ABB ret650 Product Manual

Manual is about: Relion 650 series Transformer protection

Summary of ret650

  • Page 1

    Relion ® 650 series transformer protection ret650 product guide.

  • Page 2

    Contents 1. 650 series overview........................................................3 2. Application..................................................................... 3 3. Available functions..........................................................7 4. Differential protection....................

  • Page 3

    1. 650 series overview protection for a wide range of applications, control of switching devices with interlocking, and monitoring can be provided in one ied. The 650 series ieds provide both customized and configured solutions. With the customized ieds you have the freedom to completely adapt the f...

  • Page 4

    T2w pdif 87t 3id/i cc rbrf 50bf 3i> bf cc rbrf 50bf 3i> bf oc4 ptoc 50/51 3i> oc4 ptoc 50/51 3i> cc rpld 52pd pd ef4 ptoc 51n in> cc rpld 52pd pd tr pttr 49 ith c msqi meter. V mmxu meter. C mmxu meter. Cv mmxn meter. Tcs scbr cond tcs scbr cond spvn zbat cond tr8 atcc 90 u tcm yltc 84 uv2 ptuv 27 u...

  • Page 5

    Ret650 a05 - 3 winding transformer protection 20ai 2*(6i+4u) w1 t3w pdif 87t 3id/i cc rbrf 50bf 3i> bf cc rbrf 50bf 3i> bf oc4 ptoc 50/51 3i> oc4 ptoc 51/67 3i> cc rpld 52pd pd cc rbrf 50bf 3i> bf cc rpld 52pd pd ef4 ptoc 51n in> cc rpld 52pd pd tr pttr 49 ith tr pttr 49 ith v msqi meter. C msqi met...

  • Page 6

    Ret650 a07 – oltc control for 1 or 2 transformers 10ai (6i+4u) tr pttr 49 ith ef4 ptoc 51n/67n in> cv mmxn meter. T1 oc4 ptoc 50/51 3i> etp mmtr meter. Rov ptov 59n 3u0> t2 trx atcc 90 u uv2 ptov 27 u ov2 ptov 59 u> tr pttr 49 ith ef4 ptoc 51n/67n in> cv mmxn meter. Oc4 ptoc 50/51 3i> etp mmtr meter...

  • Page 7

    3. Available functions main protection functions iec 61850 or function name ansi function description transformer ret650 ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc differential protection t2wpdif 87t transformer differential protection, two winding 0–1 1 t3wpdif 87t transformer differ...

  • Page 8

    Back-up protection functions iec 61850 or function name ansi function description transformer ret650 ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc current protection phpioc 50 instantaneous phase overcurrent protection, 3–phase output 0–3 2 3 oc4ptoc 51/67 four step phase overcurrent pro...

  • Page 9

    Control and monitoring functions iec 61850 or function name ansi function description transformer ret650 ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc control tr8atcc 90 automatic voltage control for tap changer, parallel control 0–2 1 1 2 tcmyltc 84 tap changer control and supervision, ...

  • Page 10

    Iec 61850 or function name ansi function description transformer ret650 ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc loopdelay configurable logic blocks 40 40 40 40 timerset configurable logic blocks 40 40 40 40 and configurable logic blocks 280 280 280 280 srmemory configurable logic b...

  • Page 11

    Iec 61850 or function name ansi function description transformer ret650 ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc tm_p_p2 function block for service values presentation of primary analog inputs 600trm 1 1 1 1 am_p_p4 function block for service values presentation of primary analog in...

  • Page 12

    Station communication iec 61850 or function name ansi function description transformer ret650 ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc station communication iec61850-8-1 iec 61850 communication protocol 1 1 1 1 dnpgen dnp3.0 communication general protocol 1 1 1 1 rs485dnp dnp3.0 for...

  • Page 13

    Iec 61850 or function name ansi function description transformer ret650 ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc agsal generic security application component 1 1 1 1 goosedprcv goose function block to receive a double point value 32 32 32 32 gooseintrcv goose function block to recei...

  • Page 14

    4. Differential protection transformer differential protection t2wpdif/t3wpdif the transformer differential protection, two-winding t2wpdif and transformer differential protection, three-winding t3wpdif are provided with internal ct ratio matching and vector group compensation and settable zero sequ...

  • Page 15

    Iec07000117-2-en.Vsd jx operation area operation area r operation area no operation area no operation area iec07000117 v2 en figure 5. Load encroachment influence on the offset mho z3 characteristic load encroachment lepdis heavy load transfer is common in many power networks and may make fault resi...

  • Page 16

    Breakers in case the own breaker fails to open. Ccrbrf can be current based, contact based, or an adaptive combination of these two conditions. Current check with extremely short reset time is used as check criterion to achieve high security against inadvertent operation. Contact check criteria can ...

  • Page 17

    Rov2ptov has two voltage steps, where step 1 can be set as inverse or definite time delayed. Step 2 is always definite time delayed. Overexcitation protection oexpvph when the laminated core of a power transformer or generator is subjected to a magnetic flux density beyond its design limits, stray f...

  • Page 18

    To operate is given after evaluation of conditions from other functions such as interlocking, synchrocheck, operator place selection and external or internal blockings. Apparatus control features: • select-execute principle to give high reliability • selection function to prevent simultaneous operat...

  • Page 19

    Locremctrl to the bay control qcbay function block. A parameter in function block locrem is set to choose if the switch signals are coming from the local hmi or from an external hardware switch connected via binary inputs. Voltage control tr8atcc and tcmyltc automatic voltage control for tap changer...

  • Page 20

    Automationbits autobits the automation bits function autobits is used to configure the dnp3 protocol command handling. Each of the 3 autobits available has 32 individual outputs available, each can be mapped as a binary output point in dnp3. Function commands for iec60870-5-103, i103cmd, i103iedcmd,...

  • Page 21

    To the state before the interruption, or be reset. The function also propagates timestamp and quality of input signal. • rsmemoryqt function block is a flip-flop that can reset or set an output from two inputs respectively. Each block has two outputs where one is inverted. The memory setting control...

  • Page 22

    Continuous event-logging is accomplished by the disturbance report functionality. Disturbance report drprdre, always included in the ied, acquires sampled data of all selected analog input and binary signals connected to the function block with a, maximum of 40 analog and 96 binary signals. The dist...

  • Page 23

    Measured value expander block mvexp the current and voltage measurements functions (cvmmxn, cmmxu, vmmxu and vnmmxu), current and voltage sequence measurement functions (cmsqi and vmsqi) and iec 61850 generic communication i/o functions (mvggio) are provided with measurement supervision functionalit...

  • Page 24

    The lhmi is simple and easy to understand. The whole front plate is divided into zones, each with a well-defined functionality: • status indication leds • alarm indication leds which can indicate three states with the colors green, yellow and red, with user defined and also printable label. All leds...

  • Page 25

    • local, through the local hmi • remote, through the communication ports the ied users can be created, deleted and edited only with pcm600 ied user management tool. Iec12000202-1-en.Vsd iec12000202 v1 en figure 10. Pcm600 user management tool authman this function enables/disables the maintenance me...

  • Page 26

    The denial of service functions doslan1 and dosfrnt are included to limit the inbound network traffic. The communication can thus never compromise the primary functionality of the ied. The event system has a rate limiter to reduce cpu load. The event channel has a quota of 10 events/second after the...

  • Page 27

    17. Hardware description layout and dimensions mounting alternatives • 19” rack mounting kit see ordering for details about available mounting alternatives. Rack mounting a single 3u ied b a c d iec11000248 v1 en figure 11. Rack mounted 3u ied a 224 mm + 12 mm with ring-lug connectors b 22.5 mm c 48...

  • Page 28

    18. Connection diagrams connection diagrams the connection diagrams are delivered on the ied connectivity package dvd as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/substationautomation . Connection diagrams for customized pr...

  • Page 29

    19. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 30

    Analog inputs table 2. Trm — energizing quantities, rated values and limits for transformer inputs description value frequency rated frequency f r 50 or 60 hz operating range f r ± 10% current inputs rated current i r 0.1 or 0.5 a 1) 1 or 5 a 2) operating range 0 – 50 a 0 – 500 a thermal withstand 1...

  • Page 31

    Auxiliary ac and dc voltage table 3. Power supply description psm01 psm02 psm03 u aux nominal 24, 30v dc 48, 60, 110, 125 v dc 100, 110, 120, 220, 240 v ac, 50 and 60 hz 110, 125, 220, 250 v dc u aux variation 80...120% of u n (19.2...36 v dc) 80...120% of u n (38.4...150 v dc) 80...110% of u n (80....

  • Page 32

    Table 6. Power output relays without tcs function description value rated voltage 250 v ac/dc continuous contact carry 8 a make and carry for 3.0 s 15 a make and carry for 0.5 s 30 a breaking capacity when the control-circuit time constant l/r u ≤1 a/≤0.3 a/≤0.1 a table 7. Power output relays with t...

  • Page 33

    Table 11. Irig-b type value accuracy input impedance 430 ohm - minimum input voltage high 4.3 v - maximum input voltage low 0.8 v - table 12. Eia-485 interface type value conditions minimum differential driver output voltage 1.5 v – maximum output current 60 ma - minimum differential receiver input ...

  • Page 34

    Table 16. Environmental conditions description value operating temperature range -25...+55ºc (continuous) short-time service temperature range -40...+70ºc ( note: degradation in mtbf and hmi performance outside the temperature range of -25...+55ºc relative humidity atmospheric pressure 86...106 kpa ...

  • Page 35

    Type tests according to standards table 18. Electromagnetic compatibility tests description type test value reference 100 khz and 1 mhz burst disturbance test iec 61000-4-18, level 3 iec 60255-22-1 ansi c37.90.1-2012 • common mode 2.5 kv • differential mode 2.5 kv electrostatic discharge test iec 61...

  • Page 36

    Table 18. Electromagnetic compatibility tests, continued description type test value reference voltage dips and interruptions on ac power supply dips: 40% 10/12 cycles at 50/60 hz 70% 25/30 cycles at 50/60 hz interruptions: 0–50 ms: no restart 0...∞ s: correct behaviour at power down iec 60255–11 ie...

  • Page 37

    Table 20. Mechanical tests description reference requirement vibration response tests (sinusoidal) iec 60255-21-1 class 1 vibration endurance test iec60255-21-1 class 1 shock response test iec 60255-21-2 class 1 shock withstand test iec 60255-21-2 class 1 bump test iec 60255-21-2 class 1 seismic tes...

  • Page 38

    Differential protection table 23. Transformer differential protection t2wpdif, t3wpdif function range or value accuracy operating characteristic adaptable ± 1.0% of ir for i ± 1.0% of i for i > ir reset ratio >94% - unrestrained differential current limit (1.00-50.00)x ibase on high voltage winding ...

  • Page 39

    Table 25. 1ph high impedance differential protection hzpdif function range or value accuracy operate voltage (20-400) v i=u/r ± 1.0% of i r reset ratio >95% - maximum continuous power u>trip 2 /seriesresistor ≤200 w - operate time 10 ms typically at 0 to 10 x u d - reset time 100 ms typically at 10 ...

  • Page 40

    Impedance protection table 26. Power swing detection zmrpsb function range or value accuracy reactive reach (0.10-3000.00) w/phase ± 2.0% static accuracy conditions: voltage range: (0.1-1.1) x u r current range: (0.5-30) x i r angle: at 0 degrees and 85 degrees resistive reach (0.10–1000.00) w/phase...

  • Page 41

    Current protection table 29. Instantaneous phase overcurrent protection, 3-phase output phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 20 ms typically at 0 to 2 x i set - reset time 30 ms typ...

  • Page 42

    Table 31. Instantaneous residual overcurrent protection efpioc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 20 ms typically at 0 to 2 x i set - reset time 30 ms typically at 2 to 0 x i set - criti...

  • Page 43

    Table 32. Four step residual overcurrent protection ef4ptoc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i r ± 1.0% of i at i > i r reset ratio > 95% - operate current for directional comparison, zero sequence (1–100)% of lbase ± 2.0% of i r operate current fo...

  • Page 44

    Table 33. Thermal overload protection, two time constants trpttr function range or value accuracy base current 1 and 2 (30–250)% of ibase ± 1.0% of i r operate time: 2 2 2 2 p ref i i t ln i i t æ ö - ç ÷ = × ç ÷ - è ø equation1356 v2 en (equation 1) i = actual measured current ip = load current bef...

  • Page 45

    Table 36. Directional over/underpower protection goppdop, guppdup function range or value accuracy power level (0.0–500.0)% of sbase ± 1.0% of s r at s r ± 1.0% of s at s > s r (1.0-2.0)% of sbase (2.0-10)% of sbase characteristic angle (-180.0–180.0) degrees 2 degrees timers (0.010 - 6000.000) s ± ...

  • Page 46

    Voltage protection table 38. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1–100)% of ubase ± 0.5% of u r reset ratio - inverse time characteristics for low and high step, see table 73 - see table 73 definite time delay, step 1 (0.00 - ...

  • Page 47

    Table 40. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 (1-200)% of ubase ± 0.5% of u r at u r ± 0.5% of u at u > u r operate voltage, step 2 (1–100)% of ubase ± 0.5% of u r at u r ± 0.5% of u at u > u r reset ratio > 98% - inverse time ch...

  • Page 48

    Frequency protection table 42. Under frequency protection saptuf function range or value accuracy operate value, start function (35.00-75.00) hz ± 2.0 mhz at symmetrical three- phase voltage operate value, restore frequency (45 - 65) hz ± 2.0 mhz reset ratio - operate time, start function at 50 hz: ...

  • Page 49

    Secondary system supervision table 45. Fuse failure supervision sddrfuf function range or value accuracy operate voltage, zero sequence (1-100)% of ubase ± 1.0% of u r operate current, zero sequence (1–100)% of ibase ± 1.0% of i r operate voltage, negative sequence (1–100)% of ubase ± 0.5% of u r op...

  • Page 50

    Control table 47. Voltage control tr8atcc, tcmyltc function range or value accuracy transformer reactance on atcc side (0.1–200.0)Ω, primary - time delay for lower command when fast step down mode is activated (1.0–100.0) s - voltage control set voltage (85.0–120.0)% of ub2 ±0.5% of u r outer voltag...

  • Page 51

    Table 49. Configurable logic blocks logic block quantity with cycle time range or value accuracy 5 ms 20 ms 100 ms and 60 60 160 - - or 60 60 160 - - xor 10 10 20 - - inverter 30 30 80 - - srmemory 10 10 20 - - rsmemory 10 10 20 - - gate 10 10 20 - - pulsetimer 10 10 20 (0.000–90000.000) s ± 0.5% ± ...

  • Page 52

    Monitoring table 52. Technical data covering measurement functions: cvmmxn, cmmxu, vmmxu, cmsqi, vmsqi, vnmmxu function range or value accuracy voltage (0.1-1.5) ×u r ± 0.5% of u r at u£u r ± 0.5% of u at u > u r connected current (0.2-4.0) × i r ± 0.5% of i r at i £ i r ± 0.5% of i at i > i r activ...

  • Page 53

    Table 55. Disturbance report drprdre function range or value accuracy current recording - ± 1,0% of i r at i ≤ i r ± 1,0% of i at i > ir voltage recording - ± 1,0% of u r at u ≤ u r ± 1,0% of u at u > u r pre-fault time (0.05–3.00) s - post-fault time (0.1–10.0) s - limit time (0.5–8.0) s - maximum ...

  • Page 54

    Table 58. Event recorder drprdre function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance reports 100 resolution 1 ms accuracy depending on time synchronizing table 59. Trip value recorder drprdre function value buffer capacity maximum number of...

  • Page 55

    Table 64. Circuit breaker condition monitoring sscbr function range or value accuracy alarm levels for open and close travel time (0-200) ms ± 0.5% ± 25 ms alarm levels for number of operations (0 - 9999) - setting of alarm for spring charging time (0.00-60.00) s ± 0.5% ± 25 ms time delay for gas pr...

  • Page 56

    Station communication table 67. Communication protocol function value protocol tcp/ip ethernet communication speed for the ieds 100 mbit/s protocol iec 61850–8–1 communication speed for the ieds 100base-fx protocol dnp3.0/tcp communication speed for the ieds 100base-fx protocol, serial iec 60870–5–1...

  • Page 57

    Inverse time characteristics table 69. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en i = i measured /i set k = (0.05-999) in steps of 0.01 - ansi extremely inverse a=28.2, b=0...

  • Page 58

    Table 71. Ri and rd type inverse time characteristics function range or value accuracy ri type inverse characteristic 1 0.236 0.339 = × - t k i equation1137-small v1 en i = i measured /i set k = (0.05-999) in steps of 0.01 rd type logarithmic inverse characteristic 5.8 1.35 = - × æ ö ç ÷ è ø t i in ...

  • Page 59

    Table 73. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en u set u = uv measured k = (0.05-1.10) in steps of 0.01 ±5% +60 ms type b curve: 2.0 480 0.055 32 0.5 × = + × - æ ö ç ÷ è ø k t u u u equa...

  • Page 60

    20. Ordering for customized ied guidelines carefully read and follow the set of rules to ensure order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Product specification basic ied 650 ...

  • Page 61

    Logic rule: one tripping logic must be ordered tripping logic, common 3–phase output smpptrc qty: 1 2 3 1mrk 004 922-aa optional functions differential protection restricted earth fault protection, low impedance refpdif qty: 1 2 3 1mrk 004 904-ca 1ph high impedance differential protection hzpdif qty...

  • Page 62

    Voltage protection two step undervoltage protection uv2ptuv qty: 1 2 1mrk 004 910-ab two step overvoltage protection ov2ptov qty: 1 2 1mrk 004 910-bb two step residual overvoltage protection rov2ptov qty: 1 2 1mrk 004 910-cb overexcitation protection oexpvph qty: 1mrk 004 910-dc frequency protection...

  • Page 63

    Additional local hmi user dialogue language hmi language, english us 1mrk 002 940-ma optional hardware human machine interface rule: one must be ordered. Display type keypad symbol case size local human machine interface lhmi01 iec 3u 1/1 19" 1khl160055r0001 local human machine interface lhmi01 ansi...

  • Page 64

    21. Ordering for configured ied guidelines carefully read and follow the set of rules to ensure order management. Please refer to the available functions table for included application functions. To obtain the complete ordering code, please combine code from the tables, as given in the example below...

  • Page 65

    Connection type for power supply, input/output and communication modules #7 notes and rules compression terminals s ringlug terminals r power supply slot position: ppsm 100-240v ac, 110-250v dc, 9bo, psm03 a 48-125v dc, 9bo, psm02 b 24–30v dc, 9bo, psm01 c selection for position #7. Human machine in...

  • Page 66

    22. Ordering for accessories external resistor unit high impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100v operating voltage quantity: 1 2 rk 795 101-ma high impedance resistor unit 1-ph with resistor and voltage dependent resistor for 100-400v operating voltage q...

  • Page 67

    Rule: specify the number of printed manuals requested operation manual iec quantity: 1mrk 500 096-uen technical manual iec quantity: 1mrk 504 135-uen commissioning manual iec quantity: 1mrk 504 136-uen application manual iec quantity: 1mrk 504 134-uen communication protocol manual, dnp3 iec quantity...

  • Page 68

    Related documents documents related to ret650 identity number application manual 1mrk 504 134-uen technical manual 1mrk 504 135-uen commissioning manual 1mrk 504 136-uen product guide, configured 1mrk 504 137-ben type test certificate 1mrk 504 137-ten application notes for circuit breaker control 1m...

  • Page 69

    69.

  • Page 70

    Contact us for more information please contact: abb ab grid automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 www.Abb.Com/protection-control note: we reserve the right to make technical changes or modify the contents of this document without prior notice. Abb ab does not accep...