ABS Sanimat 1501S Installation And Operating Instructions Manual - page 13
13
ABS lifting station Sanimat
4.10
Ch k f
m
The safety hints in the previous sections must be observed!
When three phase units are being commissioned for the first time and also when used on a new site, the
direction of rotation must be carefully checked by a qualified person.
c
The direction of rotation should only be altered by a qualified person.
ATTENTION
Thefollowingcharacteristicsofasubmersiblepumpindicateaprobableincorrect
directionofrotation.
Submersible pump runs unevenly and vibrates strongly.
Submersible pump does not achieve full output and the emptying times for the collection tank are too long.
The submersible pump makes unusual running noises.
4.11
f h
4.11.1 f h H M mb P m (w m )
1086-00
Figure 17 Installation of hand membrane pump
ATTENTION
Thedischargeline(1)fromthehandmembranepumpmustbeinstalled
independentlyofthedischargelineoftheABSsubmersiblesewagepump,and
likewisemustbeprovidedwithananti-siphonlooplocatedabovethesewer
backwashlevel.Thedischargelinesmustbebroughttoalocationaftertheanti-
siphonloop.
Determine a fixing location for the hand membrane pump, which is easily accessible and fasten using plugs (3)
and screws (7).
Open the connection port (8) on the collection tank in accordance with Figure 5 using a saw.
Bring the pipe line (6) from the hand membrane pump to the collection tank and connect to the outlet port (8)
chosen with the aid of flexible junction piece (4) including clamps.
ATTENTION
Thehandmembranepumpshouldneverbefastenedtothecollectiontank.