Summary of Relion 670 series

  • Page 1

    Relion ® 670 series phasor measurement unit res670 ansi customized product guide.

  • Page 2

    Contents 1. Application.........................................................................4 2. Available functions.............................................................5 3. Wide area measurement system........................................8 4. Current protection..........................

  • Page 3

    Phasor measurement unit res670 ansi 1mrk511254-bus b customized product version: 1.2 issued: february 2015 revision: b abb 3.

  • Page 4

    1. Application gateway printer events printer wan / lan substation lan c37.118 s1 s2 s3 s4 station pdc cc res670 res670 gps satellite iec11000408_1_en.Eps guid-13f439fc-6ab6-4ed0-a629-ebc8f984b447 v1 en figure 1. Pmus in a substation res 670 is a phasor measurement unit that provides power system ac...

  • Page 5

    2. Available functions wide area measurement functions iec 61850 ansi function description phasor measurement unit res670 pmuconf configuration parameters for ieee1344 and c37.118 protocol 1 pmureport protocol reporting via ieee1344 and c37.118 1 back-up protection functions iec 61850 ansi function ...

  • Page 6

    Control and monitoring functions iec 61850 ansi function description phasor measurement unit res670 control qcbay apparatus control 1 locrem handling of lrswitch positions 1 locremctr l lhmi control of psto 1 slggio logic rotating switch for function selection and lhmi presentation 15 vsggio selecto...

  • Page 7

    Iec 61850 ansi function description phasor measurement unit res670 bsstatreport logical signal status report 3 range_xp measured value expander block 66 metering pcggio pulse-counter logic 16 etpmmtr function for energy calculation and demand handling 6 designed to communicate iec 61850 ansi functio...

  • Page 8

    Basic ied functions iec 61850 function description basic functions included in all products interrorsig self supervision with internal event list 1 time time and synchronization error 1 timesynch time synchronization 1 activegroup parameter setting groups 1 test test mode functionality 1 changelock ...

  • Page 9

    Protocol reporting via ieee 1344 and c37.118 pmureport the phasor measurement reporting block moves the phasor calculations into a c37.118 frame which contains data about pmu configuration, analog values, binary signal indications and information about time synchronization quality. The message gener...

  • Page 10

    There is also available one nondirectional 3i0 step and one 3v0 overvoltage tripping step. No specific sensitive current input is needed.Sdepsde can be set as low 0.25% of ibase. Thermal overload protection, one time constant lpttr the increasing utilizing of the power system closer to the thermal l...

  • Page 11

    7. Multipurpose protection general current and voltage protection cvgapc the general current and voltage protection (cvgapc) can be utilized as a negative sequence current protection detecting unsymmetrical conditions such as open phase or unsymmetrical faults. Cvgapc can also be used to improve pha...

  • Page 12

    Bring in commands from remote (scada) to those parts of the logic configuration that do not need extensive command receiving functionality (for example, scswi). In this way, simple commands can be sent directly to the ied outputs, without confirmation. Confirmation (status) of the result of the comm...

  • Page 13

    Supervision of ma input signals the main purpose of the function is to measure and process signals from different measuring transducers. Many devices used in process control represent various parameters such as frequency, temperature and dc battery voltage as low current values, usually in the range...

  • Page 14

    The trip value recorder information is an integrated part of the disturbance record (comtrade file). Disturbance recorder drprdre the disturbance recorder function supplies fast, complete and reliable information about disturbances in the power system. It facilitates understanding system behavior an...

  • Page 15

    • status indication leds. • alarm indication leds, which consist of 15 leds (6 red and 9 yellow) with user printable label. All leds are configurable from pcm600. • liquid crystal display (lcd). • keypad with push buttons for control and navigation purposes, switch for selection between local and re...

  • Page 16

    Ma input module mim the milli-ampere input module is used to interface transducer signals in the –20 to +20 ma range from for example oltc position, temperature or pressure transducers. The module has six independent, galvanically separated channels. Optical ethernet module oem the optical fast-ethe...

  • Page 17

    Mounting alternatives • 19” rack mounting kit • flush mounting kit with cut-out dimensions: – 1/2 case size (h) 10.01 inches (w) 8.27 inches – 1/1 case size (h) 10.01 inches (w) 17.11 inches • wall mounting kit see ordering for details about available mounting alternatives. Phasor measurement unit r...

  • Page 18

    17. Connection diagrams table 1. Designations for 1/1 x 19” casing with 2 trm slots 1mrk002801-ac-6-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x131 and x132 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, r...

  • Page 19

    Table 2. Ct/vt-input designation current/voltage configuration (50/60 hz) ai01 ai02 ai03 ai04 ai05 ai06 ai07 ai08 ai09 ai10 ai11 ai12 12i, 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 12i, 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 9i+3v, 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 110-220v 110-220v 110-220v 9i+3v, 5a 5a 5...

  • Page 20

    1mrk002802-ab-11-670-1.2-pg-ansi v1 en figure 6. Binary input module (bim). Input contacts named xa corresponds to rear position x31, x41, etc. And input contacts named xb to rear position x32, x42, etc. 1mrk002802-ab-12-670-1.2-pg-ansi v1 en figure 7. Binary output module (bom). Output contacts nam...

  • Page 21

    1mrk002802-ab-8-670-1.2-pg-ansi v1 en figure 11. Ied with basic functionality communication interfaces phasor measurement unit res670 ansi 1mrk511254-bus b customized product version: 1.2 abb 21.

  • Page 22

    18. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 23

    Table 4. Trm - energizing quantities, rated values and limits for measuring transformer modules quantity rated value nominal range current i n = 1 or 5 a (0-1.8) × i n at i n = 1 a (0-1.6) × i n at i n = 5 a permissive overload 1.1 × i n cont. 1.8 × i n for 30 min at i n = 1 a 1.6 × i n for 30 min a...

  • Page 24

    Auxiliary dc voltage table 7. Psm - power supply module quantity rated value nominal range auxiliary dc voltage, el (input) el = (24 - 60) v el = (90 - 250) v el ± 20% el ± 20% power consumption 50 w typically - auxiliary dc power in-rush - binary inputs and outputs table 8. Bim - binary input modul...

  • Page 25

    Table 9. Bim - binary input module with enhanced pulse counting capabilities quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v 48/60 v 125 v 220/250 v max. 0.05 w/input max. 0.1 w/input m...

  • Page 26

    Table 11. Som - static output module data (reference standard: iec 61810-2): electromechanical relay outputs function of quantity trip and signal relays max system voltage 250v ac/dc number of outputs 6 test voltage across open contact, 1 min 1000v rms current carrying capacity: continuous 8a 1.0s 1...

  • Page 27

    Influencing factors table 13. Temperature and humidity influence parameter reference value nominal range influence ambient temperature, operate value +20 °c -10 °c to +55 °c 0.02% /°c relative humidity operative range 10%-90% 0%-95% 10%-90% - storage temperature -40 °c to +70 °c - - table 14. Auxili...

  • Page 28

    Type tests according to standards table 16. Electromagnetic compatibility test type test values reference standards 1 mhz oscillatory burst disturbance 2.5 kv iec 60255-22-1 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv ie...

  • Page 29

    Table 18. Environmental tests test type test value reference standard cold test test ad for 16 h at -25°c iec 60068-2-1 storage test test ad for 16 h at -40°c iec 60068-2-1 dry heat test test bd for 16 h at +70°c iec 60068-2-2 damp heat test, steady state test ca for 4 days at +40 °c and humidity 93...

  • Page 30

    Wide area measurement system table 21. Protocol reporting via ieee 1344 and c37.118 pmureport influencing quantity range accuracy signal frequency ± 0.1 x f r ≤ 1.0% tve signal magnitude: voltage phasor current phasor (0.1–1.2) x v n (0.5–2.0) x i n phase angle ± 180° harmonic distortion 10% from 2n...

  • Page 31

    Current protection table 22. Four step phase overcurrent protection oc4ptoc (51/67) function setting range accuracy trip current (5-2500)% of lbase ± 1.0% of i n at i ≤ i n ± 1.0% of i at i > i n reset ratio > 95% at (50–2500)% of lbase - min. Operating current (1-10000)% of lbase ± 1.0% of i n at i...

  • Page 32

    Table 23. Four step residual overcurrent protection ef4ptoc (51n/67n) function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i n at i n ± 1.0% of i at i > i n reset ratio > 95% - operate current for directional comparison (1–100)% of lbase ± 1.0% of i n timers (0.000-60.000) s...

  • Page 33

    Table 24. Four step negative sequence overcurrent protection ns4ptoc (46i2) function range or value accuracy operate value, negative sequence current, step 1-4 (1-2500)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio > 95% - timers (0.000-60.000) s ± 0.5% ± 10 ms inverse charac...

  • Page 34

    Table 25. Sensitive directional residual overcurrent and power protection sdepsde (67n) function range or value accuracy operate level for 3i 0 ·cosj directional residual overcurrent (0.25-200.00)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n at low setting: (0.25-1.00)% of i n : ±0.05% ...

  • Page 35

    Table 25. Sensitive directional residual overcurrent and power protection sdepsde (67n) , continued function range or value accuracy reset time, non-directional residual over current 60 ms typically at 2 to 0 x i set - operate time, pickup function 150 ms typically at 0 to 2 x i set - reset time, pi...

  • Page 36

    Voltage protection table 27. Two step undervoltage protection uv2ptuv (27) function range or value accuracy operate voltage, low and high step (1–100)% of vbase ± 0.5% of v n absolute hysteresis (0–100)% of vbase ± 0.5% of v n internal blocking level, step 1 and step 2 (1–100)% of vbase ± 0.5% of v ...

  • Page 37

    Frequency protection table 29. Underfrequency protection saptuf (81) function range or value accuracy operate value, pickup function (35.00-75.00) hz ± 2.0 mhz operate time, pickup function 100 ms typically - reset time, pickup function 100 ms typically - operate time, definite time function (0.000-...

  • Page 38

    Table 31. Rate-of-change frequency protection sapfrc (81) function range or value accuracy operate value, pickup function (-10.00-10.00) hz/s ± 10.0 mhz/s operate value, internal blocking level (0-100)% of vbase ± 0.5% of v n operate time, pickup function 100 ms typically - phasor measurement unit r...

  • Page 39

    Multipurpose protection table 32. General current and voltage protection cvgapc function range or value accuracy measuring current input phase a, phase b, phase c, posseq, negseq, 3*zeroseq, maxph, minph, unbalanceph, phase a-phase b, phase b-phase c, phase c-phase a, maxph- ph, minph-ph, unbalancep...

  • Page 40

    Table 32. General current and voltage protection cvgapc , continued function range or value accuracy reset time pickup undervoltage 25 ms typically at 0 to 2 x v set - high and low voltage limit, voltage dependent operation (1.0 - 200.0)% of vbase ± 1.0% of v n for v n ± 1.0% of v for v>v n directio...

  • Page 41

    Secondary system supervision table 33. Current circuit supervision ccsrdif (87) function range or value accuracy operate current (5-200)% of i n ± 10.0% of i n at i £ i n ± 10.0% of i at i > i n block current (5-500)% of i n ± 5.0% of i n at i £ i n ± 5.0% of i at i > i n table 34. Fuse failure supe...

  • Page 42

    Logic table 35. Tripping logic smpptrc (94) function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms timers (0.000-60.000) s ± 0.5% ± 10 ms table 36. Configurable logic blocks logic block quantity with cycle time range or value a...

  • Page 43

    Monitoring table 37. Measurements cvmmxn function range or value accuracy voltage (10 to 300) v ± 0.3% of v at ≤ 50 v ± 0.2% of v at v > 50 v current (0.1-4.0) × i n ± 0.8% of i at 0.1 × i n n ± 0.5% of i at 0.2 × i n n ± 0.2% of i at 0.5 × i n n active power, p (10 to 300) v (0.1–4.0) x i n ± 0.5% ...

  • Page 44

    Table 40. Phase-neutral voltage measurement vnmmxu function range or value accuracy voltage (10 to 300) v ± 0.3% of v at v ≤ 50 v ± 0.2% of v at v > 50 v phase angle (10 to 300) v ± 0.3° at v ≤ 50 v ± 0.2° at v > 50 v table 41. Current sequence component measurement cmsqi function range or value acc...

  • Page 45

    Table 44. Event counter cntggio function range or value accuracy counter value 0-100000 - max. Count up speed 10 pulses/s (50% duty cycle) - table 45. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - m...

  • Page 46

    Table 48. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance reports 100 resolution 1 ms accuracy depending on time synchronizing table 49. Trip value recorder function value buffer capacity maximum number of analog inputs 3...

  • Page 47

    Metering table 51. Pulse counter pcggio function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - table 52. Energy metering etpmmtr function range or value accuracy energy metering kwh export/import, kvarh export/ import input...

  • Page 48

    Station communication table 53. Iec 61850-8-1 communication protocol function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 608–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–19200 bd protocol tcp/i...

  • Page 49

    Hardware ied table 56. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) table 57. Water and dust protection level according to iec 60529 front ip40 (ip54 with sealing strip) sides, top and bottom ip2...

  • Page 50

    Basic ied functions table 61. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out table 62. Time synchronization, time tagging function value time tagging resolution, events and sampled measurement values 1 ms tim...

  • Page 51

    Table 65. Irig-b quantity rated value number of channels irig-b 1 number of channels pps 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00x, irig-b 12x accuracy...

  • Page 52

    Inverse characteristic table 66. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) = + × - æ ö ç ÷ ç ÷ è ø 1 p a t b td i equation1651 v1 en reset characteristic: ( ) = × - 2 1 tr t td i equation1652 v1 en i = i measured /i set td = (0.05-999) in steps ...

  • Page 53

    Table 67. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) = × - æ ö ç ÷ ç ÷ è ø 1 p a t td i equation1653 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 - time delay to reset, iec inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms i...

  • Page 54

    Table 68. Ri and rd type inverse time characteristics function range or value accuracy ri type inverse characteristic = × - 1 0.236 0.339 t td i equation1656 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 iec 60255-151, 5% + 40 ms rd type logarithmic inverse characteristic = - × æ ö ç ...

  • Page 55

    Table 70. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = - æ ö ç ÷ è ø td t vpickup v vpickup equation1658 v1 en v = v measured td = (0.05-1.10) in steps of 0.01 5% +40 ms type b curve: × = + - × - æ ö ç ÷ è ø 2.0 480 0.055 32 0.5 td t vpick...

  • Page 56

    19. Ordering guidelines carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Please refer to the available functions ta...

  • Page 57

    Current protection four step phase overcurrent protection (oc4ptoc, 51/67) qty: 1 2 3 4 5 6 7 8 1mrk 002 906-bd four step residual overcurrent protection (ef4ptoc, 51n/67n) qty: 1 2 1mrk 002 906-dd four step directional negative phase sequence overcurrent protection (ns4ptoc, 46i2) qty: 1mrk 002 906...

  • Page 58

    First local hmi user dialogue language rule: one must be ordered hmi language, english iec 1mrk 002 930-aa hmi language, english us 1mrk 002 930-ba optional hardware human machine hardware interface rule: one must be ordered. Display type keypad symbol case size medium, graphic display iec 1/1 19" 1...

  • Page 59

    Analog system note: the same type of connection terminals has to be ordered for both trms transformer input module, compression terminals 12i, 1a, 50/60 hz qty: 1 2 1mrk 002 247-cg transformer input module, compression terminals 12i, 5a, 50/60 hz qty: 1 2 1mrk 002 247-ch transformer input module, co...

  • Page 60

    Transformer input module, ring lug terminals 6i+6v, 5a, 50/60 hz qty: 1 2 1mrk 002 247-ad transformer input module, ring lug terminals 3i, 5a+3i, 1a+6v, 50/60 hz qty: 1 2 1mrk 002 247-af note: one analog digital conversion module, with time synchronization is always delivered with each transformer i...

  • Page 61

    Binary input/output modules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Binary input module (bim) 16 inputs rl 24-30 vdc, 50 ma qty: 1 2 3 4 5 6 7 8 9 10 11 1mrk 000 508-dd rl 48-60 vdc, 50 ma qty: 1 2 3 4 5 6 7 8 9 10 11 1mrk 000 508...

  • Page 62

    Binary output module 24 output relays (bom) qty: 1 2 3 4 5 6 7 8 9 10 11 1mrk 000 614-ab static binary output module (som) rl 48-60 vdc qty: 1 2 3 4 5 6 7 8 9 10 11 1mrk 002 614-ba rl 110-250 vdc qty: 1 2 3 4 5 6 7 8 9 10 11 1mrk 002 614-ca ma input module 6 channels (mim) qty: 1 2 3 4 1mrk 000 284-...

  • Page 63

    Gps antenna and mounting details gps antenna, including mounting kits quantity: 1mrk 001 640-aa cable for antenna, (appx. 65 ft) quantity: 1mrk 001 665-aa cable for antenna, (appx. 131 ft) quantity: 1mrk 001 665-ba test switch the test system combitest intended for use with the ied 670 products is d...

  • Page 64

    Manuals note: one (1) ied connect cd containing user documentation (operator’s manual, technical reference manual, installation and commissioning manual, application manual and getting started guide), connectivity packages and led label template is always included for each ied. Rule: specify additio...

  • Page 65

    Connection and installation components 1mrk 513 003-ben test system, combitest 1mrk 512 001-ben accessories for 670 series ieds 1mrk 514 012-ben 670 series spa and signal list 1mrk 500 092-wus iec 61850 data objects list for 670 series 1mrk 500 091-wus engineering manual 670 series 1mrk 511 240-uus ...

  • Page 66

    66.

  • Page 67

    Contact us abb inc. 1021 main campus drive raleigh, nc 27606, usa phone toll free: 1-800-help-365, menu option #8 abb inc. 3450 harvester road burlington, on l7n 3w5, canada phone toll free: 1-800-help-365, menu option #8 abb mexico s.A. De c.V. Paseo de las americas no. 31 lomas verdes 3a secc. 531...