    Relion ® 670 series transformer protection ret670 2.0 product guide.

  • Page 2

    Contents 1. Application..................................................................... 3 2. Available functions........................................................10 3. Differential protection....................................................23 4. Impedance protection.......................

  • Page 3

    1. Application ret670 provides fast and selective protection, monitoring and control for two- and three-winding transformers, autotransformers, step-up transformers and generator- transformer block units, phase shifting transformers, special railway transformers and shunt reactors. The ied is design...

  • Page 4

    Description of configuration a30 ret670 a30 – 2 winding transformer in single breaker arrangement 12ai (9i+3u) w2_qa1 w1_qb2 w1_qb1 w1_qa1 w1 w2 ph pioc 50 3i>> oc4 ptoc 51 4(3i>) cc rbrf 50bf 3i>bf oc4 ptoc 51 3i> cc rbrf 50bf 3i>bf fuf spvc u>/i smp ptrc 94 1 → 0 etp mmtr met w/varh c msqi met isq...

  • Page 5

    Description of configuration b30 ret670 b30 - 2 winding transformer in multi breaker arrangement 24ai (9i+3u, 9i+3u) qb9 ph pioc 50 3i>> ef pioc 50n in>> w1_qb2 w1_qb1 tcm yltc 84 ↑↓ oc4 ptoc 51 4(3i>) cc rbrf 50bf 3i> bf w1_qa2 w1_qa1 qb61 qb62 cc rbrf 50bf 3i> bf cc pdsc 52pd pd c msqi met isqi c ...

  • Page 6

    Description of configuration a40 ret670 a40 – 3 winding transformer in single breaker arrangement 24ai (9i+3u, 9i+3u) w2_qa1 w1_qb2 w1_qb1 w3_qa1 w1_qa1 other functions available from the function library optional functions w1 w2 w3 ph pioc 50 3i>> oc4 ptoc 51 4(3i>) cc rbrf 50bf 3i>bf oc4 ptoc 51 4...

  • Page 7

    Description of configuration b40 ret670 b40 - 3 winding transformer in multi breaker arrangement 24ai (9i+3u, 9i+3u) qb9 ph pioc 50 3i>> ef pioc 50n in>> w1_qb2 w1_qb1 tcm yltc 84 ↑↓ oc4 ptoc 51 4(3i>) cc rbrf 50bf 3i> bf w1_qa2 w1_qa1 qb61 qb62 cc rbrf 50bf 3i> bf cc pdsc 52pd pd c msqi met isqi c ...

  • Page 8

    Description of configuration a10 ret670 a10 – transformer backup protection 12ai (9i+3u) w2_qa1 w1_qb2 w1_qb1 w3_qa1 w1_qa1 w1 w2 w3 ph pioc 50 3i>> oc4 ptoc 51 4(3i>) cc rbrf 50bf 3i>bf oc4 ptoc 51 4(3i>) cc rbrf 50bf 3i>bf oc4 ptoc 51 3i> cc rbrf 50bf 3i>bf smp ptrc 94 1 → 0 smp ptrc 94 1 → 0 c ms...

  • Page 9

    Description of configuration a25 ret670 a25 – voltage control 12ai (6i+6u) tcm yltc 84 ↑↓ c mmxu met i tcm yltc 84 ↑↓ drp rdre dfr/ser dr trf1_w2_qa1 qa11 ccs spvc 87 ind/i other functions available from the function library optional functions lov ptuv 27 3u etp mmtr met w/varh vdc ptov 60 ud> smp p...

  • Page 10

    2. Available functions main protection functions 2 = number of basic instances 0-3 = option quantities 3-a03 = optional function included in packages a03 (refer to ordering details) transformer protection ret670 2.0 1mrk 504 141-ben c product version: 2.0 10 abb.

  • Page 11

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) differential protection t2wpdif 87t transformer differential protection, two winding 1-2 1 1 t3wpdif 87t transformer differential protection, three winding 1-2 1 1 hzp...

  • Page 12

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) zmfpdis 21 high speed distance protection 0–1 zmfcpdis 21 high speed distance protection for series compensated lines 0–1 zmrpsb 68 power swing detection 0-1 1-b12 1-b...

  • Page 13

    Back-up protection functions iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) current protection phpioc 50 instantaneous phase overcurrent protection 0-8 3 2 2 3 3 2-c19 oc4ptoc 51_67 1) four step phase overcurrent p...

  • Page 14

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) rov2ptov 59n two step residual overvoltage protection 0-3 1-d01 1b 1-d01 1b 1-d01 1b 1-d02 1b 1-d02 2-d02 oexpvph 24 overexcitation protection 0-2 1-d03 1-d03 2-d04 2-...

  • Page 15

    Control and monitoring functions iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) control sesrsyn 25 synchrocheck, energizing check and synchronizing 0-6 1 1 1-b, 2- h01 1-b, 3- h02 1-b, 4- h03 apc30 3 apparatus cont...

  • Page 16

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) i103usrcmd function commands user defined for iec 60870-5-103 1 1 1 1 1 1 1 secondary system supervision ccsspvc 87 current circuit supervision 0-5 2 3 3 5 4 fufspvc f...

  • Page 17

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) teigapc elapsed time integrator with limit transgression and overflow supervision 12 12 12 12 12 12 12 monitoring cvmmxn, cmmxu, vmmxu, cmsqi, vmsqi, vnmmxu measuremen...

  • Page 18

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) i103superv supervison status for iec 60870-5-103 1 1 1 1 1 1 1 i103usrdef status for user defiend signals for iec 60870-5-103 20 20 20 20 20 20 20 l4ufcnt event counte...

  • Page 19

    Communication iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) station communication lonspa, spa spa communication protocol 1 1 1 1 1 1 1 ade lon communication protocol 1 1 1 1 1 1 1 horzcomm network variables via lo...

  • Page 20

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) goosevctrco nf goose vctr configuration for send and receive 1 1 1 1 1 1 1 vctrsend horizontal communication via goose for vctr 1 1 1 1 1 1 1 goosevctrrc v horizontal ...

  • Page 21

    Iec 61850 ansi function description transformer ret670 ret670 (a10) ret670 (a30) ret670 (b30) ret670 (a40) ret670 (b40) ret670 (a25) transmission of analog data from ldcm 1 1 1 1 1 1 1 receive binary status from remote ldcm 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 scheme communication ecpsch 85 sch...

  • Page 22

    Basic ied functions table 1. Basic ied functions iec 61850 or function name description interrsig self supervision with internal event list selfsupevlst self supervision with internal event list timesynchgen time synchronization module synchbin, synchcan, synchcmpps, synchlon, synchpph, synchpps, sy...

  • Page 23

    Table 1. Basic ied functions, continued iec 61850 or function name description altrk service tracking activlog activity logging parameters fstaccs field service tool access via spa protocol over ethernet communication pcmaccs ied configuration protocol secalarm component for mapping security events ...

  • Page 24

    Xx05000052.Vsd iec05000052 v1 en three-winding power transformer with all three windings connected xx05000053.Vsd iec05000053 v1 en three-winding power transformer with two circuit breakers and two ct-sets on one side xx05000057.Vsd iec05000057 v1 en autotransformer with two circuit breakers and two...

  • Page 25

    • phase-to-phase current variation • zero sequence current criterion • low voltage criterion • low current criterion phase-to-phase current variation takes the current samples as input and it calculates the variation using the sampling value based algorithm. Phase-to-phase current variation function...

  • Page 26

    En05000034.Vsd r x forward operation reverse operation iec05000034 v1 en figure 10. Typical quadrilateral distance protection zone with load encroachment function activated the distance protection zones can operate, independent of each other, in directional (forward or reverse) or non-directional mo...

  • Page 27

    The independent measurement of impedance for each fault loop together with a sensitive and reliable built in phase selection makes the function suitable in applications with single phase auto-reclosing. The distance protection zones can operate, independent of each other, in directional (forward or ...

  • Page 28

    The zones can operate independently of each other in directional (forward or reverse) or non-directional mode. However, zone1 and zone2 is designed to measure in forward direction only, while one zone (zrv) is designed to measure in the reverse direction. This makes them suitable, together with a co...

  • Page 29

    Detect, evaluate, and take the required action for pole slipping occurrences in the power system. Out-of-step protection oosppam the out-of-step protection oosppam function in the ied can be used for both generator protection and as well for line protection applications. The main purpose of the oosp...

  • Page 30

    Sensitive directional residual overcurrent and power protection sdepsde in isolated networks or in networks with high impedance earthing, the earth fault current is significantly smaller than the short circuit currents. In addition to this, the magnitude of the fault current is almost independent on...

  • Page 31

    Voltage-restrained time overcurrent protection vrpvoc voltage-restrained time overcurrent protection (vrpvoc) function can be used as generator backup protection against short-circuits. The overcurrent protection feature has a settable current level that can be used either with definite time or inve...

  • Page 32

    Overexcitation protection oexpvph when the laminated core of a power transformer or generator is subjected to a magnetic flux density beyond its design limits, stray flux will flow into non-laminated components that are not designed to carry flux. This will cause eddy currents to flow. These eddy cu...

  • Page 33

    9. Secondary system supervision current circuit supervision ccsspvc open or short circuited current transformer cores can cause unwanted operation of many protection functions such as differential, earth-fault current and negative-sequence current functions. It must be remembered that a blocking of ...

  • Page 34

    Interlocking, synchrocheck, operator place selection and external or internal blockings. Apparatus control features: • select-execute principle to give high reliability • selection function to prevent simultaneous operation • selection and supervision of operator place • command supervision • block/...

  • Page 35

    Hardware selector switches are used extensively by utilities, in order to have different functions operating on pre-set values. Hardware switches are however sources for maintenance issues, lower system reliability and an extended purchase portfolio. The selector switch function eliminates all these...

  • Page 36

    Trip matrix logic tmagapc trip matrix logic tmagapc function is used to route trip signals and other logical output signals to different output contacts on the ied. The trip matrix logic function has 3 output signals and these outputs can be connected to physical tripping outputs according to the sp...

  • Page 37

    • measured voltages, currents, frequency, active, reactive and apparent power and power factor • measured analog values from merging units • primary phasors • positive, negative and zero sequence currents and voltages • ma, input currents • pulse counters supervision of ma input signals the main pur...

  • Page 38

    Disturbance recorder drprdre the disturbance recorder function supplies fast, complete and reliable information about disturbances in the power system. It facilitates understanding system behavior and related primary and secondary equipment during and after a disturbance. Recorded information is use...

  • Page 39

    15. Human machine interface local hmi iec13000239-2-en.Vsd iec13000239 v2 en figure 12. Local human-machine interface the lhmi of the ied contains the following elements: • graphical display capable of showing a user defined single line diagram and provide an interface for controlling switchgear. • ...

  • Page 40

    With unsolicited events, time synchronizing and disturbance reporting is provided for communication to rtus, gateways or hmi systems. Multiple command and transmit when ieds are used in substation automation systems with lon, spa or iec 60870-5-103 communication protocols, the event and multiple com...

  • Page 41

    Communication (spa, iec 60870-5-103 and dnp3 port) and one port is dedicated for lon communication. Line data communication module ldcm each module has one optical port, one for each remote end to which the ied communicates. Alternative cards for long range (1550 nm single mode), medium range (1310 ...

  • Page 42

    Xx08000165.Vsd j g f k h iec08000165 v1 en figure 14. Case with rear cover and 19” rack mounting kit iec06000182-2-en.Vsd iec06000182 v2 en figure 15. A 1/2 x 19” size ied side-by-side with rhgs6. Case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8.81 242.1/ 9.53 255.8/ 1...

  • Page 43

    20. Connection diagrams connection diagrams the connection diagrams are delivered on the ied connectivity package dvd as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/substationautomation . Connection diagrams for customized pr...

  • Page 44

    21. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 45

    Table 4. Mim - ma input module quantity: rated value: nominal range: input resistance r in = 194 ohm - input range ± 5, ± 10, ± 20ma 0-5, 0-10, 0-20, 4-20ma - power consumption each ma-board each ma input £ 2 w £ 0.1 w - table 5. Oem - optical ethernet module quantity rated value number of channels ...

  • Page 46

    Binary inputs and outputs table 7. Bim - binary input module quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ±20% rl ±20% rl ±20% rl ±20% power consumption 24/30 v, 50 ma 48/60 v, 50 ma 110/125 v, 50 ma 220/250 v, 50 ma 220/250 v, 110 ma ma...

  • Page 47

    Table 9. Iom - binary input/output module quantity rated value nominal range binary inputs 8 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ±20% rl ±20% rl ±20% rl ±20% power consumption 24/30 v, 50 ma 48/60 v, 50 ma 110/125 v, 50 ma 220/250 v, 50 ma 220/250 v, 110 ma max. 0.05 w/input max....

  • Page 48

    Table 11. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1 min 250 v r...

  • Page 49

    Table 13. Som - static output module data (reference standard: iec 61810-2): electromechanical relay outputs function of quantity trip and signal relays max system voltage 250 v ac/dc number of outputs 6 test voltage across open contact, 1 min 1000 v rms current carrying capacity: continuous 8 a 1.0...

  • Page 50

    Table 16. Auxiliary dc supply voltage influence on functionality during operation dependence on reference value within nominal range influence ripple, in dc auxiliary voltage operative range max. 2% full wave rectified 15% of el 0.01% / % auxiliary voltage dependence, operate value ±20% of el 0.01% ...

  • Page 51

    Type tests according to standards table 18. Electromagnetic compatibility test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-26 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv iec 61000-4-12, ...

  • Page 52

    Table 20. Environmental tests test type test value reference standard cold operation test test ad for 16 h at -25°c iec 60068-2-1 cold storage test test ab for 16 h at -40°c iec 60068-2-1 dry heat operation test test bd for 16 h at +70°c iec 60068-2-2 dry heat storage test test bb for 16 h at +85°c ...

  • Page 53

    Differential protection table 23. Transformer differential protection t2wpdif, t3wpdif function range or value accuracy operating characteristic adaptable ±1.0% of ir at i ≤ ir ±1.0% of i at i > ir reset ratio > 90% - unrestrained differential current limit (100-5000)% of ibase on high voltage windi...

  • Page 54

    Table 24. Restricted earth-fault protection, low impedance refpdif function range or value accuracy operate characteristic adaptable ± 1.0% of i r for i ≤ i r ± 1.0% of i for i > i r reset ratio >95% - minimum pickup (4.0-100.0)% of ibase ± 1.0% of i r directional characteristic fixed 180 degrees or...

  • Page 55

    Table 26. Additional security logic for differential protection ldrgfc function range or value accuracy operate current, zero sequence current (1-100)% of lbase ±1.0% of i r operate current, low current operation (1-100)% of lbase ±1.0% of i r operate voltage, phase to neutral (1-100)% of ubase ±0.5...

  • Page 56

    Impedance protection table 27. Distance measuring zone, quad zmqpdis function range or value accuracy number of zones max 5 with selectable direction - minimum operate residual current, zone 1 (5-1000)% of ibase - minimum operate current, phase- to-phase and phase-to-earth (10-1000)% of ibase - posi...

  • Page 57

    Table 28. Distance measuring zone, quadrilateral characteristic for series compensated lines zmcpdis, zmcapdis function range or value accuracy number of zones max 5 with selectable direction - minimum operate residual current, zone 1 (5-1000)% of ibase - minimum operate current, ph-ph and ph-e (10-...

  • Page 58

    Table 30. Full-scheme distance protection, mho characteristic zmhpdis function range or value accuracy number of zones, ph-e max 4 with selectable direction - minimum operate current (10–30)% of ibase - positive sequence impedance, ph-e loop (0.005–3000.000) w/phase ± 2.0% static accuracy conditions...

  • Page 59

    Table 32. Faulty phase identification with load encroachment fmpspdis function range or value accuracy load encroachment criteria: load resistance, forward and reverse (1.00–3000.00) w/phase (5–70) degrees ±2.0% static accuracy conditions: voltage range: (0.1–1.1) x u r current range: (0.5–30) x i r...

  • Page 60

    Table 34. Phase selection with load encroachment, quadrilateral characteristic frpspdis function range or value accuracy minimum operate current (5-500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reactive reach, positive sequence (0.50–3000.00) Ω/phase ±2.0% static accuracy ±2.0 degrees...

  • Page 61

    Table 36. Power swing detection zmrpsb function range or value accuracy reactive reach (0.10-3000.00) w/phase ± 2.0% static accuracy conditions: voltage range: (0.1-1.1) x u r current range: (0.5-30) x i r angle: at 0 degrees and 85 degrees resistive reach (0.10–1000.00) w/loop power swing detection...

  • Page 62

    Table 40. Phase preference logic pplphiz function range or value accuracy operate value, phase-to-phase and phase-to-neutral undervoltage (1 - 100)% of ubase ±0.5% of u r reset ratio, undervoltage - operate value, residual voltage (5 - 300)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r res...

  • Page 63

    Current protection table 42. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of ibase - operate time at 0 to 2 x i set min. = 15 ms max. = 25 ms - res...

  • Page 64

    Table 44. Instantaneous residual overcurrent protection efpioc function range or value accuracy operate current (5-2500)% of lbase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - operate time at 0 to 2 x i set min. = 15 ms max. = 25 ms - reset time at 2 to 0 ...

  • Page 65

    Table 46. Four step negative sequence overcurrent protection ns4ptoc function range or value accuracy operate value, negative sequence current, step 1-4 (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - independent time delay for step 1, 2,...

  • Page 66

    Table 47. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cosj directional residual overcurrent (0.25-200.00)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r operate level for ·3i 0 ·3u 0 cosj directional resi...

  • Page 67

    Table 48. Thermal overload protection, one time constant lcpttr/lfpttr function range or value accuracy reference current (2-400)% of ibase ±1.0% of i r reference temperature (0-300)°c, (0 - 600)°f ± 1.0°c, ±2.0°f operate time: 2 2 2 2 2 ln p trip amb p ref ref i i t t t i i i t t - = - - - × é ù ê ...

  • Page 68

    Table 50. Breaker failure protection ccrbrf function range or value accuracy operate phase current (5-200)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio, ...

  • Page 69

    Table 53. Directional overpower protection goppdop function range or value accuracy power level for step 1 and step 2 (0.0–500.0)% of sbase ±1.0% of s r at s ≤ s r ±1.0% of s at s > s r characteristic angle for step 1 and step 2 (-180.0–180.0) degrees ±2.0 degrees operate time, start at 0.5 to 2 x s...

  • Page 70

    Table 55. Capacitor bank protection cbpgapc function range or value accuracy operate value, overcurrent (10-900)% of lbase ±2.0% of i r at i ≤ i r ±2.0% of i at i > i r reset ratio, overcurrent >95% at (100-900)% of ibase - start time, overcurrent, at 0.5 to 2 x iset min. = 5 ms max. = 20 ms - reset...

  • Page 71

    Table 56. Negative sequence time overcurrent protection for machines ns2ptoc function range or value accuracy operate current, step 1 - 2 (3-500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio >95% - operate time, start at 0 to 2 x i set min. = 15 ms max. = 30 ms - reset time, s...

  • Page 72

    Voltage protection table 57. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ±0.5% of u r ...

  • Page 73

    Table 58. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time characteristics for...

  • Page 74

    Table 60. Overexcitation protection oexpvph function range or value accuracy operate value, start (100–180)% of ( ubase /f rated ) ± 0.5% of u operate value, alarm (50–120)% of start level ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r operate value, high level (100–200)% of ( ubase /f rated ) ± 0....

  • Page 75

    Frequency protection table 63. Underfrequency protection saptuf function range or value accuracy operate value, start function, at symmetrical three phase voltage (35.00-75.00) hz ± 2.0 mhz operate time, start at f set + 0.02 hz to f set - 0.02 hz fn = 50 hz min. = 80 ms - max. = 95 ms fn = 60 hz mi...

  • Page 76

    Table 65. Rate-of-change frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ±10.0 mhz/s operate value, restore enable frequency (45.00-65.00) hz ±2.0 mhz definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is greater def...

  • Page 77

    Multipurpose protection table 66. General current and voltage protection cvgapc function range or value accuracy measuring current input phase1, phase2, phase3, posseq, - negseq, -3*zeroseq, maxph, minph, unbalanceph, phase1-phase2, phase2- phase3, phase3-phase1, maxph-ph, minph-ph, unbalanceph-ph -...

  • Page 78

    Table 66. General current and voltage protection cvgapc , continued function range or value accuracy independent time delay, undervoltage at 1.2 to 0.8 x u set , step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater overvoltage: start time at 0.8 to 1.2 x u set min. = 15 ms max. = 30 ms...

  • Page 79

    Table 67. Voltage-restrained time overcurrent protection vrpvoc function range or value accuracy start overcurrent (2.0 - 5000.0)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio, overcurrent > 95% - operate time, start overcurrent at 0 to 2 x i set min. = 15 ms - max. = 30 ms res...

  • Page 80

    Secondary system supervision table 68. Current circuit supervision ccsspvc function range or value accuracy operate current (10-200)% of ibase ±10.0% of i r at i ≤ i r ±10.0% of i at i > i r reset ratio, operate current >90% block current (20-500)% of ibase ±5.0% of i r at i ≤ i r ±5.0% of i at i > ...

  • Page 81

    Table 70. Fuse failure supervision vdspvc function range or value accuracy operate value, block of main fuse failure (10.0-80.0)% of ubase ±0.5% of ur reset ratio operate time, block of main fuse failure at 1 to 0 x u r min. = 5 ms – max. = 15 ms reset time, block of main fuse failure at 0 to 1 x u ...

  • Page 82

    Control table 71. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r reset ratio, sy...

  • Page 83

    Table 72. Voltage control tr1atcc and tr8atcc function range or value accuracy transformer reactance (0.1–200.0)Ω, primary - time delay for lower command when fast step down mode is activated (1.0–100.0) s - voltage control set voltage (85.0–120.0)% of ubase ± 0.25 % of u r outer voltage deadband (0...

  • Page 84

    Table 72. Voltage control tr1atcc and tr8atcc, continued function range or value accuracy time after position change before the value is accepted (1–60) s ± 0.2% or ± 200 ms whichever is greater tap changer constant time-out (1–120) s ± 0.2% or ± 200 ms whichever is greater raise/lower command outpu...

  • Page 85

    Scheme communication table 73. Scheme communication logic for residual overcurrent protection ecpsch function range or value accuracy scheme type permissive underreaching permissive overreaching blocking - communication scheme coordination time (0.000-60.000) s ±0.2% or ±20 ms whichever is greater t...

  • Page 86

    Logic table 75. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ± 0.2% or ± 30 ms whichever is greater 3-pole trip delay (0.020-0.500) s ± 0.2% or ±10 ms whichever is greater single phase de...

  • Page 87

    Table 77. Configurable logic blocks q/t logic block quantity with cycle time range or value accuracy medium normal andqt 20 100 - - orqt 20 100 - - inverterqt 20 100 - - xorqt 10 30 - - srmemoryqt 10 30 - - rsmemoryqt 10 30 - - timersetqt 10 30 (0.000-90000.000) s ± 0.5% ± 10 ms pulsetimerqt 10 30 (...

  • Page 88

    Monitoring table 80. Measurements cvmmxn function range or value accuracy frequency (0.95-1.05) × f r ± 2.0 mhz voltage (0.1-1.5) ×u r ± 0.5% of u r at u£u r ± 0.5% of u at u > u r connected current (0.2-4.0) × i r ± 0.5% of i r at i £ i r ± 0.5% of i at i > i r active power, p 0.1 x u r r 0.2 x i r...

  • Page 89

    Table 84. Current sequence component measurement cmsqi function range or value accuracy current positive sequence, i1 three phase settings (0.1–4.0) × i r ± 0.3% of i r at i ≤ 0.5 × i r ± 0.3% of i at i > 0.5 × i r current zero sequence, 3i0 three phase settings (0.1–1.0) × i r ± 0.3% of i r at i ≤ ...

  • Page 90

    Table 88. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 113 maximum number of analog inputs 30 + 10 (e...

  • Page 91

    Table 92. Trip value recorder function value buffer capacity maximum number of analog inputs 30 maximum number of disturbance reports 100 table 93. Disturbance recorder function value buffer capacity maximum number of analog inputs 40 maximum number of binary inputs 96 maximum number of disturbance ...

  • Page 92

    Metering table 94. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - table 95. Energy metering etpmmtr function range or value accuracy energy metering kwh export/import, kvarh export/ import...

  • Page 93

    Station communication table 96. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–19200 bd protocol tcp/ip, ethernet...

  • Page 94

    Table 102. Slm – spa/iec 60870-5-103/dnp3 port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (1000m/3000ft m typically *) plastic fiber: 7 db (25m/80ft m typically *) fiber diameter glass fiber: 62.5/125 mm pl...

  • Page 95

    Remote communication table 106. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fiber graded-index multimode 62.5/125 µm singlemode 9/125 µm singlemode 9/125 µm peak emission wave length nominal maximum minimum 820 ...

  • Page 96

    Hardware ied table 107. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) table 108. Water and dust protection level according to iec 60529 front ip40 (ip54 with sealing strip) sides, top and bottom i...

  • Page 97

    Basic ied functions table 112. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out table 113. Time synchronization, time tagging function value time tagging resolution, events and sampled measurement values 1 ms t...

  • Page 98

    Table 116. Irig-b quantity rated value number of channels irig-b 1 number of optical channels 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00x, irig-b 12x acc...

  • Page 99

    Inverse characteristic table 117. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en i = i measured /i set k =...

  • Page 100

    Table 118. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en i = i measured /i set k = (0.05-2.00) in steps of 0.01 iec 60255-151, ± 2.0% or ± 40 ms whichever is greater iec normal inverse a=0.14...

  • Page 101

    Table 120. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 32 0.5 = ⋅ − ...

  • Page 102

    Table 121. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + × - ...

  • Page 103

    Table 122. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 32 0...

  • Page 104

    22. Ordering for customized ied table 123. General guidelines guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or additions to the de...

  • Page 105

    Table 128. Differential functions function function identification ordering no positi on available qty selected qty notes and rules transformer differential protection, two winding t2wpdif 1mrk005904-fa 5 0-2 note: one, and only one pdif must be ordered. Transformer differential protection, three wi...

  • Page 106

    Table 130. Impedance functions, alternatives function function identification ordering no positi on available qty selec ted qty notes and rules note: one, and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative. Alternative 1 distance protection, ...

  • Page 107

    Table 132. Current functions function function identification ordering no positi on available qty selected qty notes and rules instantaneous phase overcurrent protection phpioc 1mrk005910-aa 1 0-8 four step phase overcurrent protection oc4ptoc 1mrk005910-ba 2 0-8 instantaneous residual overcurrent p...

  • Page 108

    Table 139. General calculation position 1 s table 140. General calculation functions function function identification ordering no positi on available qty selected qty notes and rules frequency tracking filter smaihpac 1mrk005915-ka 1 0-6 table 141. Secondary system supervision position 1 2 3 g table...

  • Page 109

    Table 149. Monitoring position 1 2 m 0 table 150. Monitoring functions function function identification ordering no positi on available qty selected qty notes and rules circuit breaker condition monitoring sscbr 1mrk005924-ha 1 0-18 table 151. Station communication position 1 2 p table 152. Station ...

  • Page 110

    Table 155. Mounting selection mounting details with ip40 of protection from the front selection notes and rules no mounting kit included x 19" rack mounting kit for 1/2 x 19" case of 2xrhgs6 or rhgs12 a 19" rack mounting kit for 3/4 x 19" case or 3xrghs6 b 19" rack mounting kit for 1/1 x 19" case c ...

  • Page 111

    Table 158. Analog system selection analog system selection notes and rules no first trm included x0 note: only valid in ret670–n00 compression terminals a note: only the same type of trm (compression or ringlug) in the same terminal. Ringlug terminals b first trm 12i 1a, 50/60hz 1 first trm 12i 5a, ...

  • Page 112

    Table 160. Maximum quantity of i/o modules, with ring lug terminals, module limits se above case sizes maximum in case possible locations for i/o modules with ringlug 1/1 x 19”, one (1) trm 14 p3, p5, p7, p9, p11, p13, p15 1/1 x 19”, two (2) trm 11 p3, p5, p7, p9, p11 3/4 x 19”, one (1) trm 8 p3, p5...

  • Page 113

    Table 161. Binary input/output module selection binary input/output modules selection notes and rules slot position (rear view) x31 x41 x51 x61 x71 x81 x91 x101 x111 x121 x131 x141 x151 x161 note! Max 3 positions in 1/2 rack, 8 in 3/4 rack with 1 trm, 5 in 3/4 rack with 2 trm, 11 in 1/1 rack with 2 ...

  • Page 114

    Table 161. Binary input/output module selection, continued binary input/output modules selection notes and rules som static output module, 12 outputs, 48-60 vdc t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 note: som must not to be placed in position nearest to num; 1/2 case slot p5, 3/4 case 1 trm slot...

  • Page 115

    23. Ordering for pre-configured ied guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or additions to the delivered factory configurat...

  • Page 116

    Software options #3 notes and rules no option x 00 all fields in the ordering form do not need to be filled in restricted earth fault protection, low impedance a 01 note: a01 only for a40/ b40, 2 blocks already included high impedance differential protection - 3 blocks a 02 note: a02, b12, b13 and b...

  • Page 117

    Software options #3 notes and rules only for b40 and m17 only for a10 and a40 circuit breaker condition monitoring - 6 cb m 15 circuit breaker condition monitoring - 18 cb m 16 circuit breaker condition monitoring - 9 cb m 17 iec 62439-3 parallel redundancy protocol p 03 selection for position #3 fi...

  • Page 118

    Analog input system #9 notes and rules compression terminals a ringlug terminals b first trm, 9i+3u 1a, 110/220v 3 note: not in a25 first trm, 9i+3u 5a, 110/220v 4 note: not in a25 first trm, 5i, 1a+4i, 5a+3u, 110/220v 5 note: not in a25 first trm, 6i+6u 1a, 100/220v 6 note: only for a25 first trm, ...

  • Page 119

    Binary input/output module, ma and time synchronization boards. #10 notes and rules make bim with 50 ma inrush current the primary choice. Bim with 50 ma inrush current fulfill additional standards. As a consequence the emc withstand capability is further increased. Bim with 30 ma inrush current is ...

  • Page 120

    Remote end communication, dnp serial comm. And time synchronization modules #11 notes and rules slot position (rear view) x312 x313 x302 x303 x322 x323 available slots in 1/2 case with 1trm █ █ █ █ note: max 1 ldcm in 1/2 case available slots in 3/4 and 1/1 case with 2 trm █ █ █ █ █ █ note: max 2 ld...

  • Page 121

    24. Ordering for accessories accessories gps antenna and mounting details gps antenna, including mounting kits quantity: 1mrk 001 640-aa cable for antenna, 20 m quantity: 1mrk 001 665-aa cable for antenna, 40 m quantity: 1mrk 001 665-ba interface converter (for remote end data communication) externa...

  • Page 122

    External resistor unit high impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100v operating voltage quantity: 1 2 3 rk 795 101-ma high impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100v operating voltage quantity: rk 795 101-mb high ...

  • Page 123

    User documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 504 138-uen ansi quantity: 1mrk 504 138-uus technical manual iec quantity: 1mrk 504 139-uen ansi quantity: 1mrk 504 139-uus commissioning manual iec quantity: 1mrk 504 140-uen ansi quantity...

  • Page 124

    Engineering manual, 670 series iec quantity: 1mrk 511 308-uen ansi quantity: 1mrk 511 308-uus cyber security guideline iec quantity: 1mrk 511 309-uen reference information for our reference and statistics we would be pleased to be provided with the following application data: country: end user: stat...

  • Page 125

    125.

  • Page 126

    Contact us for more information please contact: abb ab substation automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 www.Abb.Com/substationautomation note: we reserve the right to make technical changes or modify the contents of this document without prior notice. Abb ab does n...