S q m
The rooms in which lifting stations are installed must be of adequate dimensions so that beside and over all
control elements or items where maintenance might be required a working area of at least 60 cm width or height
is available.
Electrical supply to suit the submersible pumps being used.
NOTE
Fusing,cablecross-sectionandvoltagedropofthepowerlinemustcomplywith
DIN/ENandtherelevantelectricitysupplyboardregulations.
Any openings required in walls or ceilings for discharge, vent or inlet lines, must be of adequate dimensions so
that the openings used can be sealed off using noise absorbing materials.
The inlet lines must be laid in such a manner that there is a continuous fall of the prescribed magnitude to the
inlet ports of the collection tank.
NOTE
WheninstallingliftingstationsthenoiseprotectionregulationsinbuildingstoDIN
4109shouldbeobserved.
4.
f h k
Determine the installation location and set-up the tank so that it is on level ground and horizontal in all
directions.
Secure the collection tank against movement or floating with the aid of plugs (3) hex screws (2) and washers (2).
ATTENTION
Providealsoforlaterpositioningofthesubmersiblepumps.Thesubmersiblepumps
shouldbeinstalledonthegroundatthesamelevelasthecollectiontank.
ATTENTION
Donotover-tightenhexscrew(2),orthecollectiontank(1)maybedamaged.
1033-00
Figure 4 Bolting down of the collection tank
NOTE
Hexagonheadwoodscrew10x130dowelsize12(notsupplied)