Fadini COMBI 740 Instruction Manual - page 9
9
PIC. 19
PIC. 18
1643
Drwg. No.
13
exp
GB
®
ELECTRICAL WIRING DIAGRAM OF THE ELECTRONIC
PROGRAMMER
Once the connections have been made, do the first switching
test through the control panel. Set the motor run timer so that
the motor is allowed to run 4 - 5 seconds more than the gates.
Set the other timers to meet the site requirements. Set DIP
switch B No. 3 to automatic (ON): on pulsing to 4 - 8 the gates
must be operated as pre-set, ie. opening and only after the
dwell time, closing. Adjust the times through the respective
timers. (See No. 07, 08 and 09 drwg. No. 1643).
With DIP switch "B" No. 3 to semiautomatic (OFF) one pulse
opens the gates, a second pulse to 5 - 9 is needed to close
the gates. Any one pulse to 7 - 8 will open, close or reverse
the gates independently from the operation being performed.
It is recommended to carefully read the instructions in the
control box to have all the functions performed correctly.
The 6 LEDs on the P.C. board indicate the following:
Led No. 1 It switches on when voltage is supplied
Led No. 2 Photocells - Normally on. It switches off when the
photocells are obstructed
Led No. 3 Open - It switches on when the respective switch
is activated
Led No. 4 Close - It switches on when the respective switch
it activated
Led No. 5 Stop - Normally on. It switches off when the
respective switch is activated
Led No. 6 Radio - It switches on whenever a pulse is given,
either from remote control, keyswitch or push
buttons.
P.C. BOARD
CONNECTION DIAGRAM FOR SWING GATES
1 2 3 4 5
6 7 8 9 10 11 12 13 14 15
16 17 18
7 8
M1
M2
19 20 21 22 23 24 25
12,5
+F
12,5
+F
1
2
3
4
5
6
7
8
9
–
ON
OFF
1 2 3 4 5 6 7 8
ON
RADIO CONTROL
PLUG-IN CARD SUPPORT
ON TO “0” THE DELAY
IS OUT OF SERVICE
DWELL TIME
MOTOR RUN
OPEN & CLOSE TIME
CAPACITORS
MICROPROCESSOR
DIP-SWITCH
TERMINAL FOR
CONNECTIONS TO
PUSH BUTTONS PULIN 3
1 AMP. FUSE
24 V OUTPUT
TERMINALS 12-13
TIMER SWITCHES
FUSE
630 mA
FUSE 5 AMPS
1 st
CHANNEL
24 V OUTPUT
Should more pairs of photocells be required
than the recommended quantity
, fit an auxiliary
transformer outside the control box.
= PHOTOCELLS 2
nd
P
AIR =
Inside photocells N.C. cont
act
If obstructed they prevent the ga
tes from opening
reverse ga
te direction during close cycle
N.C. CONT
ACT
PHOTOCELLS
COMMON
OPEN SWITCH N.O. CONT
ACT
CLOSE SWITCH N.O. CONT
ACT
STOP SWITCH N.C. CONT
ACT
RADIO CONT
ACT N.O.
COMMON
VOL
TAGE OUTPUT
ELECTRIC LOCK SUPPL
Y
24 V INDICA
TOR - 3 W max.
24 V
OUTPUT A.C.
Max permitted load:
2 pairs photocells
1 radio receiver
COMMON
COMMON
230 V FLASHING LAMP
25 W max.
230 V SINGLE-PHASE
SUPPL
Y VOL
TAGE
ELECTRIC MOTORS
SINGLE-PHASE
NOTE WELL: For special applications, ie. to switch on lights -
CCTV etc., SOLID STATE RELAYS are recommended to be used
only. Standard relays would affect the micro-processor.
ALL OPERATIONS
OPEN, CLOSE AND
REVERSE
RADIO CONTACT
LEAF DELAY
TIMER CLOSE
LED No. 1 - It switches on when voltage is supplied
OPEN
STOP
CLOSE
N.O.
N.C.
N.O.
3
4
5
6
26 27 28 3
CONNECTION TO THE “PULIN 3” PUSH
BUTTONS WITH STATUS INDICATION LEDS.
0
FLASHING LAMP
630 mA FUSE
SAFETY CONT
ACT N.C.
3 4
NOTE WELL: THIS PANEL IS TESTED TO OPERATE GATES ONLY
THROUGH FADINI ACCESSORIES. NO WARRANTY IS
ACKNOWLEDGED BY THE MANUFACTURER IN CASE THAT
OTHER ACCESSORIES ARE USED OR NON CONFORMING
APPLICATIONS ARE MADE WITHOUT THE MANUFACTURER’S
APPROVAL.
+
+
+
26
27
28
PEDESTRIAN MODE
ONE PULSE OPENS
ONE GATE LEAF ONLY
PULSE TWICE CONSECUTIVELY
TO OPEN BOTH GATE LEAFS
II
12
3
4
ELECTRICAL CONNECTIONS
KEYSWITCH PRIT 19
STOP
OPEN
CLOSE
COMMON
TERMINAL BOARD
PRIT 19
1 2 3 4 5 6 7 8 9 10 11 12 13
TERMINAL BOARD
R
ADIO
CON
TA
C
T
S
T
OP N.C
.C
ON
TA
C
T
C
LOSE N.
O
.CON
TA
C
T
OPEN N.O
.CON
TA
C
T
COMMO
N