Summary of RELION RET670

  • Page 1

    Relion ® 670 series transformer protection ret670 ansi pre-configured product guide.

  • Page 2

    Contents 1. Application.........................................................................3 2. Available functions.............................................................8 3. Differential protection.......................................................14 4. Current protection...............

  • Page 3

    1. Application ret670 provides fast and selective protection, monitoring and control for two- and three-winding transformers, autotransformers, generator- transformer units and shunt reactors. The transformer ied is designed to operate correctly over a wide frequency range in order to accommodate po...

  • Page 4

    The wide application flexibility makes this product an excellent choice for both new installations and the refurbishment of existing installations. Three packages have been defined for the following applications: • two-winding transformer in single breaker arrangements (a30a) • two-winding transform...

  • Page 5

    Trip bkr3 trip bkr1 50bf 87n 51p 51g 87n 87t 50bf 51g 51p/67p 94 49 bkr 3 bkr 1 ct1 ct3 ct6 ct7 wdg1 wdg2 vt’s from wdg 2 side of xfrm ret 670 51n 51n/67n 59p 27p 59n 60f ansi10000087-2-en.Vsd 24 94 ansi10000087 v2 en figure 1. A typical protection application for a two winding transformer in single...

  • Page 6

    Trip bkr3 94/86 87n 50/51p 87n 27p 59p 50/51g 50/51p bkr1 60 49 50bf2 50bf1 50bf4 50bf3 vt’s from mv side of xfrm trip bkr1 94/86 trip bkr2 94/86 trip bkr4 94/86 trip from 50-bf1, 50-bf2 trip from 50-bf3, 50-bf4 50/51n 50/51n bkr2 bkr3 bkr4 ct1 ct2 ct3 ct4 ct6 ct7 wdg1 wdg2 59n 81u 81o 81r 24 87t 50...

  • Page 7

    87n 50/51p 27p 59p 50/51g 50/51p bkr1 60 49 50bf2 50bf1 50bf4 50bf3 vt’s from mv side of xfrm 94/86 trip from 50-bf1, 50-bf2 trip from 50-bf3, 50-bf4 50/51n 50/51n bkr2 bkr4 ct1 ct2 ct7 wdg1 wdg2 59n 50bf5 50/51p 94/86 trip bkr5 bkr3 ct3 ct4 wdg3 ct5 67p 24 94/86 trip bkr3 trip bkr4 94/86 trip bkr1 ...

  • Page 8

    2. Available functions main protection functions 2 = number of basic instances 3-a03 = optional function included in packages a03 (refer to ordering details) iec 61850 ansi function description transformer ret670 (a30a) ret670 (b30a) ret670 (b40a) differential protection t2wpdif 87t transformer diff...

  • Page 9

    Back-up protection functions iec 61850 ansi function description transformer ret670 (a30a) ret670 (b30a) ret670 (b40a) current protection oc4ptoc 51_67 four step phase overcurrent protection 2 2 3 ef4ptoc 51n_67 n four step residual overcurrent protection 2 2 3 ns4ptoc 46i2 four step directional neg...

  • Page 10

    Control and monitoring functions iec 61850 ansi function description transformer ret670 (a30a) ret670 (b30a) ret670 (b40a) control sesrsyn 25 synchrocheck, energizing check and synchronizing 1 1 1 apc30 3 apparatus control for up to 6 bays, max 30 apparatuses (6cbs) incl. Interlocking 1 1 1 qcbay ap...

  • Page 11

    Iec 61850 ansi function description transformer ret670 (a30a) ret670 (b30a) ret670 (b40a) configuration logic blocks 40-280 40-280 40-280 fixed signal function blocks 1 1 1 b16i boolean 16 to integer conversion 16 16 16 b16ifcvi boolean 16 to integer conversion with logic node representation 16 16 1...

  • Page 12

    Designed to communicate iec 61850 ansi function description transformer ret670 (a30a) ret670 (b30a) ret670 (b40a) station communication spa communication protocol 1 1 1 lon communication protocol 1 1 1 iec60870-5-103 communication protocol 20/1 20/1 20/1 operation selection between spa and iec60870-...

  • Page 13

    Basic ied functions iec 61850 function description basic functions included in all products interrorsig self supervision with internal event list 1 time time and synchronization error 1 timesynch time synchronization 1 activegroup parameter setting groups 1 test test mode functionality 1 changelock ...

  • Page 14

    3. Differential protection transformer differential protection t2wpdif/ t3wpdif (87t) the transformer differential protection, two-winding (t2wpdif, 87t) and transformer differential protection, three-winding (t3wpdif, 87t) are provided with internal ct ratio matching and phase shift compensation an...

  • Page 15

    Four step residual overcurrent protection, zero sequence and negative sequence direction ef4ptoc (51n_67n) the four step residual overcurrent protection ef4ptoc (51n/67n) has an inverse or definite time delay independent for each step separately. All iec and ansi time-delayed characteristics are ava...

  • Page 16

    5. Voltage protection two step undervoltage protection uv2ptuv (27) undervoltages can occur in the power system during faults or abnormal conditions. Two step undervoltage protection (uv2ptuv, 27) function can be used to open circuit breakers to prepare for system restoration at power outages or as ...

  • Page 17

    Generating plant, generator governor problems can also cause over frequency. Saptof (81) is used mainly for generation shedding and remedial action schemes. It is also used as a frequency stage initiating load restoring. Saptof (81) is provided with an undervoltage blocking. The operation is based o...

  • Page 18

    The fuse failure supervision function basically has three different algorithms, negative sequence and zero sequence based algorithms and an additional delta voltage and delta current algorithm. The negative sequence detection algorithm is recommended for ieds used in isolated or high- impedance grou...

  • Page 19

    With enhanced security, the command is processed and the resulting position is supervised. Normal security means that only the command is evaluated and the resulting position is not supervised. Enhanced security means that the command is evaluated with an additional supervision of the status value o...

  • Page 20

    Single command, 16 signals the ieds can receive commands either from a substation automation system or from the local hmi. The command function block has outputs that can be used, for example, to control high voltage apparatuses or for other user defined functionality. 10. Logic tripping logic smppt...

  • Page 21

    Signals from start of pre-fault time to the end of post-fault time will be included in the recording. Every disturbance report recording is saved in the ied in the standard comtrade format. The same applies to all events, which are continuously saved in a ring-buffer. The local hmi is used to get in...

  • Page 22

    Before the trigger instant can be saved in the disturbance file. The disturbance recorder information for up to 100 disturbances are saved in the ied and the local hmi is used to view the list of recordings. Event function when using a substation automation system with lon or spa communication, time...

  • Page 23

    • status indication leds. • alarm indication leds, which consist of 15 leds (6 red and 9 yellow) with user printable label. All leds are configurable from pcm600. • liquid crystal display (lcd). • keypad with push buttons for control and navigation purposes, switch for selection between local and re...

  • Page 24

    Multiple command and transmit when 670 ied's are used in substation automation systems with lon, spa or iec60870-5-103 communication protocols the event and multiple command function blocks are used as the communication interface for vertical communication to station hmi and gateway and as interface...

  • Page 25

    Evaluation of operation of the ied and for all associated electrical circuits. Binary output module bom the binary output module has 24 independent output relays and is used for trip output or any signaling purpose. Static binary output module som the static binary output module has six fast static ...

  • Page 26

    Resistor, is available in a single phase unit and a three phase unit. Both are mounted on a 1/1 19 inch apparatus plate with compression type terminals. Layout and dimensions dimensions xx05000003.Vsd c b e f a d iec05000003 v1 en figure 6. 1/2 x 19” case with rear cover xx05000004.Vsd iec05000004 v...

  • Page 27

    Case size a b c d e f 6u, 1/2 x 19” 10.47 8.81 7.92 9.53 9.96 8.10 6u, 3/4 x 19” 10.47 13.23 7.92 9.53 9.96 12.52 6u, 1/1 x 19” 10.47 17.65 7.92 9.53 9.96 16.94 (inches) mounting alternatives the following mounting alternatives are available (ip40 protection from the front): • 19” rack mounting kit ...

  • Page 28

    18. Connection diagrams table 1. Designations for 1/2 x 19” casing with 1 trm slot 1mrk002801-ac-2-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x51 and x52 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs48...

  • Page 29

    Table 2. Designations for 3/4 x 19” casing with 1 trm slot 1mrk002801-ac-3-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x101 and x102 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313 tr...

  • Page 30

    Table 3. Designations for 1/1 x 19” casing with 2 trm slots 1mrk002801-ac-6-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x131 and x132 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313, ...

  • Page 31

    1mrk002802-ab-10-670-1.2-pg-ansi v1 en figure 8. Transformer input module (trm) ■ indicates high polarity. See table 4 note that internal polarity can be adjusted by setting of analog input ct neutral direction and/or on smai pre- processing function blocks. Table 4. Ct/vt-input designation current/...

  • Page 32

    1mrk002802-ab-7-670-1.2-pg-ansi v1 en figure 9. Power supply module (psm) transformer protection ret670 ansi 1mrk 504 118-bus a pre-configured product version: 1.2 32 abb.

  • Page 33

    1mrk002802-ab-11-670-1.2-pg-ansi v1 en figure 10. Binary input module (bim). Input contacts named xa corresponds to rear position x31, x41, etc. And input contacts named xb to rear position x32, x42, etc. 1mrk002802-ab-12-670-1.2-pg-ansi v1 en figure 11. Binary output module (bom). Output contacts n...

  • Page 34

    1mrk002802-ab-8-670-1.2-pg-ansi v1 en figure 15. Ied with basic functionality communication interfaces transformer protection ret670 ansi 1mrk 504 118-bus a pre-configured product version: 1.2 34 abb.

  • Page 35

    189 289 189-open 289-open 289-cl bus a bus b to main 2 relay to bus prot trm1:1-3 trm1:11-12 trm1:4-6 to bus prot to main 2 relay trm1:10 en05000262_ansi.Vsd legend: bi – binary input bo – binary output cc – close coil tc – trip coil trm – ct, vt, input transformer module + bi 189b + bi 189a + bi 28...

  • Page 36

    Figure 16. Typical connection diagram for two winding transformer in a single breaker arrangement. Note! Including io for control option. Transformer protection ret670 ansi 1mrk 504 118-bus a pre-configured product version: 1.2 36 abb.

  • Page 37

    En05000263_ansi.Vsd 87b-trip bfi 3ph sudden pressure trip man sc ok f a u l t s ig n a l l in g - + irf wind temp warn hv 50bf oil temp trip wind temp trip oil temp warn oil low gas alarm ltc raise ltc lower ltc in loc. Ltc in man ltc in auto mv 50bf block lv 51p bi bi bi bi bi bi bi bi bi bi bi bi ...

  • Page 38

    En05000265_ansi.Vsd 87b-trip bfi 3ph sudden pressure trip man sc ok f a u l t s ig n a l l in g - + irf wind temp warn hv 50bf oil temp trip wind temp trip oil temp warn oil low gas alarm ltc raise ltc lower ltc in loc. Ltc in man ltc in auto mv 50bf block lv 51p bi bi bi bi bi bi bi bi bi bi bi bi ...

  • Page 39

    Figure 18. Typical connection diagram for three winding transformer in a single breaker arrangement. Note! Including io for control option. Transformer protection ret670 ansi 1mrk 504 118-bus a pre-configured product version: 1.2 abb 39.

  • Page 40

    189 6289 bus a to main 2 to bb prot trm2:7-9 trm2:1-3 to bus prot to main 2 relay trm1:11 trm2:4-6 trm1:1-3 689 6189 to main 2 989 trm1:4-6 = to second bay trm1:12 res. For bus 2 vt en05000259_ansi.Vsd 87b-trip bfi 3ph sudden pressure trip man sc ok f a u l t s ig n a l l in g - + irf wind temp warn...

  • Page 41

    19. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 42

    Table 6. Trm - energizing quantities, rated values and limits for measuring transformer modules quantity rated value nominal range current i n = 1 or 5 a (0-1.8) × i n at i n = 1 a (0-1.6) × i n at i n = 5 a permissive overload 1.1 × i n cont. 1.8 × i n for 30 min at i n = 1 a 1.6 × i n for 30 min a...

  • Page 43

    Auxiliary dc voltage table 9. Psm - power supply module quantity rated value nominal range auxiliary dc voltage, el (input) el = (24 - 60) v el = (90 - 250) v el ± 20% el ± 20% power consumption 50 w typically - auxiliary dc power in-rush - binary inputs and outputs table 10. Bim - binary input modu...

  • Page 44

    Table 11. Bim - binary input module with enhanced pulse counting capabilities quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v 48/60 v 125 v 220/250 v max. 0.05 w/input max. 0.1 w/input ...

  • Page 45

    Table 13. Iom - binary input/output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs 10 2 max system voltage 250 v ac, dc 250 v ac, dc test voltage across open contact, 1 min 1000 v rms 800 v dc ...

  • Page 46

    Table 14. Som - static output module (reference standard: iec 61810-2): static binary outputs function of quantity static binary output trip rated voltage 48 - 60 vdc 110 - 250 vdc number of outputs 6 6 impedance open state ~300 kΩ ~810 kΩ test voltage across open contact, 1 min no galvanic separati...

  • Page 47

    Table 15. Som - static output module data (reference standard: iec 61810-2): electromechanical relay outputs function of quantity trip and signal relays max system voltage 250v ac/dc number of outputs 6 test voltage across open contact, 1 min 1000v rms current carrying capacity: continuous 8a 1.0s 1...

  • Page 48

    Influencing factors table 17. Temperature and humidity influence parameter reference value nominal range influence ambient temperature, operate value +20 °c -10 °c to +55 °c 0.02% /°c relative humidity operative range 10%-90% 0%-95% 10%-90% - storage temperature -40 °c to +70 °c - - table 18. Auxili...

  • Page 49

    Type tests according to standards table 20. Electromagnetic compatibility test type test values reference standards 1 mhz oscillatory burst disturbance 2.5 kv iec 60255-22-1 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv ie...

  • Page 50

    Table 22. Environmental tests test type test value reference standard cold test test ad for 16 h at -25°c iec 60068-2-1 storage test test ad for 16 h at -40°c iec 60068-2-1 dry heat test test bd for 16 h at +70°c iec 60068-2-2 damp heat test, steady state test ca for 4 days at +40 °c and humidity 93...

  • Page 51

    Differential protection table 25. Transformer differential protection t2wpdif, t3wpdif (87t) function range or value accuracy operating characteristic adaptable ± 1.0% of in for i ± 1.0% of in for i > in reset ratio >95% - unrestrained differential current limit (100-5000)% of ibase on high voltage ...

  • Page 52

    Table 26. Restricted earth fault protection, low impedance refpdif (87n) function range or value accuracy operate characteristic adaptable ± 1.0% of i n for i n ± 1.0% of i for i > i n reset ratio >95% - base sensitivity function (4.0-100.0)% of ibase ± 1.0% of i n directional characteristic fixed 1...

  • Page 53

    Current protection table 27. Four step phase overcurrent protection oc4ptoc (51/67) function setting range accuracy operate current (1-2500)% of lbase ± 1.0% of i n at i ≤ i n ± 1.0% of i at i > i n reset ratio > 95% - min. Operating current (1-100)% of lbase ± 1.0% of i n at i ≤ i n ± 1.0% of i at ...

  • Page 54

    Table 28. Four step residual overcurrent protection ef4ptoc (51n/67n) function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio > 95% - operate current for directional comparison (1–100)% of lbase ± 1.0% of i n timers (0.000-60.00...

  • Page 55

    Table 29. Four step negative sequence overcurrent protection ns4ptoc (46i2) function range or value accuracy operate value, negative sequence current, step 1-4 (1-2500)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio > 95% - timers (0.000-60.000) s ± 0.5% ± 10 ms inverse charac...

  • Page 56

    Table 30. Thermal overload protection, two time constants trpttr (49) function range or value accuracy base current 1 and 2 (30–250)% of ibase ± 1.0% of i n operate time: 2 2 2 2 ln p b i i t i i t æ ö - ç ÷ = × ç ÷ - è ø equation1356 v1 en (equation 1) i = i measured i p = load current before overl...

  • Page 57

    Voltage protection table 33. Two step undervoltage protection uv2ptuv (27) function range or value accuracy operate voltage, low and high step (1–100)% of vbase ± 0.5% of v n absolute hysteresis (0–100)% of vbase ± 0.5% of v n internal blocking level, low and high step (1–100)% of vbase ± 0.5% of v ...

  • Page 58

    Table 35. Two step residual overvoltage protection rov2ptov (59n) function range or value accuracy operate voltage, low and high step (1-200)% of vbase ± 0.5% of v n at v n ± 1.0% of v at v > v n absolute hysteresis (0–100)% of vbase ± 0.5% of v n at v n ± 1.0% of v at v > v n inverse time character...

  • Page 59

    Table 37. Loss of voltage check lovptuv (27) function range or value accuracy operate voltage (0–100)% of vbase ± 0.5% of v n pulse timer (0.050–60.000) s ± 0.5% ± 10 ms timers (0.000–60.000) s ± 0.5% ± 10 ms transformer protection ret670 ansi 1mrk 504 118-bus a pre-configured product version: 1.2 a...

  • Page 60

    Frequency protection table 38. Underfrequency protection saptuf (81) function range or value accuracy operate value, pickup function (35.00-75.00) hz ± 2.0 mhz operate time, pickup function 100 ms typically - reset time, pickup function 100 ms typically - operate time, definite time function (0.000-...

  • Page 61

    Table 39. Overfrequency protection saptof (81) function range or value accuracy operate value, pickup function (35.00-75.00) hz ± 2.0 mhz at symmetrical three- phase voltage operate time, pickup function 100 ms typically at f set -0.5 hz to f set +0.5 hz - reset time, pickup function 100 ms typicall...

  • Page 62

    Multipurpose protection table 41. General current and voltage protection cvgapc function range or value accuracy measuring current input phase a, phase b, phase c, posseq, negseq, 3*zeroseq, maxph, minph, unbalanceph, phase a-phase b, phase b-phase c, phase c-phase a, maxph- ph, minph-ph, unbalancep...

  • Page 63

    Table 41. General current and voltage protection cvgapc , continued function range or value accuracy operate time, pickup overvoltage 25 ms typically at 0 to 2 x v set - reset time, pickup overvoltage 25 ms typically at 2 to 0 x v set - operate time pickup undervoltage 25 ms typically 2 to 0 x v set...

  • Page 64

    Secondary system supervision table 42. Current circuit supervision ccsrdif (87) function range or value accuracy operate current (5-200)% of i n ± 10.0% of i n at i £ i n ± 10.0% of i at i > i n block current (5-500)% of i n ± 5.0% of i n at i £ i n ± 5.0% of i at i > i n table 43. Fuse failure supe...

  • Page 65

    Control table 44. Synchronizing, synchronism check and energizing check sesrsyn (25) function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage ratio, v bus /v line (0.40-25.000) % of vbasebus and vbaseline - voltage high limit for synchronism check (50.0-120.0)% of...

  • Page 66

    Logic table 45. Tripping logic smpptrc (94) function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms timers (0.000-60.000) s ± 0.5% ± 10 ms table 46. Configurable logic blocks logic block quantity with cycle time range or value a...

  • Page 67

    Monitoring table 47. Measurements cvmmxn function range or value accuracy frequency (0.95-1.05) × f n ± 2.0 mhz connected current (0.2-4.0) × i n ± 0.5% of i n at i £ i n ± 0.5% of i at i > i n table 48. Supervision of ma input signals function range or value accuracy ma measuring function ± 5, ± 10...

  • Page 68

    Table 50. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 74 maximum number of analog inputs 30 + 10 (ex...

  • Page 69

    Table 53. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance reports 100 resolution 1 ms accuracy depending on time synchronizing table 54. Trip value recorder function value buffer capacity maximum number of analog inputs 3...

  • Page 70

    Metering table 56. Pulse counter pcggio function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - table 57. Energy metering etpmmtr function range or value accuracy energy metering kwh export/import, kvarh export/ import input...

  • Page 71

    Station communication table 58. Iec 61850-8-1 communication protocol function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx table 59. Lon communication protocol function value protocol lon communication speed 1.25 mbit/s table 60. Spa communication protocol function value ...

  • Page 72

    Table 63. Slm – spa/iec 60870-5-103/dnp3 port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (3000ft/1000 m typically *) plastic fiber: 7 db (80ft/25 m typically *) diameter glass fiber: 62.5/125 mm plastic fib...

  • Page 73

    Remote communication table 67. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fiber graded-index multimode 62.5/125 µm or 50/125 µm singlemode 9/125 µm singlemode 9/125 µm wave length 850 nm 1310 nm 1550 nm optical...

  • Page 74

    Hardware ied table 68. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) table 69. Water and dust protection level according to iec 60529 front ip40 (ip54 with sealing strip) rear, sides, top and bott...

  • Page 75

    Basic ied functions table 73. Self supervision with internal event list data value recording manner continuous, event controlled list size 1000 events, first in-first out table 74. Time synchronization, time tagging function value time tagging resolution, events and sampled measurement values 1 ms t...

  • Page 76

    Table 77. Irig-b quantity rated value number of channels irig-b 1 number of channels pps 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00x, irig-b 12x accuracy...

  • Page 77

    Inverse characteristic table 78. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) = + × - æ ö ç ÷ ç ÷ è ø 1 p a t b td i equation1651 v1 en reset characteristic: ( ) = × - 2 1 tr t td i equation1652 v1 en i = i measured /i set td = (0.05-999) in steps ...

  • Page 78

    Table 79. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) = × - æ ö ç ÷ ç ÷ è ø 1 p a t td i equation1653 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 - time delay to reset, iec inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms i...

  • Page 79

    Table 80. Ri and rd type inverse time characteristics function range or value accuracy ri type inverse characteristic = × - 1 0.236 0.339 t td i equation1656 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 iec 60255-3, class 5 + 40 ms rd type logarithmic inverse characteristic = - × æ ö...

  • Page 80

    Table 81. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - æ ö ç ÷ è ø t td v vpickup vpickup equation1661 v1 en v = v measured td = (0.05-1.10) in steps of 0.01 unless otherwise stated class 5 +40 ms type b curve: = × - × - - æ ö ç ÷ è ø 2.0...

  • Page 81

    Table 82. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = - æ ö ç ÷ è ø td t vpickup v vpickup equation1658 v1 en v = v measured td = (0.05-1.10) in steps of 0.01 unless otherwise stated class 5 +40 ms type b curve: × = + - × - æ ö ç ÷ è ø 2....

  • Page 82

    Table 83. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - æ ö ç ÷ è ø t td v vpickup vpickup equation1661 v1 en v = v measured td = (0.05-1.10) in steps of 0.01 class 5 +40 ms type b curve: = × - × - - æ ö ç ÷ è ø 2.0 480 32 0.5 0.0...

  • Page 83

    20. Ordering guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configur...

  • Page 84

    Casing #5 notes and rules 1/2 x 19" case a note: only for a30a 3/4 x 19" case 1trm slot b note: only for a30a 1/1 x 19" case 2 trm slots e note: only for b30a/b40a selection for position #5. Mounting details with ip40 of protection from the front #6 notes and rules no mounting kit included x 19" rac...

  • Page 85

    Binary input/output module, ma and time synchronization boards. Note: 1 bim and 1 bom included in a30a, 2 bim and 1 bom included in b30a/ b40a. #10 notes and rules make bim with 50 ma inrush current the primary choice. Bim with 50 ma inrush current fulfill additional standards. As a consequence the ...

  • Page 86

    Remote end communication, dnp serial comm. And time synchronization modules #11 notes and rules slot position (rear view) x312 x313 x302 x303 x322 x323 available slots in 1/2 case with 1 trm █ █ █ █ note: max 1 ldcm. Available slots in 3/4 case with 1 trm █ █ █ █ note: max 2 ldcm available slots in ...

  • Page 87

    Test switch the test system combitest intended for use with the ied 670 products is described in 1mrk 512 001-ben and 1mrk 001024-ca. Please refer to the website: www.Abb.Com/substationautomation for detailed information. Test switches type rtxp 24 is ordered separately. Please refer to section "rel...

  • Page 88

    Configuration and monitoring tools front connection cable between lcd-hmi and pc quantity: 1mrk 001 665-ca led label special paper a4, 1 pc quantity: 1mrk 002 038-ca led label special paper letter, 1 pc quantity: 1mrk 002 038-da manuals note: one (1) ied connect cd containing user documentation (ope...

  • Page 89

    Reference information for our reference and statistics we would be pleased to be provided with the following application data: country: end user: station name: voltage level: kv related documents documents related to ret670 identity number operator’s manual 1mrk 504 114-uus installation and commissi...

  • Page 90

    90

  • Page 91

    Contact us abb inc. 1021 main campus drive raleigh, nc 27606, usa phone toll free: 1-800-help-365, menu option #8 abb inc. 3450 harvester road burlington, on l7n 3w5, canada phone toll free: 1-800-help-365, menu option #8 abb mexico s.A. De c.V. Paseo de las americas no. 31 lomas verdes 3a secc. 531...