10. Preparation before Starting the Controller
10.1 Make sure the controller is correctly installed to meet the ambient requirements.
10.2 Confirm all wiring connections of the controller meet the correct electric specification and
corresponding to “2.3 typical wiring diagram”. Ensure the correct polarity of the DC supply source
and that it has been protected by an external fuse. Otherwise damage to the controller may occur.
10.3 We recommend mounting an “Emergency Stop” button externally. The emergency stop input could
be connected to N.O. contact of emergency stop push button, and the other contactor point be
connected to the battery negative.
10.4 Switch on DC working power, make sure the preset parameters meet practical operating conditions,
such as P-sensor mode, T-sensor mode, etc.