ABB Relion RES670 Product Manual

Manual is about: Relion 670 Series, Phasor measurement unit

Summary of Relion RES670

  • Page 1

    Relion® 670 series — phasor measurement unit res670 version 2.2 product guide.

  • Page 2

    Contents 1. Application..................................................................... 3 2. Available functions..........................................................9 3. Impedance protection...................................................19 4. Wide area measurement system..................

  • Page 3

    1. Application guid-cf75762e-73c1-40af-8d6f-6ec3d8395982 v4 res670 is a phasor measurement unit (pmu) that provides power system ac voltages and currents as phasors for all voltage levels in power system networks. Phasors are provided as real and imaginary or as magnitude and phase angle. The refere...

  • Page 4

    Central account management is an authentication infrastructure that offers a secure solution for enforcing access control to ieds and other systems within a substation. This incorporates management of user accounts, roles and certificates and the distribution of such, a procedure completely transpar...

  • Page 5

    Sa ptuf 81u f sa ptof 81 f> uv2 ptuv 27 2(3u v mmxu met u res670 a20 – phasor measurement unit, 3 bays, single busbar, 12ai (9i+3u) drp rdre dfr/ser dr wa1_vt ccs spvc 87 ind/i oos ppam 78 ucos other functions available from the function library optional functions sde psde 67n in> q cbay 3 control s...

  • Page 6

    Description of configuration b20 guid-e8a586f6-e450-4b5e-af00-1dc9a197a2a6 v4 the configuration of the ied is shown in figure 3 . Res670 b20 configuration is applicable for a typical double busbar single breaker arrangement monitoring up to six bays. Res670 b20 is delivered in ¾, and full (1/1)19" r...

  • Page 7

    Sa ptuf 81u f sa ptuf 81 f sa ptof 81o f> sa ptof 81 f> uv2 ptuv 27 2(3u ov2 ptov 59 2(3u>) v msqi met usqi v mmxu met u res670 b20 – phasor measurement unit, 6 bays, double busbar, 24ai (9i+3u, 9i+3u) drp rdre dfr/ser dr wa1_vt c mmxu met i c msqi met isqi wa1 wa2 cv mmxn met p/q sa pfrc 81 df/dt s...

  • Page 8

    In pcm600. The ied can be adapted to special applications and special logic can be developed, such as logic for automatic opening of disconnectors and closing of ring bays, automatic load transfer from one busbar to the other, and so on. The basic ied configuration is provided with the signal matrix...

  • Page 9

    2. Available functions guid-f5776dd1-bd04-4872-bb89-a0412b4b5cc3 v1 the following tables list all the functions available in the ied. Those functions that are not exposed to the user or do not need to be configured are not described in this manual. Wide area measurement functions guid-8a114d7e-8d1a-...

  • Page 10

    Back-up protection functions guid-a8d0852f-807f-4442-8730-e44808e194f0 v13 iec 61850 or function name ansi function description phasor measurement unit res670 (customized) res670 (a20) res670 (b20) impedance protection zmrpsb 68 power swing detection 0-1 1-b23 1-b23 oosppam 78 out-of-step protection...

  • Page 11

    Control and monitoring functions guid-e3777f16-0b76-4157-a3bf-0b6b978863de v16 iec 61850 or function name ansi function description phasor measurement unit res670 (customized) res670 (a20) res670 (b20) control qcbay bay control 1 1 1 locrem handling of lr-switch positions 1 1 1 locremctrl lhmi contr...

  • Page 12

    Iec 61850 or function name ansi function description phasor measurement unit res670 (customized) res670 (a20) res670 (b20) wrncalh logic for group warning 5 5 5 indcalh logic for group indication 5 5 5 and, gate, inv, lld, or, pulsetimer, rsmemory, srmemory, timerset, xor basic configurable logic bl...

  • Page 13

    Table 1. Total number of instances for basic configurable logic blocks basic configurable logic block total number of instances and 280 gate 40 inv 420 lld 40 or 298 pulsetimer 40 rsmemory 40 srmemory 40 timerset 60 xor 40 table 2. Total number of instances for configurable logic blocks q/t configur...

  • Page 14

    Table 3. Total number of instances for extended logic package extended configurable logic block total number of instances and 180 gate 49 inv 180 lld 49 or 180 pulsetimer 89 rsmemory 40 slgapc 74 srmemory 130 timerset 109 vsgapc 120 xor 89 1mrk 511 410-ben b phasor measurement unit res670 2.2 produc...

  • Page 15

    Iec 61850 or function name ansi function description phasor measurement unit res670 (customized) res670 (a20) res670 (b20) monitoring cvmmxn power system measurement 6 6 6 cmmxu current measurement 10 10 10 vmmxu voltage measurement phase-phase 6 6 6 cmsqi current sequence measurement 6 6 6 vmsqi vo...

  • Page 16

    Iec 61850 or function name ansi function description phasor measurement unit res670 (customized) res670 (a20) res670 (b20) metering pcfcnt pulse-counter logic 16 16 16 etpmmtr function for energy calculation and demand handling 6 6 6 1mrk 511 410-ben b phasor measurement unit res670 2.2 product vers...

  • Page 17

    Communication guid-5f144b53-b9a7-4173-80cf-cd4c84579cb5 v16 iec 61850 or function name ansi function description phasor measurement unit res670 (customized) res670 (a20) res670 (b20) station communication lonspa, spa spa communication protocol 1 1 1 ade lon communication protocol 1 1 1 horzcomm netw...

  • Page 18

    Iec 61850 or function name ansi function description phasor measurement unit res670 (customized) res670 (a20) res670 (b20) rchlcch access point diagnostic for redundant ethernet ports 3 3 3 qualexp iec 61850 quality expander 96 96 96 remote communication binsignrec1_1 binsignrec1_2 binsignreceive2 b...

  • Page 19

    Table 5. Local hmi functions iec 61850 or function name ansi description lhmictrl local hmi signals language local human machine language screen local hmi local human machine screen behavior fnkeyty1–fnkeyty5 fnkeymd1– fnkeymd5 parameter setting function for hmi in pcm600 ledgen general led indicati...

  • Page 20

    Synchrophasor frame format. The pmureport block contains parameters for pmu performance class and reporting rate, the idcode and global pmu id, format of the data streamed through the protocol, the type of reported synchrophasors, as well as settings for reporting analog and digital signals. The mes...

  • Page 21

    For operating quantity with maintained short circuit capacity. There is also available one nondirectional 3i0 step and one 3u0 overvoltage tripping step. No specific sensitive current input is needed. Sensitive directional residual overcurrent and power protection (sdepsde) can be set as low 0.25% o...

  • Page 22

    Rate-of-change of frequency protection sapfrc m14965-3 v13 the rate-of-change of frequency protection function (sapfrc ) gives an early indication of a main disturbance in the system. Sapfrc measures frequency with high accuracy, and can be used for generation shedding, load shedding and remedial ac...

  • Page 23

    11. Control circuit breaker sxcbr m13489-3 v6 the purpose of circuit breaker (sxcbr) is to provide the actual status of positions and to perform the control operations, that is, pass all the commands to primary apparatuses in the form of circuit breakers via binary output boards and to supervise the...

  • Page 24

    According to the specific application needs for settable pulse or steady output. Group alarm logic function almcalh guid-16e60e27-f7a8-416d-8648-8174aac49bb5 v4 the group alarm logic function (almcalh) is used to route several alarm signals to a common indication, led and/or contact, in the ied. Gro...

  • Page 25

    • pulsetimerqt pulse timer function block can be used, for example, for pulse extensions or limiting of operation of outputs. The function also propagates the time stamp and the quality of the input signal. • rsmemoryqt function block is a flip-flop that can reset or set an output from two inputs re...

  • Page 26

    Supervision of ma input signals m16054-3 v2 the main purpose of the function is to measure and process signals from different measuring transducers. Many devices used in process control represent various parameters such as frequency, temperature and dc battery voltage as low current values, usually ...

  • Page 27

    Actions) and long perspective (for example functional analysis). The disturbance recorder acquires sampled data from selected analog and binary signals connected to the disturbance recorder function (maximum 40 analog and 352 binary signals). The binary signals available are the same as for the even...

  • Page 28

    14. Metering pulse-counter logic pcfcnt m13394-3 v7 pulse-counter logic (pcfcnt) function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy consumption values. The pulses are captured by the binary input module and then rea...

  • Page 29

    Only gps and irig-b (optical irig-b 00x is recommended), with ieee1344 support, are the acceptable time synchronization sources for synchrophasor measurement applications and res670 supports both. M11345-3 v11 precision time protocol ptp ptp according to ieee 1588-2008 and specifically its profile i...

  • Page 30

    Front port. Iec 61850-8-1 protocol allows intelligent electrical devices (ieds) from different vendors to exchange information and simplifies system engineering. Ied-to-ied communication using goose and client-server communication over mms are supported. Disturbance recording file (comtrade) uploadi...

  • Page 31

    Ied commands for iec 60870-5-103 i103iedcmd i103iedcmd is a command block in control direction with defined ied functions. All outputs are pulsed and they are not stored. Pulse-time is a hidden parameter. Function commands user-defined for iec 60870-5-103 i103usrcmd i103usrcmd is a command block in ...

  • Page 32

    Binary output module bom m6938-3 v4 the binary output module has 24 independent output relays and is used for trip output or any signaling purpose. Static binary output module som semod174196-4 v4 the static binary output module has six fast static outputs and six change over output relays for use i...

  • Page 33

    Iec06000182-2-en.Vsd iec06000182 v2 en-us figure 9. A 1/2 x 19” size ied side-by-side with rhgs6. M15243-12 v9 case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8.81 242.1/ 9.53 255.8/ 10.07 205.7/ 8.10 190.5/ 7.50 203.7/ 8.02 - 228.6/ 9.00 - 6u, 3/4 x 19” 265.9/ 10.47 33...

  • Page 34

    21. Connection diagrams guid-cf4effa5-3081-4fc7-9a14-ed127c3c0fde v7 the connection diagrams are delivered in the ied connectivity package as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/protection-control . Connection diagram...

  • Page 35

    22. Technical data general ip11376-1 v2 m10993-1 v3 definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the ...

  • Page 36

    Energizing quantities, rated values and limits analog inputs ip15842-1 v1 m16988-1 v11 table 6. Trm - energizing quantities, rated values and limits for protection transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1 or 5 a...

  • Page 37

    Table 7. Trm - energizing quantities, rated values and limits for measuring transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1a 5 a operating range (0-1.8) × i r (0-1.6) × i r thermal withstand 80 × i r for 1 s 25 × i r f...

  • Page 38

    Binary inputs and outputs ip15844-1 v1 m12576-1 v11 table 10. Bim - binary input module quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v, 50 ma 48/60 v, 50 ma 110/125 v, 50 ma 220/25...

  • Page 39

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. The stated operate time for functions include the operating time for the binary inputs and outputs. M12573-1 v10 table 12. Iom - binary input/output module quantity rated value nominal ra...

  • Page 40

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. The stated operate time for functions include the operating time for the binary inputs and outputs. M12318-1 v9 table 13. Iom - binary input/output module contact data (reference standard...

  • Page 41

    The stated operate time for functions include the operating time for the binary inputs and outputs. M12584-1 v9 table 14. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary...

  • Page 42

    The stated operate time for functions include the operating time for the binary inputs and outputs. Semod175395-2 v8 table 15. Som - static output module (reference standard: iec 61810-2): static binary outputs function of quantity static binary output trip rated voltage 48-60 vdc 110-250 vdc number...

  • Page 43

    The stated operate time for functions include the operating time for the binary inputs and outputs. M12441-1 v9 table 17. Bom - binary output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays binary outputs 24 max system voltage 250 v ac, dc test volta...

  • Page 44

    Table 19. Auxiliary dc supply voltage influence on functionality during operation dependence on reference value within nominal range influence ripple, in dc auxiliary voltage operative range max. 2% full wave rectified 15% of el 0.01%/% auxiliary voltage dependence, operate value ±20% of el 0.01%/% ...

  • Page 45

    Table 21. Electromagnetic compatibility test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-26 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv iec 61000-4-12, class iv surge withstand capabilit...

  • Page 46

    Table 23. Environmental tests test type test value reference standard cold operation test test ad for 16 h at -25°c iec 60068-2-1 cold storage test test ab for 16 h at -40°c iec 60068-2-1 dry heat operation test test bd for 16 h at +70°c iec 60068-2-2 dry heat storage test test bb for 16 h at +85°c ...

  • Page 47

    Impedance protection m16036-1 v10 table 26. Power swing detection zmrpsb function range or value accuracy reactive reach (0.10-3000.00) w /phase ±2.0% static accuracy conditions: voltage range: (0.1-1.1) x u r current range: (0.5-30) x i r angle: at 0 degrees and 85 degrees resistive reach (0.10–100...

  • Page 48

    Wide area measurement system guid-f0baebd8-e361-4d50-9737-7df8b043d66a v4 the ied is compliant with the synchrophasor measurement requirements of ieee c37.118.1-2011, including the amendment (ieee c37.118.1a-2014) for both p and m performance classes. The ied is also compliant with synchrophasor dat...

  • Page 49

    Current protection m12342-1 v21 table 28. Directional phase overcurrent protection, four steps oc4ptoc function range or value accuracy operate current, step 1-4 (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - minimum operate current, ste...

  • Page 50

    M15223-1 v17 table 29. Directional residual overcurrent protection, four steps ef4ptoc function range or value accuracy operate current, step 1-4 (1-2500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - relay characteristic angle (rca) (-180 to 180)...

  • Page 51

    Guid-e83ad807-8fe0-4244-a50e-86b9af92469e v6 table 30. Four step directional negative phase sequence overcurrent protection ns4ptoc function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase -...

  • Page 52

    Semod173350-2 v16 table 31. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cos j directional residual overcurrent (0.25-200.00)% of ibase ±1.0% of i r at i £ i r ±1.0% of i at i > i r operate level for ·3i 0 ·3u 0 cos ...

  • Page 53

    M12352-1 v15 table 32. Thermal overload protection, one time constant lcpttr/lfpttr function range or value accuracy reference current (2-400)% of ibase ±1.0% of i r reference temperature (0-300)°c, (0 - 600)°f ± 1.0°c, ±2.0°f operate time: 2 2 2 2 ln p trip amb ref ref i i t t t i i t σ , , , √ equ...

  • Page 54

    Semod175159-2 v9 table 34. Directional overpower protection goppdop function range or value accuracy power level for step 1 and step 2 (0.0–500.0)% of sbase ±1.0% of s r at s ≤ s r ±1.0% of s at s > s r characteristic angle for step 1 and step 2 (-180.0–180.0) degrees ±2.0 degrees operate time, star...

  • Page 55

    Voltage protection m13290-1 v15 table 35. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ...

  • Page 56

    M13304-1 v14 table 36. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time charac...

  • Page 57

    Frequency protection m13360-1 v15 table 37. Underfrequency protection saptuf function range or value accuracy operate value, start function, at symmetrical three phase voltage (35.00-75.00) hz ±2.0 mhz operate time, start at f set + 0.02 hz to f set - 0.02 hz fn = 50 hz min. = 80 ms - max. = 95 ms f...

  • Page 58

    M14976-1 v10 table 39. Rate-of-change of frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ±10.0 mhz/s operate value, restore enable frequency (45.00-65.00) hz ±2.0 mhz definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whicheve...

  • Page 59

    Multipurpose protection m13095-2 v10 1mrk 511 410-ben b phasor measurement unit res670 2.2 product version: 2.2 abb 59.

  • Page 60

    Table 41. General current and voltage protection cvgapc function range or value accuracy measuring current input phase1, phase2, phase3, posseq, - negseq, -3*zeroseq, maxph, minph, unbalanceph, phase1-phase2, phase2-phase3, phase3-phase1, maxph-ph, minph-ph, unbalanceph- ph - measuring voltage input...

  • Page 61

    Table 41. General current and voltage protection cvgapc , continued function range or value accuracy independent time delay, overvoltage at 0.8 x u set to 1.2 x u set , step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater independent time delay, undervoltage at 1.2 x u set to 0.8 x u s...

  • Page 62

    Table 41. General current and voltage protection cvgapc , continued function range or value accuracy undervoltage: critical impulse time 10 ms typically at 1.2 x u set to 0.8 x u set - impulse margin time 15 ms typically - 1mrk 511 410-ben b phasor measurement unit res670 2.2 product version: 2.2 62...

  • Page 63

    Secondary system supervision m12358-1 v10 table 42. Current circuit supervision ccsspvc function range or value accuracy operate current (10-200)% of ibase ±10.0% of i r at i ≤ i r ±10.0% of i at i > i r reset ratio, operate current >90% block current (20-500)% of ibase ±5.0% of i r at i ≤ i r ±5.0%...

  • Page 64

    Control 1mrk 511 410-ben b phasor measurement unit res670 2.2 product version: 2.2 64 abb.

  • Page 65

    Scheme communication 1mrk 511 410-ben b phasor measurement unit res670 2.2 product version: 2.2 abb 65.

  • Page 66

    Logic m12380-1 v13 table 44. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater evolv...

  • Page 67

    Guid-d1179280-1d99-4a66-91ac-b7343dba9f23 v3 table 51. Number of and instances logic block quantity with cycle time 3 ms 8 ms 100 ms and 60 60 160 guid-45df373f-dc39-4e1b-b45b-6b454e8e0e50 v3 table 52. Number of gate instances logic block quantity with cycle time 3 ms 8 ms 100 ms gate 10 10 20 guid-...

  • Page 68

    Guid-c6c98fe0-f559-45ee-b853-464516775417 v3 table 59. Number of timerset instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms timerset 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms guid-0b07f78c-10bd-4070-aff0-6ee36454aa03 v2 table 60. Number of xor instances logic bl...

  • Page 69

    Guid-61263951-53a8-4113-82b5-3db3bf0d9449 v1 table 67. Number of pulsetimerqt instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms pulsetimerqt - 10 30 (0.000–90000.000) s ±0.5% ±10 ms guid-94c803b4-6c5a-4072-ab5c-20dde98c9a70 v1 table 68. Number of rsmemoryqt inst...

  • Page 70

    Guid-19810098-1820-4765-8f0b-7d585ffc0c78 v7 table 72. Number of instances in the extension logic package logic block quantity with cycle time 3 ms 8 ms 100 ms slgapc 10 10 54 vsgapc 10 10 100 and 40 40 100 or 40 40 100 pulsetimer 20 20 49 gate — — 49 timerset 30 30 49 xor 10 10 69 lld — — 49 srmemo...

  • Page 71

    Guid-b258726e-1129-47c9-94f9-be634a2085fa v4 table 77. Elapsed time integrator with limit transgression and overflow supervision teigapc function cycle time (ms) range or value accuracy elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is greater 8 0 ~ 999999.9 s ±0.2% or ±100 ms w...

  • Page 72

    Monitoring m12386-1 v16 table 81. Power system measurement cvmmxn function range or value accuracy frequency (0.95-1.05) x f r ± 2.0 mhz voltage (10 to 300) v ± 0.3% of u at u ≤ 50 v ± 0.2% of u at u > 50 v current (0.1-4.0) x i r ± 0.8% of i at 0.1 x i r i 0.2 x i r ± 0.5% of i at 0.2 x i r i 0.5 x...

  • Page 73

    Guid-ed634b6d-9918-464f-b6a4-51b78129b819 v6 table 84. Voltage measurement phase-earth vnmmxu function range or value accuracy voltage (5 to 175) v ±0.5% of u at u ≤ 50 v ±0.2% of u at u > 50 v phase angle (5 to 175) v ±0.5 degrees at u ≤ 50 v ±0.2 degrees at u > 50 v guid-9b8a7fa5-9c98-4cbd-a162-71...

  • Page 74

    M12760-1 v11 table 88. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 116 maximum number of analog inpu...

  • Page 75

    Guid-83b0f607-d898-403a-94fd-7fe8d45c73ff v8 table 90. Insulation supervision for liquid medium function ssiml function range or value accuracy oil alarm level 1.00-100.00 ±10.0% of set value oil lockout level 1.00-100.00 ±10.0% of set value temperature alarm level -40.00-200.00 ±2.5% of set value t...

  • Page 76

    M12702-1 v4 table 94. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance reports 100 resolution 1 ms accuracy depending on time synchronizing m13747-1 v5 table 95. Trip value recorder function value buffer capacity maximum n...

  • Page 77

    Metering m13404-2 v5 table 99. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - semod153707-2 v5 table 100. Function for energy calculation and demand handling etpmmtr function range or valu...

  • Page 78

    Station communication m15031-1 v9 table 101. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–115200 bd protocol tc...

  • Page 79

    Table 105. Sfp - galvanic rj45 quantity rated value number of channels up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol standard ieee 802.3u 100base-tx type of cable cat5e ftp connector type rj45 communication speed fast ethernet 100 m...

  • Page 80

    Hardware ied semod53385-1 v1 m11778-1 v7 table 107. Case material steel sheet front plate stainless steel with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) m12327-1 v5 table 108. Water and dust protection level according to iec 60529 front ip40 (ip54 with se...

  • Page 81

    Connections, one blank slot is necessary between two adjacent io modules. Please refer to the ordering particulars for details. Guid-96676d5d-0835-44da-bc22-058fd18bdf34 v3 table 113. Num: communication ports num 4 ethernet ports 1 basic, 3 optional ethernet connection type sfp optical lc or galvani...

  • Page 82

    Basic ied functions m11963-1 v5 table 115. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out m12331-1 v9 table 116. Time synchronization, time tagging function value time tagging accuracy of the synchrophasor da...

  • Page 83

    Semod141136-2 v9 table 120. Irig-b quantity rated value number of channels irig-b 1 number of optical channels 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00...

  • Page 84

    Inverse characteristic m12388-1 v23 table 121. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k i = + ⋅ − equation1249-small v3 en-us reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en-us i = i measured /i set 0.05 ≤ k ≤ ...

  • Page 85

    Table 122. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.05 ≤ k ≤ 999.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater iec normal...

  • Page 86

    Table 123. Ri and rd type inverse time characteristics function range or value accuracy ri type inverse characteristic 1 0.236 0.339 = × - t k i equation1137-small v1 en-us i = i measured /i set 0.05 ≤ k ≤ 999.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater rd typ...

  • Page 87

    Table 125. Iec inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.05 ≤ k ≤ 2.00 1.5 x i set ≤ i ≤ 20 x i ...

  • Page 88

    Semod116978-2 v10 table 127. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: ...

  • Page 89

    Table 128. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en-us u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + ×...

  • Page 90

    Table 129. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 3...

  • Page 91

    23. Ordering for customized ied guid-b35852ab-adb2-42e0-ba3a-55203ebb5c70 v7 table 130. General guidelines guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be us...

  • Page 92

    Table 135. Impedance protection position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 table 136. Impedance functions function function identification ordering no position available qty selected qty notes and rules power swing ...

  • Page 93

    Table 144. Multipurpose functions function function identification ordering no position available qty selected qty notes and rules general current and voltage protection cvgapc 1mrk005915-aa 1 0–8 table 145. General calculation position 1 s table 146. General calculation functions function function ...

  • Page 94

    Table 156. Station communication functions function function identification ordering no position available qty selected qty notes and rules iec 61850-9-2 process bus communication, 8 merging units 1mrk005933-ha 1 0–1 iec 62439-3 parallel redundancy protocol prp 1mrk005932-fa 2 0–1 prp or hsr require...

  • Page 95

    Table 160. Power supply module selection power supply module ordering no selection notes and rules compression terminals 1mrk002960-ga c ringlug terminals 1mrk002960-ha r power supply module 24-60 vdc 1mrk002239-ab a power supply module 90-250 vdc 1mrk002239-bb b selected table 161. Human machine in...

  • Page 96

    Table 163. Maximum quantity of i/o modules, with compression terminals when ordering i/o modules, observe the maximum quantities according to the tables below. Note: standard order of location for i/o modules is bim-bom-som-iom-mim from left to right as seen from the rear side of the ied, but can al...

  • Page 97

    Table 165. Binary input/output module selection binary input/ output modules ordering no selection notes and rules slot position (front view/rear view) p3/x31 p4/x41 p5/x51 p6/x61 p7/x71 p8/x81 p9/x91 p10/x101 p11/x111 p12/x121 p13/x131 p14/x141 p15/x151 p16/x161 1/2 case with 1 trm █ █ █ these blac...

  • Page 98

    Table 165. Binary input/output module selection, continued binary input/ output modules ordering no selection notes and rules iom 8 inputs, 10+2 outputs, rl110, 110-125vdc, 50ma 1mrk000173-be n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 iom 8 inputs, 10+2 outputs, rl220, 220-250vdc, 50ma 1mrk000173-ce ...

  • Page 99

    Table 166. Station communication and time synchronization selection station communication and time synchronization ordering no selection notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 p30:5/x305 p30:6/x306 p30:6:1/x3061 p30:6:2/x3062 p31:2/x312 p31:3...

  • Page 100

    24. Ordering for pre-configured ied guid-d8264d89-2a4a-4af6-a68f-b3ca1c5cdc5c v7 guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or ...

  • Page 101

    Language ordering no #4 notes and rules first local hmi user dialogue language hmi language, english iec 1mrk002930-aa b1 additional local hmi user dialogue language no additional hmi language x0 hmi language, english us 1mrk002920-ub a12 selection for position #4 b1 casing ordering no #5 notes and ...

  • Page 102

    Analog system ordering no #9 notes and rules when more than one trm is selected, the connector type on both trms must be the same (a compression or b ring lug). Slot position (front view/rear view) p40/x401 p41/x411 no transformer input module included x00 x00 only valid if iec 61850-9-2 process bus...

  • Page 103

    Binary input/ output modules ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1bim and 1 bom required in positions p3 and p4 slot position (front view/rear view) p3/x31 p4/x41 p5/x51 p6/x61 p7/x71 p8/x...

  • Page 104

    Binary input/ output modules ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1bim and 1 bom required in positions p3 and p4 iom 8 inputs, 10+2 outputs, rl110, 110-125vdc, 50ma 1mrk000173-be n1 n1 n1 n...

  • Page 105

    Station communication and time synchronization ordering no #11 notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 p30:5/x305 p30:6/x306 p30:6:1/x3061 p30:6:2/x3062 p31:2/x312 p31:3/x313 p32:2/x322 p32:3/x323 ldcm mode available slots in 1/2, 3/4 and 1/1 ...

  • Page 106

    25. Ordering for accessories accessories ip15151-1 v1 gps antenna and mounting details m12374-3 v5 gps antenna, including mounting kits quantity: 1mrk 001 640-aa cable for antenna, 20 m (appx. 65 ft) quantity: 1mrk 001 665-aa cable for antenna, 40 m (appx. 131 ft) quantity: 1mrk 001 665-ba test swit...

  • Page 107

    Configuration and monitoring tools ip15162-1 v2 m15042-3 v4 front connection cable between lhmi and pc quantity: 1mrk 001 665-ca semod131414-4 v3 led label special paper a4, 1 pc quantity: 1mrk 002 038-ca led label special paper letter, 1 pc quantity: 1mrk 002 038-da manuals m15161-3 v14 note: one (...

  • Page 108

    User documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 511 407-uen ansi quantity: 1mrk 511 407-uus technical manual iec quantity: 1mrk 511 408-uen ansi quantity: 1mrk 511 408-uus commissioning manual iec quantity: 1mrk 511 409-uen ansi quantity...

  • Page 109

    Ansi quantity: 1mrk 511 398-uus cyber security deployment guideline iec quantity: 1mrk 511 399-uen application guide, communication set-up iec quantity: 1mrk 505 382-uen reference information m2175-3 v4 for our reference and statistics we would be pleased to be provided with the following applicatio...

  • Page 110

    110

  • Page 111

    — abb ab grid automation products 721 59 västerås, sweden phone: +46 (0) 21 32 50 00 abb.Com/protection-control © copyright 2017 abb. All rights reserved. Specifications subject to change without notice. 1mrk 511 41 0-ben.