltage. The rex061 coupling capacitor unit grounding point and grounding brush of the rotor shaft should be properly interconnected. Shunt resistor unit rex062 gu...

  • Page 45

    22. Connection diagrams guid-cf4effa5-3081-4fc7-9a14-ed127c3c0fde v6 the connection diagrams are delivered in the ied connectivity package as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/protection-control . Connection diagram...

  • Page 46

    23. Technical data general ip11376-1 v2 m10993-1 v3 definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the ...

  • Page 47

    Energizing quantities, rated values and limits analog inputs ip15842-1 v1 m16988-1 v11 table 9. Trm - energizing quantities, rated values and limits for protection transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1 or 5 a...

  • Page 48

    Table 10. Trm - energizing quantities, rated values and limits for measuring transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1a 5 a operating range (0-1.8) × i r (0-1.6) × i r thermal withstand 80 × i r for 1 s 25 × i r ...

  • Page 49

    Table 13. Sfp - galvanic rj45 quantity rated value number of channels up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol standard ieee 802.3u 100base-tx type of cable cat5e ftp table 13. Sfp - galvanic rj45, continued quantity rated valu...

  • Page 50

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M50609-2 v7 table 16. Bim - binary input module with enhanced pulse counting capabilities quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 22...

  • Page 51

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M12318-1 v8 table 18. Iom - binary input/output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) ...

  • Page 52

    Bom/iom/som should be activated continuously due to power dissipation. M12584-1 v7 table 19. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max s...

  • Page 53

    Bom/iom/som should be activated continuously due to power dissipation. Semod175395-2 v7 table 20. Som - static output module (reference standard: iec 61810-2): static binary outputs function of quantity static binary output trip rated voltage 48-60 vdc 110-250 vdc number of outputs 6 6 impedance ope...

  • Page 54

    Table 21. Som - static output module data (reference standard: iec 61810-2): electromechanical relay outputs function of quantity trip and signal relays max system voltage 250 v ac/dc number of outputs 6 test voltage across open contact, 1 min 1000 v rms current carrying capacity: continuous 8 a 1.0...

  • Page 55

    Table 24. Auxiliary dc supply voltage influence on functionality during operation dependence on reference value within nominal range influence ripple, in dc auxiliary voltage operative range max. 2% full wave rectified 15% of el 0.01%/% auxiliary voltage dependence, operate value ±20% of el 0.01%/% ...

  • Page 56

    Table 26. Electromagnetic compatibility test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-26 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv iec 61000-4-12, class iv surge withstand capabilit...

  • Page 57

    Table 28. Environmental tests test type test value reference standard cold operation test test ad for 16 h at -25°c iec 60068-2-1 cold storage test test ab for 16 h at -40°c iec 60068-2-1 dry heat operation test test bd for 16 h at +70°c iec 60068-2-2 dry heat storage test test bb for 16 h at +85°c ...

  • Page 58

    Injection equipment guid-87197cb5-8590-4872-a5b6-8c6d2a815c9e v3 table 31. Electromagnetic compatibility tests test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-26 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii surge withstand cap...

  • Page 59

    Table 33. Insulation tests, rex061 test type test values reference standard dielectric test 7.48 kv dc, 1min (connections to rotor) 2.8 kv dc, 1 min ieee 421.3 iec 60255-27 impulse voltage test 12.0 kv, 1.2/50 µs, 0.5 j (connections to rotor) 5.0 kv, 1.2/50 µs, 0.5 j iec 60664-1 iec 60255-27 insulat...

  • Page 60

    Guid-9d1f44fc-896b-4907-9609-c32781ca1798 v3 table 36. Auxiliary dc supply voltage influence test type test values influence auxiliary voltage dependence, operate value ±20% of el 0.01%/% ripple in dc auxiliary voltage, operate value 15% of el 0.01%/% guid-a1bed9a8-2791-4acf-8400-b20206f057a8 v3 tab...

  • Page 61

    Differential protection semod175004-2 v10 table 39. Generator differential protection genpdif function range or value accuracy unrestrained differential current limit (1-50)p.U. Of ibase ±1.0% of set value reset ratio > 95% - minimum pickup (0.05–1.00)p.U. Of ibase ±1.0% of i r negative sequence cur...

  • Page 62

    M13046-1 v12 table 40. Transformer differential protection t2wpdif/t3wpdif function range or value accuracy operating characteristic adaptable ±1.0% of ir at i ≤ ir ±1.0% of i at i > ir reset ratio > 90% - unrestrained differential current limit (100-5000)% of ibase on high voltage winding ±1.0% of ...

  • Page 63

    M13062-1 v19 table 41. Restricted earth-fault protection, low impedance refpdif function range or value accuracy operating characteristic adaptable ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% - minimum pickup, idmin (4.0-100.0)% of ibase ±1.0% of i r directional characteristic fi...

  • Page 64

    Impedance protection semod173242-2 v14 table 43. Full-scheme distance protection, mho characteristic zmhpdis function range or value accuracy number of zones, ph-e max 4 with selectable direction - minimum operate current (10–30)% of ibase - positive sequence impedance, ph-e loop (0.005–3000.000) w ...

  • Page 65

    Guid-6c2ef52a-8166-4a23-9861-38931682aa7d v7 table 44. High speed distance protection zmfpdis, zmfcpdis function range or value accuracy number of zones 3 selectable directions, 3 fixed directions - minimum operate current, ph-ph and ph-e (5-6000)% of ibase ±1.0% of i r positive sequence reactance r...

  • Page 66

    Semod175136-2 v8 table 46. Out-of-step protection oosppam function range or value accuracy impedance reach (0.00 - 1000.00)% of zbase ±2.0% of u r /(√3 ⋅ i r ) rotor start angle (90.0 - 130.0) degrees ±5.0 degrees rotor trip angle (15.0 - 90.0) degrees ±5.0 degrees zone 1 and zone 2 trip counters (1...

  • Page 67

    Guid-956187e5-a466-47bf-b671-f46548a5df2e v3 table 49. Sttiphiz technical data function range or value accuracy fault resistance sensitivity can be reached at steady state operating condition of the machine 50 kΩ typically 10 kΩ injection frequency (50.000 - 250.000) hz ±0.1 hz injection voltage 240...

  • Page 68

    Wide area measurement system guid-f0baebd8-e361-4d50-9737-7df8b043d66a v4 table 51. Protocol reporting via ieee 1344 and c37.118 pmureport influencing quantity range accuracy signal frequency ± 0.1 x f r ≤ 1.0% tve signal magnitude: voltage phasor current phasor (0.1–1.2) x u r (0.5–2.0) x i r phase...

  • Page 69

    Current protection m12336-1 v13 table 52. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of ibase - operate time at 0 to 2 x i set min. = 15 ms max. ...

  • Page 70

    M12342-1 v20 table 53. Directional phase overcurrent protection, four steps oc4ptoc function setting range accuracy operate current, step 1-4 (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - minimum operate current, step 1-4 (1-10000)% of ...

  • Page 71

    M15223-1 v17 table 55. Directional residual overcurrent protection, four steps ef4ptoc function range or value accuracy operate current, step 1-4 (1-2500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - relay characteristic angle (rca) (-180 to 180)...

  • Page 72

    Guid-e83ad807-8fe0-4244-a50e-86b9af92469e v6 table 56. Four step directional negative phase sequence overcurrent protection ns4ptoc function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase -...

  • Page 73

    Semod173350-2 v16 table 57. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cos j directional residual overcurrent (0.25-200.00)% of ibase ±1.0% of i r at i £ i r ±1.0% of i at i > i r operate level for ·3i 0 ·3u 0 cos ...

  • Page 74

    M13266-2 v8 table 58. Thermal overload protection, two time constants trpttr function range or value accuracy base current 1 and 2 (30–250)% of ibase ±1.0% of i r operate time: 2 2 2 2 p ref i i t ln i i t æ ö - ç ÷ = × ç ÷ - è ø equation1356 v2 en-us (equation 1) i = actual measured current ip = lo...

  • Page 75

    M13279-1 v10 table 60. Pole discordance protection ccpdsc function range or value accuracy operate current (0–100)% of ibase ±1.0% of i r independent time delay between trip condition and trip signal (0.000-60.000) s ±0.2% or ± 30 ms whichever is greater semod175152-2 v11 table 61. Directional under...

  • Page 76

    Guid-e5718f80-556d-4852-a8f2-90e0f578d763 v9 table 63. Negative sequence time overcurrent protection for machines ns2ptoc function range or value accuracy operate current, step 1 - 2 (3-500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio >95% - operate time, start at 0 to 2 x i ...

  • Page 77

    Guid-9b1c0c10-8af9-4d9e-8076-b3e1c238d29a v8 table 64. Accidental energizing protection for synchronous generator aegpvoc function range or value accuracy operate value, overcurrent (5-900)% of ibase ±1.0% of i r at i≤i r ±1.0% of i at i>i r reset ratio, overcurrent >95% at (20–900)% of ibase - tran...

  • Page 78

    Guid-a1cb5b4f-768e-4b1b-937e-b91ec3efa2cc v4 table 66. Generator rotor overload protection grpttr function range or value accuracy overcurrent start level for overload protection (105.0–900.0)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio, overcurrent >95% — start time, overcur...

  • Page 79

    Guid-7ea9731a-8d56-4689-9072-d72d9cdfd795 v8 table 67. Voltage-restrained time overcurrent protection vrpvoc function range or value accuracy start overcurrent (2.0 - 5000.0)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio, overcurrent > 95% - operate time, start overcurrent at 0...

  • Page 80

    Voltage protection m13290-1 v15 table 68. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ...

  • Page 81

    M13304-1 v14 table 69. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time charac...

  • Page 82

    M13317-2 v14 table 70. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 - step 2 (1.0-200.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r in...

  • Page 83

    Semod166919-2 v7 table 72. Voltage differential protection vdcptov function range or value accuracy voltage difference for alarm and trip (2.0–100.0) % of ubase ±0.5% of u r under voltage level (1.0–100.0) % of ubase ±0.5% of u r independent time delay for voltage differential alarm at 0.8 x udalarm...

  • Page 84

    Frequency protection m13360-1 v15 table 74. Underfrequency protection saptuf function range or value accuracy operate value, start function, at symmetrical three phase voltage (35.00-75.00) hz ±2.0 mhz operate time, start at f set + 0.02 hz to f set - 0.02 hz fn = 50 hz min. = 80 ms - max. = 95 ms f...

  • Page 85

    M14976-1 v9 table 76. Rate-of-change of frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ±10.0 mhz/s operate value, restore enable frequency (45.00-65.00) hz ±2.0 mhz definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever...

  • Page 86

    Multipurpose protection m13095-2 v8 1mrk 502 074-ben a generator protection reg670 2.2 and injection equipment rex060, rex061, rex062 product version: 2.2.1 86 abb.

  • Page 87

    Table 78. General current and voltage protection cvgapc function range or value accuracy measuring current input phase1, phase2, phase3, posseq, - negseq, -3*zeroseq, maxph, minph, unbalanceph, phase1-phase2, phase2-phase3, phase3-phase1, maxph-ph, minph-ph, unbalanceph- ph - measuring voltage input...

  • Page 88

    Table 78. General current and voltage protection cvgapc , continued function range or value accuracy independent time delay, overvoltage at 0.8 x u set to 1.2 x u set , step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater independent time delay, undervoltage at 1.2 x u set to 0.8 x u s...

  • Page 89

    Table 78. General current and voltage protection cvgapc , continued function range or value accuracy undervoltage: critical impulse time 10 ms typically at 1.2 x u set to 0.8 x u set - impulse margin time 15 ms typically - semod175176-2 v5 table 79. Rotor earth fault protection based on general curr...

  • Page 90

    Secondary system supervision m12358-1 v10 table 80. Current circuit supervision ccsspvc function range or value accuracy operate current (10-200)% of ibase ±10.0% of i r at i ≤ i r ±10.0% of i at i > i r reset ratio, operate current >90% block current (20-500)% of ibase ±5.0% of i r at i ≤ i r ±5.0%...

  • Page 91

    Guid-e2ea8017-bb4b-48b0-beda-e71fee353774 v5 table 82. Fuse failure supervision vdspvc function range or value accuracy operate value, block of main fuse failure (10.0-80.0)% of ubase ±0.5% of ur reset ratio operate time, block of main fuse failure at 1 x u r to 0 min. = 5 ms – max. = 15 ms reset ti...

  • Page 92

    Control m12359-1 v15 table 83. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r rese...

  • Page 93

    Semod175215-2 v14 table 84. Tap changer control tcmyltc/tclyltc function range or value accuracy tap position for lowest and highest voltage (1–63) - ma for lowest and highest voltage tap position (0.000–25.000) ma - type of code conversion bin, bcd, gray, single, ma - time after position change bef...

  • Page 94

    Logic m12380-1 v12 table 85. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater evolv...

  • Page 95

    Guid-d1179280-1d99-4a66-91ac-b7343dba9f23 v2 table 92. Number of and instances logic block quantity with cycle time 3 ms 8 ms 100 ms and 60 60 160 guid-45df373f-dc39-4e1b-b45b-6b454e8e0e50 v2 table 93. Number of gate instances logic block quantity with cycle time 3 ms 8 ms 100 ms gate 10 10 20 guid-...

  • Page 96

    Guid-c6c98fe0-f559-45ee-b853-464516775417 v2 table 100. Number of timerset instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms timerset 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms guid-0b07f78c-10bd-4070-aff0-6ee36454aa03 v1 table 101. Number of xor instances logic ...

  • Page 97

    Guid-61263951-53a8-4113-82b5-3db3bf0d9449 v1 table 108. Number of pulsetimerqt instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms pulsetimerqt - 10 30 (0.000–90000.000) s ±0.5% ±10 ms guid-94c803b4-6c5a-4072-ab5c-20dde98c9a70 v1 table 109. Number of rsmemoryqt in...

  • Page 98

    Guid-19810098-1820-4765-8f0b-7d585ffc0c78 v7 table 113. Number of instances in the extension logic package logic block quantity with cycle time 3 ms 8 ms 100 ms slgapc 10 10 54 vsgapc 10 10 100 and 40 40 100 or 40 40 100 pulsetimer 20 20 49 gate — — 49 timerset 30 30 49 xor 10 10 69 lld — — 49 srmem...

  • Page 99

    Table 118. Integratortigapc function cycle time (ms) range of value accuracy time integration continuous active 3 0-999999.99 s ±0.2% or ±20 ms whichever is greater time integration continuous active 8 0-999999.99 s ± 0.2% or ±50 ms whichever is greater table 118. Integratortigapc , continued functi...

  • Page 100

    Monitoring m12386-1 v15 table 124. Power system measurement cvmmxn function range or value accuracy frequency (0.95-1.05) x f r ± 2.0 mhz voltage (10 to 300) v ± 0.3% of u at u ≤ 50 v ± 0.2% of u at u > 50 v current (0.1-4.0) x i r ± 0.8% of i at 0.1 x i r i 0.2 x i r ± 0.5% of i at 0.2 x i r i 0.5 ...

  • Page 101

    Guid-ed634b6d-9918-464f-b6a4-51b78129b819 v6 table 127. Voltage measurement phase-earth vnmmxu function range or value accuracy voltage (5 to 175) v ±0.5% of u at u ≤ 50 v ±0.2% of u at u > 50 v phase angle (5 to 175) v ±0.5 degrees at u ≤ 50 v ±0.2 degrees at u > 50 v guid-9b8a7fa5-9c98-4cbd-a162-7...

  • Page 102

    M12760-1 v10 table 131. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 167 maximum number of analog inp...

  • Page 103

    Guid-83b0f607-d898-403a-94fd-7fe8d45c73ff v7 table 133. Insulation supervision for liquid medium function ssiml function range or value accuracy oil alarm level 1.00-100.00 ±10.0% of set value oil lockout level 1.00-100.00 ±10.0% of set value temperature alarm level -40.00-200.00 ±2.5% of set value ...

  • Page 104

    M12700-1 v4 table 136. Event list function value buffer capacity maximum number of events in the list 1000 resolution 1 ms accuracy depending on time synchronizing m13765-1 v5 table 137. Indications function value buffer capacity maximum number of indications presented for single disturbance 352 max...

  • Page 105

    Guid-f5e124e3-0b85-41ac-9830-a2362fd289f2 v1 table 142. Running hour-meter teilgapc function range or value accuracy time limit for alarm supervision, talarm (0 - 99999.9) hours ±0.1% of set value time limit for warning supervision, twarning (0 - 99999.9) hours ±0.1% of set value time limit for over...

  • Page 106

    Metering m13404-2 v5 table 143. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - semod153707-2 v5 table 144. Function for energy calculation and demand handling etpmmtr function range or val...

  • Page 107

    Station communication m15031-1 v8 table 145. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–115200 bd protocol tc...

  • Page 108

    M12589-1 v4 table 150. Slm – lon port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (1000m/3000 ft typically *) plastic fiber: 7 db (10m/35ft typically *) fiber diameter glass fiber: 62.5/125 m m plastic fiber...

  • Page 109

    Remote communication m12756-1 v10 table 154. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fiber graded-index multimode 62.5/125 µm graded-index multimode 50/125 µm singlemode 9/125 µm singlemode 9/125 µm peak emi...

  • Page 110

    Hardware ied semod53385-1 v1 m11778-1 v6 table 155. Case material steel sheet front plate stainless steel with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) m12327-1 v4 table 156. Water and dust protection level according to iec 60529 front ip40 (ip54 with se...

  • Page 111

    Connections, one blank slot is necessary between two adjacent io modules. Please refer to the ordering particulars for details. Guid-96676d5d-0835-44da-bc22-058fd18bdf34 v2 table 161. Num: communication ports num 4 ethernet ports 1 basic, 3 optional ethernet connection type sfp optical lc or galvani...

  • Page 112

    Injection equipment hardware guid-edf13da3-4658-4a20-8641-cd62f6c3be0f v3 table 163. Injection unit rex060 specifications values case size 6u, 1/2 19”; 223.7 x 245 x 267 mm (w x d x h) weight 8.0 kg burden, binary inputs bi 220 v: burden 0.4 w bi 110 v: burden 0.2 w bi 48 v: burden 0.1 w burden, rim...

  • Page 113

    Guid-e7b9192f-abd5-4395-94f2-ed0b2f0dfeb7 v3 table 165. Shunt resistor unit rex062 specifications values case size 218 x 150 x 243 mm (w x d x h) weight 4.5 kg assembling 6 x 5 mm screws (3 at bottom and 3 at top) rated stator injection voltage 240 v rated stator voltage 240 v burden, injection x1:2...

  • Page 114

    Basic ied functions m11963-1 v5 table 166. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out m12331-1 v8 table 167. Time synchronization, time tagging function value time tagging accuracy of the synchrophasor da...

  • Page 115

    Semod141136-2 v8 table 171. Irig-b quantity rated value number of channels irig-b 1 number of optical channels 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00...

  • Page 116

    Inverse characteristic m12388-1 v21 table 172. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en-us i = i ...

  • Page 117

    Table 173. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 3.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater iec normal i...

  • Page 118

    Guid-19f8e187-4ed0-48c3-92f6-0d9eaa2b39bb v3 table 175. Ansi inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us re...

  • Page 119

    Table 176. Iec inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 2.00 1.5 x i set ≤ i ≤ 20 x i ...

  • Page 120

    Guid-2ae8c92e-5da8-487f-927d-8e553ee29240 v1 table 178. Ansi inverse time characteristics for voltage restrained time overcurrent protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristi...

  • Page 121

    Semod116978-2 v10 table 180. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: ...

  • Page 122

    Table 181. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en-us u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + ×...

  • Page 123

    Table 182. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 3...

  • Page 124

    24. Ordering for customized ied guid-0076b561-1ff1-4a89-ac04-df53a413e2af v7 table 183. General guidelines guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be us...

  • Page 125

    Table 188. Differential functions function function identification ordering no position available qty selected qty notes and rules transformer differential protection, two winding t2wpdif 1mrk005904-fc 4 0-2 transformer differential protection, three winding t3wpdif 1mrk005904-gb 5 0-2 high impedanc...

  • Page 126

    Table 193. Voltage protection position 1 2 3 4 5 6 7 8 d 0 0 table 194. Voltage functions function function identification ordering no position available qty selected qty notes and rules two step undervoltage protection uv2ptuv 1mrk005912-aa 1 0-2 two step overvoltage protection ov2ptov 1mrk005912-b...

  • Page 127

    Table 203. Control position 1 2 3 4 5 6 7 8 9 10 11 h 0 0 0 0 0 0 0 table 204. Control functions function function identification ordering no position available qty selected qty notes and rules synchrocheck, energizing check and synchronizing sesrsyn 1mrk005917-xd 2 0-2 control functionality for up ...

  • Page 128

    Table 212. Language selection language ordering no selection notes and rules first local hmi user dialogue language hmi language, english iec 1mrk002930-aa b1 additional local hmi user dialogue language no additional hmi language x0 hmi language, english us 1mrk002920-ub a12 selected b1 table 213. C...

  • Page 129

    Table 217. Analog system selection analog system ordering no selection notes and rules when more than one trm is selected, the connector type on both trms must be the same (a compression or b ring lug). Slot position (front view/rear view) p40/x401 p41/x411 no transformer input module included x0 x0...

  • Page 130

    Table 218. Maximum quantity of i/o modules, with compression terminals when ordering i/o modules, observe the maximum quantities according to the tables below. Note: standard order of location for i/o modules is bim-bom-som-iom-mim from left to right as seen from the rear side of the ied, but can al...

  • Page 131

    Table 220. Binary input/output module selection binary input/ output modules ordering no selection notes and rules slot position (front view/rear view) p3/x31 p4/x41 p5/x51 p6/x61 p7/x71 p8/x81 p9/x91 p10/x101 p11/x111 p12/x121 p13/x131 p14/x141 p15/x151 p16/x161 1/2 case with 1 trm █ █ █ these blac...

  • Page 132

    Table 220. Binary input/output module selection, continued binary input/ output modules ordering no selection notes and rules iom 8 inputs, 10+2 outputs, rl110, 110-125vdc, 50ma 1mrk000173-be n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 iom 8 inputs, 10+2 outputs, rl220, 220-250vdc, 50ma 1mrk000173-ce ...

  • Page 133

    Table 221. Station communication, remote end serial communication and time synchronization selection station communication, remote end serial communication and time synchronization ordering no selection notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 ...

  • Page 134

    25. Ordering for pre-configured ied guid-44ac94a2-c927-463b-bb10-f4c476745d03 v11 guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or...

  • Page 135

    Language ordering no #4 notes and rules first local hmi user dialogue language hmi language, english iec 1mrk002930-aa b1 additional local hmi user dialogue language no additional hmi language x0 hmi language, english us 1mrk002920-ub a12 selection for position #4 b1 casing ordering no #5 notes and ...

  • Page 136

    Analog system ordering no #9 notes and rules when more than one trm is selected, the connector type on both trms must be the same (a compression or b ring lug). Slot position (front view/rear view) p40/x401 p41/x411 no transformer input module included x0 x0 only valid if iec 61850-9-2 process bus c...

  • Page 137

    Binary input/output modules ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1bim and 1 bom required in slots p3 and p4. Slot position (front/rear view) p3/x31 p4/x41 p5/x51 p6/x61 p7/x71 p8/x81 p9/x91...

  • Page 138

    Station communication, remote end serial communication and time synchronization ordering no #11 notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 p30:5/x305 p30:6/x306 p30:6:1/x3061 p30:6:2/x3062 p31:1/x311 p31:2/x312 p31:3/x313 p32:2/x322 p32:3/x323 ld...

  • Page 139

    26. Ordering for accessories accessories ip15151-1 v1 gps antenna and mounting details m12374-3 v5 gps antenna, including mounting kits quantity: 1mrk 001 640-aa cable for antenna, 20 m (appx. 65 ft) quantity: 1mrk 001 665-aa cable for antenna, 40 m (appx. 131 ft) quantity: 1mrk 001 665-ba interface...

  • Page 140

    External resistor unit semod120228-4 v8 high impedance resistor unit with resistor and voltage dependent resistor 20-100v, 1ph quantity: 1 2 3 rk 795 101-ma high impedance resistor unit with resistor and voltage dependent resistor 20-100v, 3ph quantity: rk 795 101-mb high impedance resistor unit wit...

  • Page 141

    Injection equipment guid-3447c871-562c-46b4-a36c-0b8b62d38e48 v7 rule: if injection equipment is ordered, rotiphiz or sttiphizsensitive rotor earth fault protection, injection based (option b31) or 100% stator earth fault protection, injection based (option b32) is required in the ied. Injection uni...

  • Page 142

    Combiflex ip15161-1 v1 key switch for settings semod130356-4 v6 key switch for lock-out of settings via lhmi quantity: 1mrk 000 611-a note: to connect the key switch, leads with 10 a combiflex socket on one end must be used. Semod130267-5 v6 mounting kit ordering number side-by-side mounting kit qua...

  • Page 143

    User documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 502 071-uen ansi quantity: 1mrk 502 071-uus technical manual iec quantity: 1mrk 502 072-uen ansi quantity: 1mrk 502 072-uus commissioning manual iec quantity: 1mrk 502 073-uen ansi quantity...

  • Page 144

    Ansi quantity: 1mrk 511 398-uus cyber security deployment guideline iec quantity: 1mrk 511 399-uen application guide, communication set-up iec quantity: 1mrk 505 382-uen reference information m2175-3 v4 for our reference and statistics we would be pleased to be provided with the following applicatio...

  • Page 145

    145.

  • Page 146

    — abb ab grid automation products 721 59 västerås, sweden phone: +46 (0) 21 32 50 00 abb.Com/protection-control © copyright 2017 abb. All rights reserved. Specifications subject to change without notice. 1mrk 502 0 74-ben.