Powerware 9395 ups and plus 1 ups 450–550 kva installation and operation manual ®.
Page 2
Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...
Page 3
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com i table of contents 1 introduction 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 4
Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com ii 4.6 installing ups external and battery power wiring 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 5
Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com iii 7.3 single ups operation 7−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 6
Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com iv 8 communication 8−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 ...
Page 7
Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com v list of figures figure 1-2. Powerware 9395 plus 1 ups (450–550 kva) cabinet with the field installed upm 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 8
Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com vi figure 6-1. Main elements of the ups system 6−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 9
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−1 chapter 1 introduction eaton’s powerware 9395 uninterruptible power supply (ups) is a true online, continuous−duty, transformerless, double−conversion, solid−state, three−phase system, ...
Page 10
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−2 isbm or iom section upm section figure 1-1. Powerware 9395 ups (450–550 kva) cabinet.
Page 11
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−3 isbm or iom section upm section fi−upm figure 1-2. Powerware 9395 plus 1 ups (450–550 kva) cabinet with the field installed upm.
Page 12
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−4 1.1.2 control panel the control panel, located on the front of the ups, contains a liquid crystal display (lcd) and pushbutton switches to control the operation of the ups ...
Page 13
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−5 1.2.3 maintenance bypass module the maintenance bypass module (mbm) enables power to completely bypass and isolate the ups so that the ups can be safely serviced or replace...
Page 14
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−6 1.2.8 input output module configuration the ups can be supplied in an input output module (iom) configuration without the bypass input connections, the static switch, the m...
Page 15
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−7 s enotify remote monitoring and diagnostics service – an optional service that provides 24/7 remote monitoring of 43 alarms, temperature/humidity and battery charge informa...
Page 16
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−8 1.5 using this manual this manual describes how to install and operate the powerware 9395 ups (450–550 kva) cabinet. Read and understand the procedures described in this ma...
Page 17
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−9 1.7 symbols, controls, and indicators the following are examples of symbols used on the ups or accessories to alert you to important information: risk of electric shock − o...
Page 18
Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−10 1.8 for more information refer to the powerware 9395 integrated battery cabinet (model ibc−l) installation manual for the following additional information: s integrated ba...
Page 19
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−1 chapter 2 safety warnings important safety instructions save these instructions this manual contains important instructions that should be followed during installation and maintenance o...
Page 20
Safety warnings eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−2 s the operating environment should be maintained within the parameters stated in this manual. S keep surroundings uncluttered, clean, and free from excess moisture. S ob...
Page 21
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−1 section i installation.
Page 22
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−2.
Page 23
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−1 chapter 3 ups installation plan and unpacking use the following basic sequence of steps to install the ups: 1. Create an installation plan for the ups system (chapter 3). 2. Prepare you...
Page 24
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−2 for field installed upm (fi−upm) weights and dimensions, refer to the powerware 9395 field installed upm mechanical installation manual, listed in pa...
Page 25
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−3 dimensions are in millimeters [inches]. Figure 3-1. Ups cabinet dimensions (front view) dimensions are in millimeters [inches]. Figure 3-2. Ups cabin...
Page 26
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−4 front dimensions are in millimeters [inches]. Figure 3-3. Ups cabinet dimensions (top view) front dimensions are in millimeters [inches]. Figure 3-4....
Page 27
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−5 1873.9 [73.8] 1873.8 [73.8] 830 [32.7] 929.4 [36.6] 1140.2 [44.9] 435.2 [17.1] cg cg dimensions are in millimeters [inches]. Figure 3-6. Ups cabinet ...
Page 28
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−6 3.2.2 ups system power wiring preparation read and understand the following notes while planning and performing the installation: s refer to national...
Page 29
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−7 if the power rating listed on the nameplate of the installed ups is not found in the following tables, wire the ups using the fully rated specificati...
Page 30
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−8 for external wiring requirements, including the minimum awg size of external wiring, see table 3-4 for common battery system installations, table 3-5...
Page 31
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−9 table 3-5. Input/output ratings and external wiring requirements for the powerware 9395−550/450, 9395−550/500, and 9395−550/550 – separate battery ba...
Page 32
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−10 ac input to the ups with separate rectifier inputs is wired as if each upm is rated for 275 kva (see table 3-6). The bypass input, battery input, an...
Page 33
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−11 for a ups with common rectifier input terminals, e1 through e12 are 2-hole bus bar mountings for standard nema 2-hole barrel lugs. The power wiring ...
Page 34
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−12 table 3-8. Supplied terminal hardware kit part size quantity terminals used on eaton part number bolt, grade 5 m10 x 30 mm 23 ground and neutral 180...
Page 35
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−13 conduit sizes were chosen from nec table 4, electrical metallic tubing (emt). See table 3-11 for conduit requirements. Per nec article 300, 3(b)(1),...
Page 36
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−14 external overcurrent protection and disconnect are not provided by this product, but are required by codes. Refer to table 3-4 on page 3−8, table 3-...
Page 37
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−15 table 3-14. Recommended bypass, output, and mob circuit breaker ratings ups model output rating load rating 480v powerware 9395−550/450 80% rated 70...
Page 38
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−16 3.2.3 ups system interface wiring preparation control wiring for features and options should be connected at the customer interface terminal blocks ...
Page 39
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−17 3.2.4 distributed bypass power wiring preparation read and understand the following notes while planning and performing the installation: s all dist...
Page 40
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−18 3.3 inspecting and unpacking the ups cabinet the ups cabinet is palleted separately for shipping. The cabinet is shipped bolted to a wooden pallet (...
Page 41
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−19 note the ups cabinet is shipped with debris shields covering the ventilation grills on top of the unit. Do not remove the debris shields until insta...
Page 42
Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−20 this page intentionally left blank..
Page 43
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−1 chapter 4 ups system installation 4.1 preliminary installation information w a r n i n g installation should be performed only by qualified personnel. Refer to the following while insta...
Page 44
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−2 note for the following steps, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see table 3-1 on page 3−2 for cabinet weight)...
Page 45
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−3 shipping bracket bolts shipping bracket bolts pallet left side shipping bracket upm removable front panels figure 4-1. Removing the left side shipping bracket.
Page 46
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−4 shipping bracket bolts shipping bracket bolts front door removable left front panel pallet right side shipping bracket figure 4-2. Removing the right side shippi...
Page 47
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−5 4.3 field installed upm installation if installing a plus 1 model, install the fi−upm using the instructions in the powerware 9395 field installed upm mechanical...
Page 48
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−6 4.6 installing ups external and battery power wiring note the ups cabinet is shipped with debris shields covering the ventilation grills on top of the cabinet. D...
Page 49
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−7 top entry conduit landing for ac input and output, and dc input (remove panel to drill or punch conduit holes.) top view interface entry conduit landings for tb1...
Page 50
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−8 7. Proceed to step 10. 8. Using hardware from the external wiring terminal hardware kit (see table 3-8 on page 3−12), connect phase a, b, and c rectifier input p...
Page 51
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−9 note required parallel system wiring length must be equal to ensure approximately equal current sharing when in bypass mode. For proper operation the following m...
Page 52
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−10 (see figure 4-6 for detail aa.) dc input from battery + (e4) – (e5) dc input from battery (e12) neutral ac input to ups rectifier (a, b, c) ac output to critica...
Page 53
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−11 ground terminals ac output to critical load phase c (e8) phase a (e6) phase b (e7) (e12) neutral ac input to ups rectifier phase a (e1) phase c (e3) phase b (e2...
Page 54
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−12 (see figure 4-8 for detail aa.) dc input from battery + (e4) – (e5) dc input from battery (e12) neutral ac input to upm rectifiers (a, b, c) ac output to critic...
Page 55
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−13 ground terminals ac output to critical load phase c (e8) phase a (e6) phase b (e7) (e12) neutral upm rectifier input terminal block phase c (e11) phase a (e9) p...
Page 56
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−14 4.6.2 battery power wiring c a u t i o n when sizing the battery system, do not exceed the internal battery charger capabilities. See chapter 10, product specif...
Page 57
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−15 dc input from battery + (e4) – (e5) dc input from battery figure 4-10. Ups power terminal detail bb – common battery.
Page 58
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−16 dc input from battery + (e4) – (e5) dc input from battery dc input from battery + (e4) (upm 1) (upm 2) (upm 1) – (e5) dc input from battery (upm 2) (upm 4 – fi−...
Page 59
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−17 3. Remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door off. Retain the hardware for later us...
Page 60
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−18 x−slot communication bays tb3 tb1 and tb2 (see figure 4-13 for detail.) (see figure 4-15 on page 4−21 for terminal assignments.) (see figure 4-18 on page 4−24 f...
Page 61
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−19 table 4-1. Tb1, tb2, and tb3 interface connections terminal tb1 name description 1 repo nc input: normally-closed dry contact used to activate ups epo from a re...
Page 62
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−20 tb1 tb2 x−slot communication bays see figure 4-15 for terminal assignments. Figure 4-13. Interface terminal detail tb2 note alarm relay contacts have a maximum ...
Page 63
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−21 ups building alarm 3 building alarm 3 return building alarm 4 building alarm 5 building alarm 4 return building alarm 5 return note all building alarm inputs re...
Page 64
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−22 4.7.2 tb1 battery interface connections to install wiring to connections: 1. Verify the ups system is turned off and all power sources are removed. See chapter ...
Page 65
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−23 17. Reinstall the small top internal safety shield panel and secure with the cabinet mounted screws. 18. If wiring x−slot connections, proceed to paragraph 4.7....
Page 66
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−24 4.7.3 x−slot connections note lan and telephone drops for use with x−slot cards must be provided by the customer. Note when installing external wiring to x−slot...
Page 67
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−25 4.8 installing a repo switch a latching−type remote emergency power−off (repo) switch can be used in an emergency to shut down the ups and remove power to the c...
Page 68
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−26 6. If not already accomplished, remove one top screw and two bottom screws securing the ups left front panel (see figure 4-2 on page 4−4). Lift the panel straig...
Page 69
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−27 3 (no) ups tb1 repo switch (no) twisted wires 1 (nc) note repo switch rating is 24 vdc, 1a minimum. Note the repo switch must be a latching−type switch not tied...
Page 70
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−28 3 (no) ups tb1 repo switch (nc) twisted wires 1 (nc) 2 (return) 4 (return) note repo switch rating is 24 vdc, 1a minimum. Note the repo switch must be a latchin...
Page 71
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−29 4.9 installing options, accessories, and distributed bypass control wiring to install options, accessories, and distributed bypass control wiring, see chapter 5...
Page 72
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−30 installation checklist - all packing materials and restraints have been removed from each cabinet. - each cabinet in the ups system is placed in its installed l...
Page 73
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−31 distributed bypass installation checklist - each cabinet in the distributed bypass system is placed in its installed location. - all conduits and cables are pro...
Page 74
Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−32 notes _________________________________________________________________________ _________________________________________________________________________ ______...
Page 75
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−1 chapter 5 installing options and accessories 5.1 installing an optional powerware hot sync can bridge card as an option, a powerware hot sync controller area network (can) bridge card, ...
Page 76
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−2 7. Read and understand the following notes while planning and performing the wiring installation: s conduit must be installed between the ups cabinet ...
Page 77
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−3 connections for parallel system control connections for rmp ii, rim ii, or scm ii alarm j3 connections for bypass status figure 5-2. Powerware hot syn...
Page 78
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−4 5.2 installing distributed bypass control wiring note when installing external wiring to the powerware hot sync can bridge card, conduit must be insta...
Page 79
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−5 ups 1 ups 2 ups 3 ups 4 can (if installed) (if installed) pull chain note this drawing is for distributed bypass wiring purposes and is not a floor la...
Page 80
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−6 1 2 3 4 5 7 8 6 9 10 ups 1 twisted pair twisted pair twisted pair twisted pair twisted pair twisted pair 1 2 3 4 5 7 8 6 9 10 1 2 3 4 5 7 8 6 9 10 ups...
Page 81
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−7 note nc and no designations on mob aux contacts are defined with breaker in off (open) position. Note if mob contacts have pigtail leads, use the same...
Page 82
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−8 table 5-4. Pull−chain wiring terminations with mobs from to function ups 1 can bridge card j3–1 (alarm) mob 1 aux 1 nc mob open alarm ups 1 can bridge...
Page 83
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−9 note when installing signal wiring for can card j3 terminals, conduit must be installed between the device and the ups cabinet. 4. Remove the ups cabi...
Page 84
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−10 ups can card j3 120 vac from critical bus line neutral twisted pair ground terminal rmp ii, rim ii, or scm ii figure 5-8. Remote monitor panel ii, re...
Page 85
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−11 5.4 installing an optional relay interface module ii to install rim ii wiring: 1. Verify the ups system is turned off and all power sources are remov...
Page 86
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−12 table 5-6. J1 through j4 interface connectors status j1 through j4 description ups available pins 1 and 12 contacts are closed when the ups is operat...
Page 87
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−13 7. Install wiring between the ups and scm ii. See figure 5-2 and table 5-1 for the powerware hot sync can bridge card terminal location and wiring in...
Page 88
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−14 system normal no redundancy on generator bypass not available on battery ups alarm on bypass shutdown imminent figure 5-11. Supervisory contact modul...
Page 89
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−15 5.6 accessory mounting dimensions figure 5-12 through figure 5-14 show the dimensions of the rmp ii, the rim ii, and the scm ii. Flush mount using #1...
Page 90
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−16 knockouts provided on five surfaces surface mount using #10 pan head screws for hanging. (mount with vent holes facing up.) flush mount using #10 pan...
Page 91
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−17 knockouts provided on five surfaces surface mount using #10 pan head screws for hanging. (mount with vent holes facing up.) flush mount using #10 pan...
Page 92
Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−18 this page intentionally left blank..
Page 93
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−19 section ii operation.
Page 94
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−20
Page 95
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−1 chapter 6 understanding ups operation 6.1 ups system overview the powerware 9395 ups is a continuous−duty, solid-state, transformerless (at 480 vac), three−phase, true online system tha...
Page 96
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−2 the emergency bypass consists of a continuous−duty static switch and backfeed protection contactor k5. The backfeed protection contactor is located in series...
Page 97
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−3 static switch rectifier inverter k1 k3 battery converter battery battery breaker main power flow trickle current energized de−energized closed open breakers ...
Page 98
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−4 6.2.3 bypass mode the ups automatically switches to bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the co...
Page 99
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−5 6.2.4 energy saver mode when the ups is operating in energy saver mode, the bypass source supplies the commercial ac power to the load directly through the s...
Page 100
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−6 static switch k5 rectifier inverter k1 k3 battery converter battery battery breaker main power flow trickle current energized de−energized closed open breake...
Page 101
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−7 6.3 ups system oneline configurations the system oneline drawings in this section show the simplified internal structure of the ups, battery supply, and basi...
Page 102
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−8 input breaker (cb1) (optional) x−slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to table 3-4 on ...
Page 103
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−9 input breaker (cb1) (optional) x−slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to table 3-5 on ...
Page 104
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−10 input breaker (cb1) (optional) x−slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to table 3-4 on...
Page 105
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−11 input breaker (cb1) (optional) e1, e2, e3 e6, e7, e8, e12 note callout letters a , b , c , and d map to table 3-5 on page 3−9. Note if the load requires a n...
Page 106
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−12 input breaker (cb1) (optional) x−slot interface e1, e2, e3 48v battery shunt trip note callout letters a , c , and d map to table 3-4 on page 3−8. Note if t...
Page 107
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−13 input breaker (cb1) (optional) x−slot interface e1, e2, e3 48v battery shunt trip note callout letters a , c , and d map to table 3-5 on page 3−9. Note if t...
Page 108
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−14 input breaker (cb1) (optional) x−slot interface e1, e2, e3 48v battery shunt trip note callout letters a , c , and d map to table 3-4 on page 3−8. Note if t...
Page 109
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−15 input breaker (cb1) (optional) e1, e2, e3 note callout letters a , c , and d map to table 3-5 on page 3−9. Note if the load requires a neutral, a bypass sou...
Page 110
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−16 e1, e2, e3 e6, e7, e8, e12 note callout letter a maps to table 3-6 on page 3−10. Callout letters b , c , and d map to table 3-5 on page 3−9. Note if the loa...
Page 111
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−17 note callout letter a maps to table 3-6 on page 3−10. Callout letters b , c , and d map to table 3-5 on page 3−9. Note if the load requires a neutral, a byp...
Page 112
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−18 e1, e2, e3 note callout letter a maps to table 3-6 on page 3−10. Callout letters c and d map to table 3-5 on page 3−9. Note if the load requires a neutral, ...
Page 113
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−19 note callout letter a maps to table 3-6 on page 3−10. Callout letters c and d map to table 3-5 on page 3−9. Note if the load requires a neutral, a bypass so...
Page 114
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−20 maintenance bypass panel output from ups mis to ups rectifier input rib: rectifier input breaker bib: bypass input breaker mis: maintenance isolation breake...
Page 115
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−21 6.4 multiple ups distributed bypass system distributed bypass parallel operation extends the normal operation of powerware 9395 upss by offering increased c...
Page 116
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−22 the upss continually monitor themselves and the incoming utility power and automatically switch between these modes as required, without operator interventi...
Page 117
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−23 if the utility ac power is interrupted or is out of specification, the upss automatically switch to battery mode to support the critical load without interr...
Page 118
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−24 in a distributed bypass system, each ups operates similar to a single ups, but in parallel with each other. The bypass source for the load is derived from t...
Page 119
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−25 main power flow ups 1 ups 2 ups 3 ups 4 output to critical load battery ups input tie cabinet ups 1 output bypass input ups 2 output ups 3 output ups 4 outp...
Page 120
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−26 6.5 multiple ups distributed bypass system oneline configurations the distributed bypass system oneline drawings in this section show the simplified interna...
Page 121
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−27 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b tie c...
Page 122
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−28 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b tie c...
Page 123
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−29 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b tie c...
Page 124
Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−30 this page intentionally left blank..
Page 125
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−1 chapter 7 ups operating instructions this section describes how to operate the ups. Note before starting the ups, ensure all installation tasks are complete and a preliminary startup ha...
Page 126
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−2 7.1.1 control panel the control panel is used to set up and control the ups, and to monitor ups operation. For a description of the ups control panel function...
Page 127
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−3 7.2.1 status indicators the four symbols on the right side of the control panel are status indicators. These colored light emitting diode (led) lamps work wit...
Page 128
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−4 7.2.3 using the lcd and pushbuttons the lcd on the control panel provides an operator interface with the ups system. Figure 7-3 identifies the display areas d...
Page 129
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−5 7.2.4 using the menu the ups menu bar allows you to display data in the information area to help you monitor and control ups operation. Table 7-2 shows the ba...
Page 130
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−6 7.2.6 display menu operation table 7-3 describes the menu functions and and how to use them. Table 7-3. Display menu operation function subfunction operation ...
Page 131
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−7 table 7-3. Display menu operation (continued) operation subfunction function contrast adjust select contrast from the system setup level 0 menu to display the...
Page 132
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−8 table 7-3. Display menu operation (continued) operation subfunction function com port selection the com port setup screen allows selection of the serial com p...
Page 133
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−9 table 7-4. Typical system status messages function message ups shutdown; bypass; online; energy saver; high alert bypass off; on; available maintenance bypass...
Page 134
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−10 7.2.8 load off screen the load off screen (figure 7-6) is displayed when the load off pushbutton is selected from the main menu bar, the ups control command ...
Page 135
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−11 10. Close the battery breaker. 11. Verify no alarms are active. 12. On the system status screen, select the ups command. 13. Press the controls pushbutton on...
Page 136
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−12 8. Press the controls pushbutton on the main menu bar. The system status screen is displayed. 9. On the system status screen, verify the ups status is shutdo...
Page 137
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−13 16. Verify the following messages display sequentially on the upm status line: dc starting, charger off inverter starting inverter syncing ready the upm 1 re...
Page 138
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−14 9. On the system status screen, the ups status should indicate shutdown and the upm status should indicate offline. 10. Verify no alarms are active. 11. On t...
Page 139
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−15 5. Press the select pushbutton on the bypass command menu bar. The ups transfers to bypass mode and the critical load is immediately supplied by the bypass s...
Page 140
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−16 5. Press the select pushbutton on the ups command menu bar. The ups transfers to energy saver mode and the critical load is immediately supplied by the bypas...
Page 141
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−17 5. Press the select pushbutton on the ups command menu bar. The ups transfers to high alert mode, but remains online. After one hour the ups transfers to ene...
Page 142
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−18 7.3.12 transfer from energy saver to bypass mode to transfer the critical load to bypass mode: note the energy saver mode commands are displayed only if enab...
Page 143
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−19 7.3.14 transfer from high alert to bypass mode to transfer the critical load to bypass mode: note the high alert mode commands are displayed only if enabled ...
Page 144
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−20 7.3.16 transfer from high alert to energy saver mode to transfer the critical load to energy saver mode: note the high alert and energy saver mode commands a...
Page 145
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−21 10. Press the select pushbutton on the upm 1 command menu bar. The upm status indicates shutdown . The power module is turned off. Logic power remains on. 11...
Page 146
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−22 4. Press the controls pushbutton on the ups control command menu bar. The upm control command screen is displayed. 5. On the upm control command screen, sele...
Page 147
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−23 to turn the battery charger off: 1. Press the controls pushbutton on the main menu bar. The system status screen is displayed. 2. On the system status screen...
Page 148
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−24 3. Press the controls pushbutton on the system status menu bar. The ups or bypass control command screen is displayed. 4. On the control command screen, sele...
Page 149
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−25 7.3.23 using the remote emergency power−off switch a ups emergency power−off is initiated by the repo pushbutton switch. In an emergency, you can use this sw...
Page 150
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−26 7.4 multiple ups distributed bypass operation 7.4.1 starting the distributed bypass system in normal mode to start the distributed bypass system: 1. Unfasten...
Page 151
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−27 17. Verify the following messages display sequentially on the ups status line: dc starting, charger off inverter starting inverter syncing online, charger on...
Page 152
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−28 13. On the bypass control command screen, select go to bypass . 14. Press the select pushbutton on the bypass command menu bar. The critical load is immediat...
Page 153
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−29 17. Repeat steps 12 through 15 selecting upm 2 to start upm 2. 18. Verify the following messages display sequentially on the upm status line: dc starting, ch...
Page 154
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−30 13. Press the controls pushbutton on the ups control command menu bar. The upm control command screen is displayed. 14. On the upm control command screen, se...
Page 155
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−31 7.4.6 transfer from bypass to normal mode to transfer the critical load to normal mode: 1. If not already closed, close the battery breaker. 2. On any ups, p...
Page 156
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−32 7.4.8 transfer from energy saver to normal mode to transfer the critical load to normal mode: note the energy saver mode commands are displayed only if enabl...
Page 157
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−33 7.4.10 transfer from high alert to normal mode to transfer the critical load to normal mode: note the high alert mode commands are displayed only if enabled ...
Page 158
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−34 7.4.12 transfer from energy saver to bypass mode to transfer the critical load to bypass mode: note the energy saver mode commands are displayed only if enab...
Page 159
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−35 7.4.14 transfer from high alert to bypass mode to transfer the critical load to bypass mode: note the high alert mode commands are displayed only if enabled ...
Page 160
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−36 7.4.16 transfer from high alert to energy saver mode to transfer the critical load to energy saver mode: note the high alert and energy saver mode commands a...
Page 161
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−37 10. Press the select pushbutton on the upm 1 command menu bar. The upm status indicates shutdown . The power module is turned off. Logic power remains on. 11...
Page 162
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−38 3. On the ups control command screen, select the upm to restart. 4. Press the controls pushbutton on the ups control command menu bar. The upm control comman...
Page 163
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−39 7. Perform the load off procedure in paragraph 7.4.25 on the ups being shut down. The input, output, battery, and bypass backfeed contactors open, and the po...
Page 164
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−40 11. Press the select pushbutton on the upm 1 command menu bar. The upm status indicates shutdown . The input, output, and battery contactors open, and the po...
Page 165
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−41 11. Verify external communications failure alarm has cleared and no other alarms are active on the online upss. 12. On the system status screen, select the u...
Page 166
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−42 7.4.24 charger control to turn the battery charger on: 1. Press the controls pushbutton on the main menu bar. The system status screen is displayed. 2. On th...
Page 167
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−43 3. If another ups is to be shut down, proceed to that ups and repeat steps 1 and 2. C a u t i o n do not attempt to restart the system after load off until t...
Page 168
Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−44 7.4.26 using the remote emergency power−off switch a ups emergency power−off is initiated by the repo pushbutton switch. In an emergency, you can use this sw...
Page 169
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−1 chapter 8 communication this chapter describes the communication features of the powerware 9395 ups and provides information about connecting hardware and using terminal mode. For termi...
Page 170
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−2 lan and telephone drops for use with x−slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an x−slot card, contact...
Page 171
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−3 the enotify service relies on a connectups−x web/snmp card (or power xpert card) installed with the ups sending one−way status and event e−mails to powerware remote monito...
Page 172
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−4 remote notification differs from the basic terminal mode with the addition of the following functions: s call answer the call answer function allows the user to call into ...
Page 173
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−5 8.5.2 event history log this key sequence prints the entire event history log of the ups at the time the data is requested. The printout begins with the oldest alarm entry...
Page 174
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−6 model: powerware 9395 cto: tf12710000000 serial: mcu dsp: 70.81.14 mcu bootloader: 80.40 mcu pld: 1.00 pmf 1 dsp: 80.81.14 pmf 1 bootloader: 80.40 pmf 1 pld: 1.00 xslot ca...
Page 175
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−7 8.6 building alarm monitoring this standard feature lets you connect the ups to your building alarms, such as smoke detectors or overtemperature alarms. The customer inter...
Page 176
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−8 the rmp ii contains a local horn and the backlit status indicators listed in table 8-1. Table 8-1. Rmp ii status indicators system normal the ups is energized (either with...
Page 177
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−9 8.9 relay interface module ii an optional rim ii uses relay contact closures to indicate the operating status and alarm condition of the ups system. The module uses a seri...
Page 178
Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−10 8.10 supervisory contact module ii an optional scm ii establishes an interface between the ups system and the customer’s monitor. This interface allows the customer to mo...
Page 179
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−1 chapter 9 ups maintenance the components inside the ups cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little d...
Page 180
Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−2 s proper disposal of batteries is required. Refer to your local codes for disposal requirements. S do not dispose of batteries in a fire. Batteries may explode when expo...
Page 181
Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−3 isbm air filter locations upm air filter locations ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄ...
Page 182
Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−4 c a u t i o n verify washed filter is thoroughly dry before reinstalling. C. Push the washed or new foam filter over the screw heads on the cabinet mounted studs until s...
Page 183
Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−5 9.2.5 battery maintenance contact an eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorized ser...
Page 184
Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−6 this page intentionally left blank..
Page 185
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 10−1 chapter 10 product specifications 10.1 model numbers the ups is housed in a free-standing cabinet with safety shields behind the door and front panels. The ups is available in 50 or 60...
Page 186
Product specifications eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 10−2 10.2.2 ups output ups output capacity 100% rated current output voltage regulation "1% (10% to 100% load) output voltage adjustment (nominal +/–3%) 480 vac nomin...
Page 187
Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com w−1 warranty limited factory warranty for three-phase powerware ® ups products warrantor: the warrantor for the limited warranties set forth herein is eaton corporation, a delaware corporat...
Page 188
Warranty eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com w−2 this page intentionally left blank..