ABB REQ650 Product Manual

Manual is about: Breaker protection

Summary of REQ650

  • Page 1

    Relion ® 650 series breaker protection req650 product guide.

  • Page 2

    Contents 1. 650 series overview........................................................3 2. Application.....................................................................3 3. Available functions..........................................................7 4. Current protection..........................

  • Page 3

    1. 650 series overview the 650 series ieds provide both customized and configured solutions. With the customized ieds you have the freedom to completely adapt the functionality according to your needs. The 650 series ieds provide optimum 'off-the- shelf', ready-to-use solutions. It is configured wit...

  • Page 4

    Req650-a01 – single busbar single breaker 10ai (4i+1i+5u) three phase variant smb rrec 79 0->1 smp ptrc 94 1->0 ses rsyn 25 sync tcs scbr cond spvn zbat cond other configured functions ov2 ptov 59 3u> ph pioc 50 3i>> cc rbrf 50bf v mmxu meter. C mmxu meter. Etp mmtr wh qa1 qb1 qb9 qc9 qc2 qc1 ef4 pt...

  • Page 5

    Req650-a11 – single busbar single breaker 10ai (4i+1i+5u) single phase variant stb rrec 79 0->1 spt ptrc 94 1->0 ses rsyn 25 sync tcs scbr cond spvn zbat cond other configured functions ov2 ptov 59 3u> spt pioc 50 i>> csp rbrf 50bf v mmxu meter. C mmxu meter. Etp mmtr wh qa1 qb1 qb9 qc9 qc2 qc1 ef4 ...

  • Page 6

    Qa1 qb1 qb2 qb9 qc9 qc2 qc1 wa1 wa2 132 kv bus 132kv/110v 132kv/ 110v 132kv/ 110v req650-b11 – double busbar single breaker 10ai (4i+1i+5u) single phase variant stb rrec 79 0->1 spt ptrc 94 1->0 ses rsyn 25 sync etp mmtr wh ef4 ptoc 51n/67n in> cv mmxn meter. Oc4s ptoc 51/67 3i> sde psde 67n in lfpt...

  • Page 7

    3. Available functions breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 7.

  • Page 8

    Back-up protection functions iec 61850/ function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb current protection phpioc 50 instantaneous phase overcurrent protection, 3–phase output 0–1 1 sptpioc 50 instantaneous phase...

  • Page 9

    Iec 61850/ function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb rov2ptov 59n two step residual overvoltage protection 0–1 1 1 1 lovptuv 27 loss of voltage check 0–1 1 1 1 frequency protection saptuf 81 underfrequency ...

  • Page 10

    Control and monitoring functions iec 61850/function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb control sesrsyn 25 synchrocheck, energizing check, and synchronizing 0–1 1 1 1 smbrrec 79 autorecloser for 3–phase operat...

  • Page 11

    Iec 61850/function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb logic smpptrc 94 tripping logic, common 3–phase output 0–1 1 sptptrc 94 tripping logic, phase segregated output 0–1 1 1 tmaggio trip matrix logic 12 12 12...

  • Page 12

    Iec 61850/function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb vmmxu phase-phase voltage measurement 6 6 6 6 cmsqi current sequence component measurement 6 6 6 6 vmsqi voltage sequence measurement 6 6 6 6 vnmmxu phase...

  • Page 13

    Iec 61850/function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb i103meas measurands for iec60870-5-103 1 1 1 1 i103measusr measurands user defined signals for iec60870-5-103 3 3 3 3 i103ar function status auto-recloser...

  • Page 14

    Communication iec 61850/function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb station communication iec61850-8-1 iec 61850 communication protocol 1 1 1 1 dnpgen dnp3.0 for tcp/ip communication protocol 1 1 1 1 rs485dnp...

  • Page 15

    Iec 61850/function block name ansi function description breaker req650 req650 (a01) 3ph/1cb/1bb req650 (a11) 1ph/1cb/1bb req650 (b11) 1ph/1cb/2bb rs485103 iec60870-5-103 serial communication for rs485 1 1 1 1 gooseintlkrcv horizontal communication via goose for interlocking 59 59 59 59 goosebinrcv g...

  • Page 16

    Basic ied functions iec 61850/function block name function description basic functions included in all products interrsig self supervision with internal event list 1 selfsupevlst self supervision with internal event list 1 timesynchgen time synchronization 1 sntp time synchronization 1 dtsbegin, dts...

  • Page 17

    4. Current protection instantaneous phase overcurrent protection, 3- phase output phpioc the instantaneous three phase overcurrent function has a low transient overreach and short tripping time to allow use as a high set short- circuit protection function. Instantaneous phase overcurrent protection,...

  • Page 18

    Use either the residual current or residual power component 3u 0 ·3i 0 ·cos j , for operating quantity. There is also available one non-directional 3i 0 step and one non-directional 3u 0 overvoltage tripping step. Thermal overload protection, one time constant the increasing utilizing of the power s...

  • Page 19

    To electrical or mechanical failures. An open phase can cause negative and zero sequence currents which cause thermal stress on rotating machines and can cause unwanted operation of zero sequence or negative sequence current functions. Normally the own breaker is tripped to correct such a situation....

  • Page 20

    Two step residual overvoltage protection rov2ptov function calculates the residual voltage from the three-phase voltage input transformers or measures it from a single voltage input transformer fed from an open delta or neutral point voltage transformer. Rov2ptov has two voltage steps, where step 1 ...

  • Page 21

    The presence of the negative-sequence current 3i 2 . The zero sequence detection algorithm is recommended for ieds used in directly or low impedance earthed networks. It is based on the zero sequence measuring quantities, a high value of zero sequence voltage 3u 0 without the presence of the zero se...

  • Page 22

    Local remote locrem /local remote control locremctrl the signals from the local hmi or from an external local/remote switch are applied via the function blocks locrem and locremctrl to the bay control (qcbay) function block. A parameter in function block locrem is set to choose if the switch signals...

  • Page 23

    Tripping logic phase segregated output sptptrc a function block for protection tripping is provided for each circuit breaker involved in the tripping of the fault. It provides the pulse prolongation to ensure an one- or three-phase trip pulse of sufficient length, as well as all functionality necess...

  • Page 24

    10. Monitoring iec61850 generic communication i/o function spggio iec61850 generic communication i/o functions (spggio) is used to send one single logical signal to other systems or equipment in the substation. Iec61850 generic communication 1/o function 16 inputs iec 61850 generic communication i/o...

  • Page 25

    Report function that have changed status during a disturbance. Event recorder drprdre quick, complete and reliable information about disturbances in the primary and/or in the secondary system is vital, for example, time- tagged events logged during disturbances. This information is used for differen...

  • Page 26

    Information based on the gas pressure in the circuit breaker is used as input signals to the function. In addition, the function generates alarms based on received information. Insulation liquid monitoring function ssiml insulation liquid monitoring function ssiml is used for monitoring the circuit ...

  • Page 27

    To internal system events generated by the different built-in self-supervision elements. The internal events are saved in an internal event list. Time synchronization use a common global source for example gps time synchronization inside each substation as well as inside the area of the utility resp...

  • Page 28

    Disturbance files are accessed using the iec 61850-8-1 protocol. Disturbance files are available to any ethernet based application via ftp in the standard comtrade format. Further, the ied can send and receive binary values, double point values and measured values (for example from mmxu functions), ...

  • Page 29

    The functions iec60870-5-103 optical serial communication (optical103) and iec60870-5-103 serial communication for rs485 (rs485103) are used to configure the communication parameters for either the optical serial or rs485 serial communication interfaces. 15. Hardware description layout and dimension...

  • Page 30

    16. Connection diagrams customized connection diagrams for 650 series iec12000593 v1 en figure 6. Designation for 3u, 1/1x19" casing with 1 trm iec12000594 v1 en figure 7. Designation for 3u, 1/1x19" casing with 1 trm and 1 aim breaker protection req650 1mrk 505 283-ben - product version: 1.2 30 abb.

  • Page 31

    Iec12000595 v1 en figure 8. Communication module (com) breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 31.

  • Page 32

    Iec12000596 v1 en figure 9. Power supply module (psm) 48-125v dc breaker protection req650 1mrk 505 283-ben - product version: 1.2 32 abb.

  • Page 33

    Iec12000597 v1 en figure 10. Power supply module (psm) 110-250v dc, 100–240v ac iec12000598 v1 en figure 11. Transformer module (trm) breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 33.

  • Page 34

    Iec12000599 v1 en figure 12. Analog input (aim) iec12000600 v1 en figure 13. Binary input/output (bio) option breaker protection req650 1mrk 505 283-ben - product version: 1.2 34 abb.

  • Page 35

    17. Connection diagrams configured iec12000533 v1 en figure 14. Designation for 3u, 1/1x19" casing with 1 trm breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 35.

  • Page 36

    Connection diagrams for req650 a01 iec12000534 v1 en figure 15. Communication module (com) breaker protection req650 1mrk 505 283-ben - product version: 1.2 36 abb.

  • Page 37

    Iec12000535 v1 en figure 16. Power supply module (psm) 48-125v dc breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 37.

  • Page 38

    Iec12000536 v1 en figure 17. Power supply module (psm), 110-250v dc, 100–240v ac breaker protection req650 1mrk 505 283-ben - product version: 1.2 38 abb.

  • Page 39

    Iec12000537 v1 en figure 18. Transformer module (trm) breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 39.

  • Page 40

    Iec12000538 v1 en figure 19. Binary input/output (bio) option breaker protection req650 1mrk 505 283-ben - product version: 1.2 40 abb.

  • Page 41

    Connection diagrams for req650 a11 iec12000540 v1 en figure 20. Communication module (com) breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 41.

  • Page 42

    Iec12000541 v1 en figure 21. Power supply module (psm) 48-125v dc breaker protection req650 1mrk 505 283-ben - product version: 1.2 42 abb.

  • Page 43

    Iec12000542 v1 en figure 22. Power supply module (psm), 110-250v dc, 100–240v ac breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 43.

  • Page 44

    Iec12000543 v1 en figure 23. Transformer module (trm) breaker protection req650 1mrk 505 283-ben - product version: 1.2 44 abb.

  • Page 45

    Iec12000544 v1 en figure 24. Binary input/output (bio) option breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 45.

  • Page 46

    Iec12000545 v1 en figure 25. Binary input/output (bio) option breaker protection req650 1mrk 505 283-ben - product version: 1.2 46 abb.

  • Page 47

    Connection diagrams for req650 b11 iec12000547 v1 en figure 26. Communication module (com) breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 47.

  • Page 48

    Iec12000548 v1 en figure 27. Power supply module (psm) 48-125v dc breaker protection req650 1mrk 505 283-ben - product version: 1.2 48 abb.

  • Page 49

    Iec12000549 v1 en figure 28. Power supply module (psm), 110-250v dc, 100–240v ac breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 49.

  • Page 50

    Iec12000550 v1 en figure 29. Transformer module (trm) breaker protection req650 1mrk 505 283-ben - product version: 1.2 50 abb.

  • Page 51

    Iec12000551 v1 en figure 30. Binary input/output (bio) option breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 51.

  • Page 52

    Iec12000552 v1 en figure 31. Binary input/output (bio) option breaker protection req650 1mrk 505 283-ben - product version: 1.2 52 abb.

  • Page 53

    18. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 54

    Auxiliary ac and dc voltage table 3. Power supply description 600psm02 600psm03 u aux nominal 48, 60, 110, 125 v dc 100, 110, 120, 220, 240 v ac, 50 and 60 hz 110, 125, 220, 250 v dc u aux variation 80...120% of u n (38.4...150 v dc) 85...110% of u n (85...264 v ac) 80...120% of u n (88...300 v dc) ...

  • Page 55

    Table 6. Power output relays without tcs function description value rated voltage 250 v ac/dc continuous contact carry 8 a make and carry for 3.0 s 15 a make and carry for 0.5 s 30 a breaking capacity when the control-circuit time constant l/ r ≤1 a/≤0.3 a/≤0.1 a table 7. Power output relays with tc...

  • Page 56

    Table 10. X8/irig-b and eia-485 interface type protocol cable screw terminal, pin row header irig-b shielded twisted pair cable recommended: cat 5, belden rs-485 (9841- 9844) or alpha wire (alpha 6222-6230) screw terminal, pin row header shielded twisted pair cable recommended: descaflex rd-h(st)h-2...

  • Page 57

    Table 14. Optical serial port (x9) wave length fibre type connector permitted path attenuation 1) 820 nm mm 62,5/125 µm glass fibre core st 6.8 db (approx. 1700m length with 4 db / km fibre attenuation) 820 nm mm 50/125 µm glass fibre core st 2.4 db (approx. 600m length with 4 db / km fibre attenuat...

  • Page 58

    Table 18. Environmental tests description type test value reference cold tests operation storage 96 h at -25ºc 16 h at -40ºc 96 h at -40ºc iec 60068-2-1/ansi c37.90-2005 (chapter 4) dry heat tests operation storage 16 h at +70ºc 96 h at +85ºc iec 60068-2-2/ansi c37.90-2005 (chapter 4) damp heat test...

  • Page 59

    Type tests according to standards table 19. Electromagnetic compatibility tests description type test value reference 100 khz and 1 mhz burst disturbance test iec 61000-4-18, level 3 iec 60255-22-1 ansi c37.90.1-2002 • common mode 2.5 kv • differential mode 2.5 kv electrostatic discharge test iec 61...

  • Page 60

    Table 19. Electromagnetic compatibility tests, continued description type test value reference voltage dips and short interruptionsc on dc power supply dips: 40%/200 ms 70%/500 ms interruptions: 0-50 ms: no restart 0...∞ s : correct behaviour at power down iec 60255-11 iec 61000-4-11 voltage dips an...

  • Page 61

    Table 20. Insulation tests description type test value reference dielectric tests: iec 60255-5 ansi c37.90-2005 • test voltage 2 kv, 50 hz, 1 min 1 kv, 50 hz, 1 min, communication impulse voltage test: iec 60255-5 ansi c37.90-2005 • test voltage 5 kv, unipolar impulses, waveform 1.2/50 μs, source en...

  • Page 62

    Emc compliance table 23. Emc compliance description reference emc directive 2004/108/ec standard en 50263 (2000) en 60255-26 (2007) current protection table 24. Instantaneous phase overcurrent protection, 3-phase output phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0...

  • Page 63

    Table 26. Four step phase overcurrent protection, 3-phase output oc4ptoc function setting range accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% - min. Operating current (1-10000)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r 2...

  • Page 64

    Table 27. Four step phase overcurrent protection, phase segregated output oc4sptoc function setting range accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - min. Operating current (1-10000)% of lbase ± 1.0% of i r at i r ± 1.0% of i at i >...

  • Page 65

    Table 29. Four step residual overcurrent protection ef4ptoc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i i r ± 1.0% of i at i > i r reset ratio > 95% - operate current for directional comparison, zero sequence (1–100)% of lbase ± 2.0% of i r operate current ...

  • Page 66

    Table 30. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cos j directional residual overcurrent (0.25-200.00)% of lbase at low setting: (2.5-10) ma (10-50) ma ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r ± 0.5 ma ± ...

  • Page 67

    Table 30. Sensitive directional residual overcurrent and power protection sdepsde, continued function range or value accuracy reset time, non-directional residual overvoltage 120 ms typically at 1.2 to 0.8 x u set - operate time, directional residual over current 260 ms typically at 0.5 to 2 x i set...

  • Page 68

    Table 32. Breaker failure protection, 3-phase activation and output ccrbrf function range or value accuracy operate phase current (5-200)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ± 1.0% of i r at i £ i r ±...

  • Page 69

    Table 34. Stub protection stbptoc function range or value accuracy operating current (1-2500)% of ibase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 20 ms typically at 0 to 2 x i set - reset time 30 ms typically at 2 to 0 x i set - critical impulse time 10 ms typi...

  • Page 70

    Table 38. Negative sequence based overcurrent function dnsptoc function range or value accuracy operate current (2.0 - 5000.0) % of ibase ± 1.0% of i r at i r ± 1.0% of i at i > i r reset ratio > 95 % - low voltage level for memory (0.0 - 5.0) % of ubase r relay characteristic angle (-180 - 180) deg...

  • Page 71

    Table 40. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, low and high step (1-200)% of ubase ± 0.5% of u r at u r ± 0.5% of u at u > u r reset ratio >95% - inverse time characteristics for low and high step, see table 76 - see table 76 definite time delay, ...

  • Page 72

    Table 42. Loss of voltage check lovptuv function range or value accuracy operate voltage (0–100)% of ubase ± 0.5% of u r reset ratio - pulse timer (0.050–60.000) s ± 0.5% ± 25 ms timers (0.000–60.000) s ± 0.5% ± 25 ms frequency protection table 43. Under frequency protection saptuf function range or...

  • Page 73

    Table 45. Rate-of-change frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ± 10.0 mhz/s operate value, restore enable frequency (45.00 - 65.00) hz ± 2.0 mhz timers (0.000 - 60.000) s operate time, start function at 50 hz: 100 ms typically ...

  • Page 74

    Control table 49. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage ratio, u bus /u line 0.500 - 2.000 - reset ratio, synchrocheck > 95% - frequency difference limit between bus and line for synchroch...

  • Page 75

    Table 50. Autorecloser for 3-phase operation smbrrec function range or value accuracy number of autoreclosing shots 1 - 5 - autoreclosing open time: shot 1 - t1 3ph (0.000-60.000) s ± 0.5% ± 25 ms shot 2 - t2 3ph shot 3 - t3 3ph shot 4 - t4 3ph shot 5 - t5 3ph (0.00-6000.00) s autorecloser maximum w...

  • Page 76

    Table 51. Autorecloser for 1/3-phase operation stbrrec function range or value accuracy number of autoreclosing shots 1-5 - autoreclosing open time: shot 1 - t1 3ph shot 1 - t1 1ph (0.000-60.000) s ± 0.5% ± 25 ms shot 2 - t2 3ph shot 3 - t3 3ph shot 4 - t4 3ph shot 5 - t5 3ph (0.00-6000.00) s autore...

  • Page 77

    Table 54. Configurable logic blocks logic block quantity with cycle time range or value accuracy 5 ms 20 ms 100 ms and 60 60 160 - - or 60 60 160 - - xor 10 10 20 - - inverter 30 30 80 - - srmemory 10 10 20 - - rsmemory 10 10 20 - - gate 10 10 20 - - pulsetimer 10 10 20 (0.000–90000.000) s ± 0.5% ± ...

  • Page 78

    Table 57. Disturbance report drprdre function range or value accuracy current recording - ± 1,0% of i r at i ≤ i r ± 1,0% of i at i > ir voltage recording - ± 1,0% of u r at u ≤ u r ± 1,0% of u at u > u r pre-fault time (0.05–3.00) s - post-fault time (0.1–10.0) s - limit time (0.5–8.0) s - maximum ...

  • Page 79

    Table 60. Event recorder drprdre function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance reports 100 resolution 1 ms accuracy depending on time synchronizing table 61. Trip value recorder drprdre function value buffer capacity maximum number of...

  • Page 80

    Table 65. Insulation liquid monitoring function ssiml function range or value accuracy alarm, oil level 0.00-25.00 - oil level lockout 0.00-25.00 - temperature alarm -40.00-200.00 - temperature lockout -40.00-200.00 - timers (0.000-60.000) s ± 0.5% ± 110 ms table 66. Circuit breaker condition monito...

  • Page 81

    Station communication table 69. Communication protocol function value protocol tcp/ip ethernet communication speed for the ieds 100 mbit/s protocol iec 61850–8–1 communication speed for the ieds 100base-fx protocol dnp3.0/tcp communication speed for the ieds 100base-fx protocol, serial iec 60870–5–1...

  • Page 82

    Inverse time characteristics table 73. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = + × - æ ö ç ÷ ç ÷ è ø p a t b k i equation1249-small v1 en i = i measured /i set k = (0.05-999) in steps of 0.01 - ansi extremely inverse a=28.2, b=0.1217, p=2....

  • Page 83

    Table 75. Ri and rd type inverse time characteristics function range or value accuracy ri type inverse characteristic 1 0.236 0.339 = × - t k i equation1137-small v1 en i = i measured /i set k = (0.05-999) in steps of 0.01 rd type logarithmic inverse characteristic 5.8 1.35 = - × æ ö ç ÷ è ø t i in ...

  • Page 84

    Table 77. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en u set u = uv measured k = (0.05-1.10) in steps of 0.01 ±5% +60 ms type b curve: 2.0 480 0.055 32 0.5 × = + × - æ ö ç ÷ è ø k t u u u equa...

  • Page 85

    19. Ordering for customized ied guidelines carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Product specification b...

  • Page 86

    Logic rule: one tripping logic type only must be ordered note: selection of tripping logic type rules the selection of instantaneous phase overcurrent protection, four step phase overcurrent protection, breaker failure protection and autorecloser. Tripping logic, common 3–phase output (smpptrc) qty:...

  • Page 87

    Voltage protection two step undervoltage protection (uv2ptuv) qty: 1mrk 004 910-ab two step overvoltage protection (ov2ptov) qty: 1mrk 004 910-bb two step residual overvoltage protection (rov2ptov) qty: 1mrk 004 910-cb loss of voltage check (lovptuv) qty: 1mrk 004 910-ea frequency protection underfr...

  • Page 88

    Optional hardware human machine interface rule: one must be ordered. Display type keypad symbol case size local human machine interface (lhmi) iec 3u 1/1 19" 1khl160055r0001 local human machine interface (lhmi) ansi 3u 1/1 19" 1khl160042r0001 analog system rule: one transformer input module must be ...

  • Page 89

    20. Ordering for configured ied guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. To obtain the complete ordering code, please combine code from the tables, as given in the ...

  • Page 90

    Mounting details with ip40 of protection from the front #6 notes and rules no mounting kit included x rack mounting kit for 3u 1/1 x 19" h selection for position #6. Connection type for power supply, input/output and communication modules #7 notes and rules compression terminals s ringlug terminals ...

  • Page 91

    Communication and processing module #11 notes and rules slot position (rear view) pcom 12bi, irig-b, rs485, ethernet, lc optical, st serial f selection for position #11. F breaker protection req650 1mrk 505 283-ben - product version: 1.2 abb 91.

  • Page 92

    21. Ordering for accessories configuration and monitoring tools front connection cable between lcd-hmi and pc quantity: 1mrk 001 665-ca led label special paper a4, 1 pc quantity: 1mrk 002 038-ca led label special paper letter, 1 pc quantity: 1mrk 002 038-da manuals note: one (1) ied connect dvd cont...

  • Page 93

    Rule: specify the number of printed manuals requested operation manual iec quantity: 1mrk 500 095-uen technical manual iec quantity: 1mrk 505 281-uen commissioning manual iec quantity: 1mrk 505 282-uen application manual iec quantity: 1mrk 505 280-uen communication protocol manual, dnp3 iec quantity...

  • Page 94

    Related documents documents related to req650 identity number application manual 1mrk 505 280-uen technical manual 1mrk 505 281-uen commissioning manual 1mrk 505 282-uen product guide 1mrk 505 283-ben type test certificate 1mrk 505 283-ten application notes for circuit breaker control 1mrg006806 650...

  • Page 95

    95.

  • Page 96

    Contact us abb ab substation automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 fax +46 (0) 21 14 69 18 www.Abb.Com/substationautomation 1mrk 505 283-ben - © copyright 2012 abb. All rights reserved..