ABB Relion 670 series Communication Protocol Manual

Manual is about: Transformer protection

Summary of Relion 670 series

  • Page 1

    Relion® 650 series — spa, 650 series version 2.2 communication protocol manual.

  • Page 3

    Document id: 1mrk 511 418-uen issued: october 2017 revision: a product version: 2.2.1 © copyright 2017 abb. All rights reserved.

  • Page 4

    Copyright this document and parts thereof must not be reproduced or copied without written permission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and...

  • Page 5

    Disclaimer the data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intende...

  • Page 6

    Conformity this product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagnetic compatibility (emc directive 2004/108/ec) and concerning electrical equipment for use within specified voltage limits (low-...

  • Page 7

    Table of contents section 1 introduction.......................................................................3 this manual........................................................................................ 3 intended audience.......................................................................

  • Page 8

    Fibre optic loop............................................................................26 optical budget calculation for serial communication with spa/iec ..................................................................................... 26 section 7 spa functions...............................

  • Page 9

    Section 1 introduction 1.1 this manual guid-ab423a30-13c2-46af-b7fe-a73bb425eb5f v18 the communication protocol manual describes the communication protocols supported by the ied. The manual concentrates on the vendor-specific implementations. 1.2 intended audience guid-c9b8127f-5748-4bea-9e4f-cc762f...

  • Page 10

    1.3 product documentation 1.3.1 product documentation set guid-3aa69ea6-f1d8-47c6-a8e6-562f29c67172 v15 iec07000220-4-en.Vsd p la n n in g & p u rc h a se e n gi n e e rin g in st a lli n g c o m m is si o n in g o p e ra tio n m ai n te n a n ce d e co m m is si o n in g d e in st a lli n g & d is ...

  • Page 11

    Describes the process of testing an ied in a station which is not in service. The chapters are organized in the chronological order in which the ied should be commissioned. The relevant procedures may be followed also during the service and maintenance activities. The operation manual contains instr...

  • Page 12

    1.3.3 related documents guid-94e8a5ca-be1b-45af-81e7-5a41d34ee112 v5 documents related to reb650 document numbers application manual 1mrk 505 388-uen commissioning manual 1mrk 505 390-uen product guide 1mrk 505 391-ben technical manual 1mrk 505 389-uen type test certificate 1mrk 505 391-ten document...

  • Page 13

    Documents related to ret650 document numbers application manual 1mrk 504 169-uen commissioning manual 1mrk 504 171-uen product guide 1mrk 504 172-ben technical manual 1mrk 504 170-uen type test certificate 1mrk 504 172-ten 650 series manuals document numbers operation manual 1mrk 500 128-uen enginee...

  • Page 14

    The caution hot surface icon indicates important information or warning about the temperature of product surfaces. The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of ...

  • Page 15

    • the character ^ in front of an input/output signal name indicates that the signal name may be customized using the pcm600 software. • the character * after an input signal name indicates that the signal must be connected to another function block in the application configuration to achieve a valid...

  • Page 16

    10

  • Page 17

    Section 2 spa application 2.1 spa communication protocol ip14614-1 v1 2.1.1 application ip14785-1 v1 semod115767-5 v6 spa communication protocol is an alternative to iec 60870-5-103, and they use the same rear communication port. When communicating with a pc connected to the utility substation lan v...

  • Page 18

    Functionality semod115767-25 v2 the spa protocol v2.5 is an ascii-based protocol for serial communication. The communication is based on a master-slave principle, where the ied is a slave and the pc is the master. Only one master can be applied on each fibre optic loop. A program is required in the ...

  • Page 19

    Section 3 spa operation principle 3.1 operation principle ip14401-1 v3 m11880-3 v2 the spa bus uses an asynchronous serial communications protocol (1 start bit, 7 data bits + even parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For more information on recommended baud rate for each ty...

  • Page 20

    Function block spa address cnt_val spa address new_val pcfcnt:10 6-o-2842 6-o-2841 pcfcnt:11 6-o-2848 6-o-2847 pcfcnt:12 6-o-2854 6-o-2853 pcfcnt:13 6-o-2860 6-o-2859 pcfcnt:14 6-o-2866 6-o-2865 pcfcnt:15 6-o-2872 6-o-2871 pcfcnt:16 6-o-2878 6-o-2877 3.1.2.1 i/o modules m11880-16 v4 to read binary i...

  • Page 21

    Function block spa address cmd input spa address cmd output singlecmd1-cmd9 4-s-4647 5-o-519 singlecmd1-cmd10 4-s-4648 5-o-520 singlecmd1-cmd11 4-s-4649 5-o-521 singlecmd1-cmd12 4-s-4650 5-o-522 singlecmd1-cmdt13 4-s-4651 5-o-523 singlecmd1-cmd14 4-s-4652 5-o-524 singlecmd1-cmd15 4-s-4653 5-o-525 si...

  • Page 22

    Function block spa address cmd input spa address cmd output singlecmd3-cmd16 4-s-4720 5-o-558 singlecmd4-cmd1 4-s-4738 5-o-559 singlecmd4-cmd2 4-s-4739 5-o-560 singlecmd4-cmd3 4-s-4740 5-o-561 singlecmd4-cmd4 4-s-4741 5-o-562 singlecmd4-cmd5 4-s-4742 5-o-563 singlecmd4-cmd6 4-s-4743 5-o-564 singlecm...

  • Page 23

    Main menu/settings / ied settings / control / commands / single command or via parameter setting tool (pst). 3.1.2.3 event function event m11880-82 v6 the event function (event) sends time-tagged events to the station level (for example, operator workplace) over the station bus. On the station level...

  • Page 24

    3.1.2.4 connection of signals as events m11880-311 v5 signals coming from different protection and control functions and sent as events to the station level over the spa-bus (or lon-bus), are connected to the event function block as specified in figure 4 . Event block ^input1 ^input2 ^input3 ^input4...

  • Page 25

    Iec16000079-1-en.Vsd iec16000079 v1 en-us figure 5: rear view of 1/2 x 19” casing with 1 trm slot there are two types of io connectors: snap-in connector for plastic fibre cables and st/bayonet connector for glass fibre cables. The slm can be equipped with either type or connector or with a combinat...

  • Page 26

    Spa cannot be accessed via pcm600. When communicating between the local hmi and a pc, the only hardware required is a front-connection cable. Spa can be accessed via lhmi front only when using the field service tool access (fstaccs). Section 3 1mrk 511 418-uen a spa operation principle 20 650 series...

  • Page 27

    Section 4 spa settings 4.1 settings ip14403-1 v2 pid-6195-settings v5 table 4: spa non group settings (basic) name values (range) unit step default description slaveaddress 1 - 899 - 1 30 slave address baudrate 300 bd 1200 bd 2400 bd 4800 bd 9600 bd 19200 bd 38400 bd - - 9600 bd baudrate on serial l...

  • Page 28

    22.

  • Page 29

    Section 5 spa technical data 5.1 technical data ip14404-1 v1 m11901-1 v2 table 6: spa communication protocol function value protocol spa communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 bd slave number 1 to 899 1mrk 511 418-uen a section 5 spa technical data 650 series 2.2 iec 23 comm...

  • Page 30

    24.

  • Page 31

    Section 6 establishing connection and verifying the spa/iec communication 6.1 establishing connection and verifying the spa/iec communication ip371 v2 about this chapter this chapter contains instructions on how to establish connection and verify that the spa/iec communication operates as intended w...

  • Page 32

    6.1.2 verifying the communication m11735-77 v1 to verify that the rear communication with the sms/scs system is working, there are some different methods. Choose one of the following. 6.1.2.1 verifying spa communication m11735-81 v5 procedure 1. Use a spa-emulator and send “rf” to the ied. The answe...

  • Page 33

    Distance 1 km glass distance 25 m plastic losses in connection box, two contacts (1 db/contact) - 2 db margin for 2 repair splices (0.5 db/splice) 1 db - maximum total attenuation 11 db 7 db 1mrk 511 418-uen a section 6 establishing connection and verifying the spa/iec communication 650 series 2.2 i...

  • Page 34

    28.

  • Page 35

    Section 7 spa functions 7.1 event function event semod120002-1 v2 7.1.1 identification semod167950-2 v2 function description iec 61850 identification iec 60617 identification ansi/ieee c37.2 device number event function event s00946 v1 en-us - m12805-6 v11 when using a substation automation system w...

  • Page 36

    7.1.3 signals ip11335-1 v2 pid-4145-inputsignals v6 table 9: event input signals name type default description block boolean 0 block of function input1 group signal 0 input 1 input2 group signal 0 input 2 input3 group signal 0 input 3 input4 group signal 0 input 4 input5 group signal 0 input 5 input...

  • Page 37

    7.1.4 settings ip11336-1 v2 pid-4145-settings v6 table 10: event non group settings (basic) name values (range) unit step default description spachannelmask off channel 1-8 channel 9-16 channel 1-16 - - off spa channel mask lonchannelmask off channel 1-8 channel 9-16 channel 1-16 - - off lon channel...

  • Page 38

    Name values (range) unit step default description eventmask9 noevents onset onreset onchange autodetect - - autodetect reporting criteria for input 9 eventmask10 noevents onset onreset onchange autodetect - - autodetect reporting criteria for input 10 eventmask11 noevents onset onreset onchange auto...

  • Page 39

    Name values (range) unit step default description minrepintval13 0 - 3600 s 1 2 minimum reporting interval input 13 minrepintval14 0 - 3600 s 1 2 minimum reporting interval input 14 minrepintval15 0 - 3600 s 1 2 minimum reporting interval input 15 minrepintval16 0 - 3600 s 1 2 minimum reporting inte...

  • Page 40

    It is possible to define which part of the event function generates the events. This can be performed individually for communication types spachannelmask and lonchannelmask . For each communication type these settings are available: • off • channel 1-8 • channel 9-16 • channel 1-16 for lon communica...

  • Page 41

    7.2.3 minrepintval (1 - 16) m12811-29 v3 a time interval between cyclic events can be set individually for each input channel. This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cyclic communication. M12811-34 v1 it is important to set the time interva...

  • Page 42

    7.3.4 signals pid-4144-inputsignals v6 table 11: binstatrep input signals name type default description block boolean 0 block of function input1 boolean 0 single status report input 1 input2 boolean 0 single status report input 2 input3 boolean 0 single status report input 3 input4 boolean 0 single ...

  • Page 43

    7.3.5 settings pid-4144-settings v6 table 13: binstatrep non group settings (basic) name values (range) unit step default description t 0.0 - 60.0 s 0.1 10.0 time delay of function 7.3.6 operation principle guid-537921ca-82b9-4a02-bad1-67e3ac61ae96 v3 the logical signal status report (binstatrep) fu...

  • Page 44

    38.

  • Page 45

    Section 8 glossary 8.1 glossary m14893-1 v16 ac alternating current acc actual channel act application configuration tool within pcm600 a/d converter analog-to-digital converter adbs amplitude deadband supervision adm analog digital conversion module, with time synchronization ai analog input ansi a...

  • Page 46

    Cb circuit breaker cbm combined backplane module ccitt consultative committee for international telegraph and telephony. A united nations-sponsored standards body within the international telecommunications union. Ccm can carrier module ccvt capacitive coupled voltage transformer class c protection ...

  • Page 47

    Dfc data flow control dft discrete fourier transform dhcp dynamic host configuration protocol dip-switch small switch mounted on a printed circuit board di digital input dllb dead line live bus dnp distributed network protocol as per ieee std 1815-2012 dr disturbance recorder dram dynamic random acc...

  • Page 48

    Gcm communication interface module with carrier of gps receiver module gde graphical display editor within pcm600 gi general interrogation command gis gas-insulated switchgear goose generic object-oriented substation event gps global positioning system gsal generic security application gse generic s...

  • Page 49

    Ied intelligent electronic device iet600 integrated engineering tool i-gis intelligent gas-insulated switchgear iom binary input/output module instance when several occurrences of the same function are available in the ied, they are referred to as instances of that function. One instance of a functi...

  • Page 50

    Mvb multifunction vehicle bus. Standardized serial bus originally developed for use in trains. Ncc national control centre nof number of grid faults num numerical module oco cycle open-close-open cycle ocp overcurrent protection oltc on-load tap changer otev disturbance data recording initiated by o...

  • Page 51

    Rs422 a balanced serial interface for the transmission of digital data in point-to-point connections rs485 serial link according to eia standard rs485 rtc real-time clock rtu remote terminal unit sa substation automation sbo select-before-operate sc switch or push button to close scl short circuit l...

  • Page 52

    Tcp transmission control protocol. The most common transport layer protocol used on ethernet and the internet. Tcp/ip transmission control protocol over internet protocol. The de facto standard ethernet protocols incorporated into 4.2bsd unix. Tcp/ip was developed by darpa for internet working and e...

  • Page 53

    Phonetic alphabet stands for "z", which stands for longitude zero. Uv undervoltage wei weak end infeed logic vt voltage transformer 3i o three times zero-sequence current.Often referred to as the residual or the earth-fault current 3u o three times the zero sequence voltage. Often referred to as the...

  • Page 54

    48.

  • Page 55

    49.

  • Page 56

    — abb ab grid automation products 721 59 västerås, sweden phone: +46 (0) 21 32 50 00 abb.Com/protection-control © copyright 2017 abb. All rights reserved. Specifications subject to change without notice. 1mrk 511 418-uen.