Abrelex EnerSolis ES 10000 User Manual - page 22
42
DC Connector
Connector
Communication
Communication
Interfaces
Standard
RS-232 & RS-485
Optional
USB, RS-485, Dry contact, TCP / IP, WiFi
Front Panel
LCD
Boost input Voltage / Boost input Current / Boost input Power /
AC output Voltage / AC output frequency / AC output current /
AC output power / AC Energy / yield / Inner Temperature /
Heat sink Temperature / Status message / Error message
LED
RED
On: Ground fault or DC input insulation fault
Yellow
On: Unit Error or Alarm
Green
Flash: Standby or Sleeping mode
On: Normal Operation
Key Pad
Up key / Down key / Function key / Enter key
Protection
Utility
Over / under Voltage, Over / under Frequency,
Ground fault, DC Isolation fault
Islanding operation
detection
Passive: Voltage phase jump detection
Active: Reactive power control
Over temperature
Downgraded output power
Certification
On-Grid Performance
VDE 0126-1-1, VDE AR-N 4105, AS 4777.2/.3
ENEL 2010, G83/1
VDE 0126-1-1,
VDE AR-N 4105
Safety
EN 62109-1, EN 62109-2, EN 60730, AS 3100
EMI/EMC
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4,
EN 61000-3-2, EN 61000-3-3
Note:
1.
This product can cause current with a d.c. component. Where a residual current operated
protective (RCD) or monitoring (RCM) device is used for protection in case if direct or indirect
contact, only an RCD or RCM of Type B is allowed on the supply side of this product.
2.
The PV modules must be have an IEC 61730 Class A rating.