ABS Sanimat 1501S Installation And Operating Instructions Manual - page 11
11
ABS lifting station Sanimat
Control line (3) has a continuous rise as shown in Figure 9.
The control line should be shortened where necessary, pushed on to the hose nozzle of the submerged tube
screw connector (5).
The submerged tube screw connector (5) is prevented from turning by using an open ended spanner SW 13
and a spigot nut (4) is fully tightened.
ATTENTION
Thesubmergedtubefixingscrew(5)shouldnotbetwisted.
4.
f h
ATTENTION
Thecontrolunitshouldbefittedabovepossiblefloodlevelinawellventilatedroom
andinaneasilyaccessibleposition.ProtectionClassofthecontrolunitIP54.
The control unit should be secured at all fixing points. The fixing holes are accessible after unscrewing the
lower housing cover.
ATTENTION
Donotdrillthroughthehousingofthecontrolunititself.
NOTE
Themountinglocationofthecontrolunitshouldbechoseninsuchamannerthatthe
controllinerisesinacontinuousmannertothecontrolunit.Thecontrollinemustnot
bekinked.
NOTE
Anumberofdifferentcontrolboxmodelsexist.Pleasecheckthewiringdiagram/
instructionmanualinthecontrolbox.
4.
E C
c
Before commissioning an expert should check that one of the necessary electrical protective devices
is available. Earthing, neutral, earth leakage circuit breakers, etc. must comply with the regulations
of the local electricity supply authority and a qualified person should check that these are in perfect
order.
ATTENTION
ThepowersupplysystemonsitemustcomplywithVDEorotherlocalregulations
withregardtocross-sectionalareaandmaximumvoltagedrop.Thevoltagestatedon
thenameplateofthepumpmustcorrespondtothatofthemains
The power supply cable must be protected by an adequately dimensioned slow-blow fuse corresponding to the
rated power of the pump.
c
The incoming power supply as well as the connection of the pump itself to the terminals on the control
panel must comply with the circuit diagram of the control panel as well as the motor connection
diagrams and must be carried out by a qualified person.
All relevant safety regulators as well as general good technical practice must be complied with.
NOTE
Theoverloadrelayinthecontrolunithasbeencorrectlysetatthefactory.
NOTE
Pleaseconsultyourelectrician.