14
ABS lifting station Sanimat
5
C mm
m
The safety hints in the previous sections must be observed!
Before commissioning the unit should be checked and a functional test carried out. Particular attention should
be paid to the following:
Have the electrical connections been carried out in accordance with regulations?
Is the direction of rotation correct - even if run via an emergency generator?
Was the control line (plastic hose) laid in such a manner that it has a continuous rise?
Was the collection tank secured against floating?
Has venting been installed in accordance with the regulations?
ATTENTION
Beforecommissioningthecollectiontankshouldbecleanedofanylargeparticles
andfilledwithwater.Ifthecontrolline(plastichose)wasconnectedtothe
submergedtubewiththetankalreadyfull,thenthecollectiontankmustbefully
emptiedoncebyactivationoftheselectorswitch“Hand”.Aftercommissioningthe
faecalliftingstationisnormallyoperatedwiththeselectorswitchinposition“Auto”.
6
M
c
Before commencing any maintenance work the unit should be completely disconnected from the
mains by a qualified person and care should be taken that it cannot be inadvertently switched back on.
m
When carrying out any repair or maintenance work, the safety regulations covering work in enclosed
areas of sewage installations as well as good general technical pratices should be followed.
NOTE
Themaintenancehintsgivenherearenotdesignedfor“do-it-yourself”repairsas
specialtechnicalknowledgeisrequired.
NOTE
Amaintenancecontractwithourworksservicedepartmentwillguaranteeyouthe
besttechnicalserviceunderallcircumstances.
6.1
C mm y m fL f S w hEN1056.
It is recommended that the lifting station be inspected monthly and its function checked.
In accordance with EN regulations, the lifting station should be maintained by a qualified person at the following
intervals:
in commercial premises - every three months.
in apartment blocks - every six months.
in a single family home - once a year.
In addition we recommend that a maintenance contract be taken out with a qualified company.
-
-
-
-
-
-
-
-
-