Summary of Powerware 9395

  • Page 1

    Powerware 9395 ups and plus 1 ups 450–550 kva installation and operation manual ®.

  • Page 2

    Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...

  • Page 3

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com i table of contents 1 introduction 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 4

    Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com ii 4.6 installing ups external and battery power wiring 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....

  • Page 5

    Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com iii 7.3 single ups operation 7−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....

  • Page 6

    Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com iv 8 communication 8−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 ...

  • Page 7

    Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com v list of figures figure 1-2. Powerware 9395 plus 1 ups (450–550 kva) cabinet with the field installed upm 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 8

    Table of contents eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com vi figure 6-1. Main elements of the ups system 6−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 9

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−1 chapter 1 introduction eaton’s powerware 9395 uninterruptible power supply (ups) is a true online, continuous−duty, transformerless, double−conversion, solid−state, three−phase system, ...

  • Page 10

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−2 isbm or iom section upm section figure 1-1. Powerware 9395 ups (450–550 kva) cabinet.

  • Page 11

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−3 isbm or iom section upm section fi−upm figure 1-2. Powerware 9395 plus 1 ups (450–550 kva) cabinet with the field installed upm.

  • Page 12

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−4 1.1.2 control panel the control panel, located on the front of the ups, contains a liquid crystal display (lcd) and pushbutton switches to control the operation of the ups ...

  • Page 13

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−5 1.2.3 maintenance bypass module the maintenance bypass module (mbm) enables power to completely bypass and isolate the ups so that the ups can be safely serviced or replace...

  • Page 14

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−6 1.2.8 input output module configuration the ups can be supplied in an input output module (iom) configuration without the bypass input connections, the static switch, the m...

  • Page 15

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−7 s enotify remote monitoring and diagnostics service – an optional service that provides 24/7 remote monitoring of 43 alarms, temperature/humidity and battery charge informa...

  • Page 16

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−8 1.5 using this manual this manual describes how to install and operate the powerware 9395 ups (450–550 kva) cabinet. Read and understand the procedures described in this ma...

  • Page 17

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−9 1.7 symbols, controls, and indicators the following are examples of symbols used on the ups or accessories to alert you to important information: risk of electric shock − o...

  • Page 18

    Introduction eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 1−10 1.8 for more information refer to the powerware 9395 integrated battery cabinet (model ibc−l) installation manual for the following additional information: s integrated ba...

  • Page 19

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−1 chapter 2 safety warnings important safety instructions save these instructions this manual contains important instructions that should be followed during installation and maintenance o...

  • Page 20

    Safety warnings eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−2 s the operating environment should be maintained within the parameters stated in this manual. S keep surroundings uncluttered, clean, and free from excess moisture. S ob...

  • Page 21

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−1 section i installation.

  • Page 22

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 2−2.

  • Page 23

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−1 chapter 3 ups installation plan and unpacking use the following basic sequence of steps to install the ups: 1. Create an installation plan for the ups system (chapter 3). 2. Prepare you...

  • Page 24

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−2 for field installed upm (fi−upm) weights and dimensions, refer to the powerware 9395 field installed upm mechanical installation manual, listed in pa...

  • Page 25

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−3 dimensions are in millimeters [inches]. Figure 3-1. Ups cabinet dimensions (front view) dimensions are in millimeters [inches]. Figure 3-2. Ups cabin...

  • Page 26

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−4 front dimensions are in millimeters [inches]. Figure 3-3. Ups cabinet dimensions (top view) front dimensions are in millimeters [inches]. Figure 3-4....

  • Page 27

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−5 1873.9 [73.8] 1873.8 [73.8] 830 [32.7] 929.4 [36.6] 1140.2 [44.9] 435.2 [17.1] cg cg dimensions are in millimeters [inches]. Figure 3-6. Ups cabinet ...

  • Page 28

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−6 3.2.2 ups system power wiring preparation read and understand the following notes while planning and performing the installation: s refer to national...

  • Page 29

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−7 if the power rating listed on the nameplate of the installed ups is not found in the following tables, wire the ups using the fully rated specificati...

  • Page 30

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−8 for external wiring requirements, including the minimum awg size of external wiring, see table 3-4 for common battery system installations, table 3-5...

  • Page 31

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−9 table 3-5. Input/output ratings and external wiring requirements for the powerware 9395−550/450, 9395−550/500, and 9395−550/550 – separate battery ba...

  • Page 32

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−10 ac input to the ups with separate rectifier inputs is wired as if each upm is rated for 275 kva (see table 3-6). The bypass input, battery input, an...

  • Page 33

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−11 for a ups with common rectifier input terminals, e1 through e12 are 2-hole bus bar mountings for standard nema 2-hole barrel lugs. The power wiring ...

  • Page 34

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−12 table 3-8. Supplied terminal hardware kit part size quantity terminals used on eaton part number bolt, grade 5 m10 x 30 mm 23 ground and neutral 180...

  • Page 35

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−13 conduit sizes were chosen from nec table 4, electrical metallic tubing (emt). See table 3-11 for conduit requirements. Per nec article 300, 3(b)(1),...

  • Page 36

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−14 external overcurrent protection and disconnect are not provided by this product, but are required by codes. Refer to table 3-4 on page 3−8, table 3-...

  • Page 37

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−15 table 3-14. Recommended bypass, output, and mob circuit breaker ratings ups model output rating load rating 480v powerware 9395−550/450 80% rated 70...

  • Page 38

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−16 3.2.3 ups system interface wiring preparation control wiring for features and options should be connected at the customer interface terminal blocks ...

  • Page 39

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−17 3.2.4 distributed bypass power wiring preparation read and understand the following notes while planning and performing the installation: s all dist...

  • Page 40

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−18 3.3 inspecting and unpacking the ups cabinet the ups cabinet is palleted separately for shipping. The cabinet is shipped bolted to a wooden pallet (...

  • Page 41

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−19 note the ups cabinet is shipped with debris shields covering the ventilation grills on top of the unit. Do not remove the debris shields until insta...

  • Page 42

    Ups installation plan and unpacking eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 3−20 this page intentionally left blank..

  • Page 43

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−1 chapter 4 ups system installation 4.1 preliminary installation information w a r n i n g installation should be performed only by qualified personnel. Refer to the following while insta...

  • Page 44

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−2 note for the following steps, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see table 3-1 on page 3−2 for cabinet weight)...

  • Page 45

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−3 shipping bracket bolts shipping bracket bolts pallet left side shipping bracket upm removable front panels figure 4-1. Removing the left side shipping bracket.

  • Page 46

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−4 shipping bracket bolts shipping bracket bolts front door removable left front panel pallet right side shipping bracket figure 4-2. Removing the right side shippi...

  • Page 47

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−5 4.3 field installed upm installation if installing a plus 1 model, install the fi−upm using the instructions in the powerware 9395 field installed upm mechanical...

  • Page 48

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−6 4.6 installing ups external and battery power wiring note the ups cabinet is shipped with debris shields covering the ventilation grills on top of the cabinet. D...

  • Page 49

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−7 top entry conduit landing for ac input and output, and dc input (remove panel to drill or punch conduit holes.) top view interface entry conduit landings for tb1...

  • Page 50

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−8 7. Proceed to step 10. 8. Using hardware from the external wiring terminal hardware kit (see table 3-8 on page 3−12), connect phase a, b, and c rectifier input p...

  • Page 51

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−9 note required parallel system wiring length must be equal to ensure approximately equal current sharing when in bypass mode. For proper operation the following m...

  • Page 52

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−10 (see figure 4-6 for detail aa.) dc input from battery + (e4) – (e5) dc input from battery (e12) neutral ac input to ups rectifier (a, b, c) ac output to critica...

  • Page 53

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−11 ground terminals ac output to critical load phase c (e8) phase a (e6) phase b (e7) (e12) neutral ac input to ups rectifier phase a (e1) phase c (e3) phase b (e2...

  • Page 54

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−12 (see figure 4-8 for detail aa.) dc input from battery + (e4) – (e5) dc input from battery (e12) neutral ac input to upm rectifiers (a, b, c) ac output to critic...

  • Page 55

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−13 ground terminals ac output to critical load phase c (e8) phase a (e6) phase b (e7) (e12) neutral upm rectifier input terminal block phase c (e11) phase a (e9) p...

  • Page 56

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−14 4.6.2 battery power wiring c a u t i o n when sizing the battery system, do not exceed the internal battery charger capabilities. See chapter 10, product specif...

  • Page 57

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−15 dc input from battery + (e4) – (e5) dc input from battery figure 4-10. Ups power terminal detail bb – common battery.

  • Page 58

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−16 dc input from battery + (e4) – (e5) dc input from battery dc input from battery + (e4) (upm 1) (upm 2) (upm 1) – (e5) dc input from battery (upm 2) (upm 4 – fi−...

  • Page 59

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−17 3. Remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door off. Retain the hardware for later us...

  • Page 60

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−18 x−slot communication bays tb3 tb1 and tb2 (see figure 4-13 for detail.) (see figure 4-15 on page 4−21 for terminal assignments.) (see figure 4-18 on page 4−24 f...

  • Page 61

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−19 table 4-1. Tb1, tb2, and tb3 interface connections terminal tb1 name description 1 repo nc input: normally-closed dry contact used to activate ups epo from a re...

  • Page 62

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−20 tb1 tb2 x−slot communication bays see figure 4-15 for terminal assignments. Figure 4-13. Interface terminal detail tb2 note alarm relay contacts have a maximum ...

  • Page 63

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−21 ups building alarm 3 building alarm 3 return building alarm 4 building alarm 5 building alarm 4 return building alarm 5 return note all building alarm inputs re...

  • Page 64

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−22 4.7.2 tb1 battery interface connections to install wiring to connections: 1. Verify the ups system is turned off and all power sources are removed. See chapter ...

  • Page 65

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−23 17. Reinstall the small top internal safety shield panel and secure with the cabinet mounted screws. 18. If wiring x−slot connections, proceed to paragraph 4.7....

  • Page 66

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−24 4.7.3 x−slot connections note lan and telephone drops for use with x−slot cards must be provided by the customer. Note when installing external wiring to x−slot...

  • Page 67

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−25 4.8 installing a repo switch a latching−type remote emergency power−off (repo) switch can be used in an emergency to shut down the ups and remove power to the c...

  • Page 68

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−26 6. If not already accomplished, remove one top screw and two bottom screws securing the ups left front panel (see figure 4-2 on page 4−4). Lift the panel straig...

  • Page 69

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−27 3 (no) ups tb1 repo switch (no) twisted wires 1 (nc) note repo switch rating is 24 vdc, 1a minimum. Note the repo switch must be a latching−type switch not tied...

  • Page 70

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−28 3 (no) ups tb1 repo switch (nc) twisted wires 1 (nc) 2 (return) 4 (return) note repo switch rating is 24 vdc, 1a minimum. Note the repo switch must be a latchin...

  • Page 71

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−29 4.9 installing options, accessories, and distributed bypass control wiring to install options, accessories, and distributed bypass control wiring, see chapter 5...

  • Page 72

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−30 installation checklist - all packing materials and restraints have been removed from each cabinet. - each cabinet in the ups system is placed in its installed l...

  • Page 73

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−31 distributed bypass installation checklist - each cabinet in the distributed bypass system is placed in its installed location. - all conduits and cables are pro...

  • Page 74

    Ups system installation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 4−32 notes _________________________________________________________________________ _________________________________________________________________________ ______...

  • Page 75

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−1 chapter 5 installing options and accessories 5.1 installing an optional powerware hot sync can bridge card as an option, a powerware hot sync controller area network (can) bridge card, ...

  • Page 76

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−2 7. Read and understand the following notes while planning and performing the wiring installation: s conduit must be installed between the ups cabinet ...

  • Page 77

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−3 connections for parallel system control connections for rmp ii, rim ii, or scm ii alarm j3 connections for bypass status figure 5-2. Powerware hot syn...

  • Page 78

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−4 5.2 installing distributed bypass control wiring note when installing external wiring to the powerware hot sync can bridge card, conduit must be insta...

  • Page 79

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−5 ups 1 ups 2 ups 3 ups 4 can (if installed) (if installed) pull chain note this drawing is for distributed bypass wiring purposes and is not a floor la...

  • Page 80

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−6 1 2 3 4 5 7 8 6 9 10 ups 1 twisted pair twisted pair twisted pair twisted pair twisted pair twisted pair 1 2 3 4 5 7 8 6 9 10 1 2 3 4 5 7 8 6 9 10 ups...

  • Page 81

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−7 note nc and no designations on mob aux contacts are defined with breaker in off (open) position. Note if mob contacts have pigtail leads, use the same...

  • Page 82

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−8 table 5-4. Pull−chain wiring terminations with mobs from to function ups 1 can bridge card j3–1 (alarm) mob 1 aux 1 nc mob open alarm ups 1 can bridge...

  • Page 83

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−9 note when installing signal wiring for can card j3 terminals, conduit must be installed between the device and the ups cabinet. 4. Remove the ups cabi...

  • Page 84

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−10 ups can card j3 120 vac from critical bus line neutral twisted pair ground terminal rmp ii, rim ii, or scm ii figure 5-8. Remote monitor panel ii, re...

  • Page 85

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−11 5.4 installing an optional relay interface module ii to install rim ii wiring: 1. Verify the ups system is turned off and all power sources are remov...

  • Page 86

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−12 table 5-6. J1 through j4 interface connectors status j1 through j4 description ups available pins 1 and 12 contacts are closed when the ups is operat...

  • Page 87

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−13 7. Install wiring between the ups and scm ii. See figure 5-2 and table 5-1 for the powerware hot sync can bridge card terminal location and wiring in...

  • Page 88

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−14 system normal no redundancy on generator bypass not available on battery ups alarm on bypass shutdown imminent figure 5-11. Supervisory contact modul...

  • Page 89

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−15 5.6 accessory mounting dimensions figure 5-12 through figure 5-14 show the dimensions of the rmp ii, the rim ii, and the scm ii. Flush mount using #1...

  • Page 90

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−16 knockouts provided on five surfaces surface mount using #10 pan head screws for hanging. (mount with vent holes facing up.) flush mount using #10 pan...

  • Page 91

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−17 knockouts provided on five surfaces surface mount using #10 pan head screws for hanging. (mount with vent holes facing up.) flush mount using #10 pan...

  • Page 92

    Installing options and accessories eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−18 this page intentionally left blank..

  • Page 93

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−19 section ii operation.

  • Page 94

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 5−20

  • Page 95

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−1 chapter 6 understanding ups operation 6.1 ups system overview the powerware 9395 ups is a continuous−duty, solid-state, transformerless (at 480 vac), three−phase, true online system tha...

  • Page 96

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−2 the emergency bypass consists of a continuous−duty static switch and backfeed protection contactor k5. The backfeed protection contactor is located in series...

  • Page 97

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−3 static switch rectifier inverter k1 k3 battery converter battery battery breaker main power flow trickle current energized de−energized closed open breakers ...

  • Page 98

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−4 6.2.3 bypass mode the ups automatically switches to bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the co...

  • Page 99

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−5 6.2.4 energy saver mode when the ups is operating in energy saver mode, the bypass source supplies the commercial ac power to the load directly through the s...

  • Page 100

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−6 static switch k5 rectifier inverter k1 k3 battery converter battery battery breaker main power flow trickle current energized de−energized closed open breake...

  • Page 101

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−7 6.3 ups system oneline configurations the system oneline drawings in this section show the simplified internal structure of the ups, battery supply, and basi...

  • Page 102

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−8 input breaker (cb1) (optional) x−slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to table 3-4 on ...

  • Page 103

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−9 input breaker (cb1) (optional) x−slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to table 3-5 on ...

  • Page 104

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−10 input breaker (cb1) (optional) x−slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to table 3-4 on...

  • Page 105

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−11 input breaker (cb1) (optional) e1, e2, e3 e6, e7, e8, e12 note callout letters a , b , c , and d map to table 3-5 on page 3−9. Note if the load requires a n...

  • Page 106

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−12 input breaker (cb1) (optional) x−slot interface e1, e2, e3 48v battery shunt trip note callout letters a , c , and d map to table 3-4 on page 3−8. Note if t...

  • Page 107

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−13 input breaker (cb1) (optional) x−slot interface e1, e2, e3 48v battery shunt trip note callout letters a , c , and d map to table 3-5 on page 3−9. Note if t...

  • Page 108

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−14 input breaker (cb1) (optional) x−slot interface e1, e2, e3 48v battery shunt trip note callout letters a , c , and d map to table 3-4 on page 3−8. Note if t...

  • Page 109

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−15 input breaker (cb1) (optional) e1, e2, e3 note callout letters a , c , and d map to table 3-5 on page 3−9. Note if the load requires a neutral, a bypass sou...

  • Page 110

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−16 e1, e2, e3 e6, e7, e8, e12 note callout letter a maps to table 3-6 on page 3−10. Callout letters b , c , and d map to table 3-5 on page 3−9. Note if the loa...

  • Page 111

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−17 note callout letter a maps to table 3-6 on page 3−10. Callout letters b , c , and d map to table 3-5 on page 3−9. Note if the load requires a neutral, a byp...

  • Page 112

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−18 e1, e2, e3 note callout letter a maps to table 3-6 on page 3−10. Callout letters c and d map to table 3-5 on page 3−9. Note if the load requires a neutral, ...

  • Page 113

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−19 note callout letter a maps to table 3-6 on page 3−10. Callout letters c and d map to table 3-5 on page 3−9. Note if the load requires a neutral, a bypass so...

  • Page 114

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−20 maintenance bypass panel output from ups mis to ups rectifier input rib: rectifier input breaker bib: bypass input breaker mis: maintenance isolation breake...

  • Page 115

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−21 6.4 multiple ups distributed bypass system distributed bypass parallel operation extends the normal operation of powerware 9395 upss by offering increased c...

  • Page 116

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−22 the upss continually monitor themselves and the incoming utility power and automatically switch between these modes as required, without operator interventi...

  • Page 117

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−23 if the utility ac power is interrupted or is out of specification, the upss automatically switch to battery mode to support the critical load without interr...

  • Page 118

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−24 in a distributed bypass system, each ups operates similar to a single ups, but in parallel with each other. The bypass source for the load is derived from t...

  • Page 119

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−25 main power flow ups 1 ups 2 ups 3 ups 4 output to critical load battery ups input tie cabinet ups 1 output bypass input ups 2 output ups 3 output ups 4 outp...

  • Page 120

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−26 6.5 multiple ups distributed bypass system oneline configurations the distributed bypass system oneline drawings in this section show the simplified interna...

  • Page 121

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−27 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b tie c...

  • Page 122

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−28 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b tie c...

  • Page 123

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−29 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b tie c...

  • Page 124

    Understanding ups operation eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 6−30 this page intentionally left blank..

  • Page 125

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−1 chapter 7 ups operating instructions this section describes how to operate the ups. Note before starting the ups, ensure all installation tasks are complete and a preliminary startup ha...

  • Page 126

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−2 7.1.1 control panel the control panel is used to set up and control the ups, and to monitor ups operation. For a description of the ups control panel function...

  • Page 127

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−3 7.2.1 status indicators the four symbols on the right side of the control panel are status indicators. These colored light emitting diode (led) lamps work wit...

  • Page 128

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−4 7.2.3 using the lcd and pushbuttons the lcd on the control panel provides an operator interface with the ups system. Figure 7-3 identifies the display areas d...

  • Page 129

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−5 7.2.4 using the menu the ups menu bar allows you to display data in the information area to help you monitor and control ups operation. Table 7-2 shows the ba...

  • Page 130

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−6 7.2.6 display menu operation table 7-3 describes the menu functions and and how to use them. Table 7-3. Display menu operation function subfunction operation ...

  • Page 131

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−7 table 7-3. Display menu operation (continued) operation subfunction function contrast adjust select contrast from the system setup level 0 menu to display the...

  • Page 132

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−8 table 7-3. Display menu operation (continued) operation subfunction function com port selection the com port setup screen allows selection of the serial com p...

  • Page 133

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−9 table 7-4. Typical system status messages function message ups shutdown; bypass; online; energy saver; high alert bypass off; on; available maintenance bypass...

  • Page 134

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−10 7.2.8 load off screen the load off screen (figure 7-6) is displayed when the load off pushbutton is selected from the main menu bar, the ups control command ...

  • Page 135

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−11 10. Close the battery breaker. 11. Verify no alarms are active. 12. On the system status screen, select the ups command. 13. Press the controls pushbutton on...

  • Page 136

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−12 8. Press the controls pushbutton on the main menu bar. The system status screen is displayed. 9. On the system status screen, verify the ups status is shutdo...

  • Page 137

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−13 16. Verify the following messages display sequentially on the upm status line: dc starting, charger off inverter starting inverter syncing ready the upm 1 re...

  • Page 138

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−14 9. On the system status screen, the ups status should indicate shutdown and the upm status should indicate offline. 10. Verify no alarms are active. 11. On t...

  • Page 139

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−15 5. Press the select pushbutton on the bypass command menu bar. The ups transfers to bypass mode and the critical load is immediately supplied by the bypass s...

  • Page 140

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−16 5. Press the select pushbutton on the ups command menu bar. The ups transfers to energy saver mode and the critical load is immediately supplied by the bypas...

  • Page 141

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−17 5. Press the select pushbutton on the ups command menu bar. The ups transfers to high alert mode, but remains online. After one hour the ups transfers to ene...

  • Page 142

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−18 7.3.12 transfer from energy saver to bypass mode to transfer the critical load to bypass mode: note the energy saver mode commands are displayed only if enab...

  • Page 143

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−19 7.3.14 transfer from high alert to bypass mode to transfer the critical load to bypass mode: note the high alert mode commands are displayed only if enabled ...

  • Page 144

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−20 7.3.16 transfer from high alert to energy saver mode to transfer the critical load to energy saver mode: note the high alert and energy saver mode commands a...

  • Page 145

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−21 10. Press the select pushbutton on the upm 1 command menu bar. The upm status indicates shutdown . The power module is turned off. Logic power remains on. 11...

  • Page 146

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−22 4. Press the controls pushbutton on the ups control command menu bar. The upm control command screen is displayed. 5. On the upm control command screen, sele...

  • Page 147

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−23 to turn the battery charger off: 1. Press the controls pushbutton on the main menu bar. The system status screen is displayed. 2. On the system status screen...

  • Page 148

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−24 3. Press the controls pushbutton on the system status menu bar. The ups or bypass control command screen is displayed. 4. On the control command screen, sele...

  • Page 149

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−25 7.3.23 using the remote emergency power−off switch a ups emergency power−off is initiated by the repo pushbutton switch. In an emergency, you can use this sw...

  • Page 150

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−26 7.4 multiple ups distributed bypass operation 7.4.1 starting the distributed bypass system in normal mode to start the distributed bypass system: 1. Unfasten...

  • Page 151

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−27 17. Verify the following messages display sequentially on the ups status line: dc starting, charger off inverter starting inverter syncing online, charger on...

  • Page 152

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−28 13. On the bypass control command screen, select go to bypass . 14. Press the select pushbutton on the bypass command menu bar. The critical load is immediat...

  • Page 153

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−29 17. Repeat steps 12 through 15 selecting upm 2 to start upm 2. 18. Verify the following messages display sequentially on the upm status line: dc starting, ch...

  • Page 154

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−30 13. Press the controls pushbutton on the ups control command menu bar. The upm control command screen is displayed. 14. On the upm control command screen, se...

  • Page 155

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−31 7.4.6 transfer from bypass to normal mode to transfer the critical load to normal mode: 1. If not already closed, close the battery breaker. 2. On any ups, p...

  • Page 156

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−32 7.4.8 transfer from energy saver to normal mode to transfer the critical load to normal mode: note the energy saver mode commands are displayed only if enabl...

  • Page 157

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−33 7.4.10 transfer from high alert to normal mode to transfer the critical load to normal mode: note the high alert mode commands are displayed only if enabled ...

  • Page 158

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−34 7.4.12 transfer from energy saver to bypass mode to transfer the critical load to bypass mode: note the energy saver mode commands are displayed only if enab...

  • Page 159

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−35 7.4.14 transfer from high alert to bypass mode to transfer the critical load to bypass mode: note the high alert mode commands are displayed only if enabled ...

  • Page 160

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−36 7.4.16 transfer from high alert to energy saver mode to transfer the critical load to energy saver mode: note the high alert and energy saver mode commands a...

  • Page 161

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−37 10. Press the select pushbutton on the upm 1 command menu bar. The upm status indicates shutdown . The power module is turned off. Logic power remains on. 11...

  • Page 162

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−38 3. On the ups control command screen, select the upm to restart. 4. Press the controls pushbutton on the ups control command menu bar. The upm control comman...

  • Page 163

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−39 7. Perform the load off procedure in paragraph 7.4.25 on the ups being shut down. The input, output, battery, and bypass backfeed contactors open, and the po...

  • Page 164

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−40 11. Press the select pushbutton on the upm 1 command menu bar. The upm status indicates shutdown . The input, output, and battery contactors open, and the po...

  • Page 165

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−41 11. Verify external communications failure alarm has cleared and no other alarms are active on the online upss. 12. On the system status screen, select the u...

  • Page 166

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−42 7.4.24 charger control to turn the battery charger on: 1. Press the controls pushbutton on the main menu bar. The system status screen is displayed. 2. On th...

  • Page 167

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−43 3. If another ups is to be shut down, proceed to that ups and repeat steps 1 and 2. C a u t i o n do not attempt to restart the system after load off until t...

  • Page 168

    Ups operating instructions eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 7−44 7.4.26 using the remote emergency power−off switch a ups emergency power−off is initiated by the repo pushbutton switch. In an emergency, you can use this sw...

  • Page 169

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−1 chapter 8 communication this chapter describes the communication features of the powerware 9395 ups and provides information about connecting hardware and using terminal mode. For termi...

  • Page 170

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−2 lan and telephone drops for use with x−slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an x−slot card, contact...

  • Page 171

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−3 the enotify service relies on a connectups−x web/snmp card (or power xpert card) installed with the ups sending one−way status and event e−mails to powerware remote monito...

  • Page 172

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−4 remote notification differs from the basic terminal mode with the addition of the following functions: s call answer the call answer function allows the user to call into ...

  • Page 173

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−5 8.5.2 event history log this key sequence prints the entire event history log of the ups at the time the data is requested. The printout begins with the oldest alarm entry...

  • Page 174

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−6 model: powerware 9395 cto: tf12710000000 serial: mcu dsp: 70.81.14 mcu bootloader: 80.40 mcu pld: 1.00 pmf 1 dsp: 80.81.14 pmf 1 bootloader: 80.40 pmf 1 pld: 1.00 xslot ca...

  • Page 175

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−7 8.6 building alarm monitoring this standard feature lets you connect the ups to your building alarms, such as smoke detectors or overtemperature alarms. The customer inter...

  • Page 176

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−8 the rmp ii contains a local horn and the backlit status indicators listed in table 8-1. Table 8-1. Rmp ii status indicators system normal the ups is energized (either with...

  • Page 177

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−9 8.9 relay interface module ii an optional rim ii uses relay contact closures to indicate the operating status and alarm condition of the ups system. The module uses a seri...

  • Page 178

    Communication eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 8−10 8.10 supervisory contact module ii an optional scm ii establishes an interface between the ups system and the customer’s monitor. This interface allows the customer to mo...

  • Page 179

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−1 chapter 9 ups maintenance the components inside the ups cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little d...

  • Page 180

    Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−2 s proper disposal of batteries is required. Refer to your local codes for disposal requirements. S do not dispose of batteries in a fire. Batteries may explode when expo...

  • Page 181

    Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−3 isbm air filter locations upm air filter locations ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄ ÄÄÄÄÄÄ...

  • Page 182

    Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−4 c a u t i o n verify washed filter is thoroughly dry before reinstalling. C. Push the washed or new foam filter over the screw heads on the cabinet mounted studs until s...

  • Page 183

    Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−5 9.2.5 battery maintenance contact an eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorized ser...

  • Page 184

    Ups maintenance eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 9−6 this page intentionally left blank..

  • Page 185

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 10−1 chapter 10 product specifications 10.1 model numbers the ups is housed in a free-standing cabinet with safety shields behind the door and front panels. The ups is available in 50 or 60...

  • Page 186

    Product specifications eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com 10−2 10.2.2 ups output ups output capacity 100% rated current output voltage regulation "1% (10% to 100% load) output voltage adjustment (nominal +/–3%) 480 vac nomin...

  • Page 187

    Eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com w−1 warranty limited factory warranty for three-phase powerware ® ups products warrantor: the warrantor for the limited warranties set forth herein is eaton corporation, a delaware corporat...

  • Page 188

    Warranty eaton powerware ® 9395 ups (450–550 kva) installation and operation manual s 164201701 rev 2 www.Powerware.Com w−2 this page intentionally left blank..

  • Page 190

    *1642017012* 164201701 2.