Galletti AREO 12 Technical Manual - Areo
17
AP66000265 - 03
All copying, even partial, of this manual is strictly forbidden
AREO
13
ELECTRICAL DATA
Features of the standard motor:
- tropicalised
- equipped internally with a thermal cutout
- IP 55 protection degree
- class F winding
- closed type: asynchronous three-phase 2-speed motors (400/400 V star-
delta connection) or single-phase 3-speed motors.
400/400 V - Y motors are equipped internally with a thermal cutout and
speeds are selected by means of a normal star-delta switch (accessory
CST).
The terminals of the cutouts are connected to the terminal block so that they
can be used as protection in series with the coil of a contactor.
If the internal cutout is not used to protect the motor, it will be necessary to
provide a motor overload cutout set at a current that is 10-15% higher than
the current indicated on the unit rating plate.
Special 4/8 pole motors are available on request (single-voltage, dual
polarity).
Model
Number of poles
Fan revolution
Voltage
Power input
Current absorbed
r.p.min
V
W
A
4 6
1400 / 900
400
67 / 46
0,209 / 0,118
6 8
900 / 700
400
55 / 27
0,140 / 0,056
4 6 8
1400 / 900 / 700
230
105 / 62 / 48
0,48 / 0,38 / 0,31
4 6
1400 / 900
400
277 / 172
0,61 / 0,32
6 8
900 / 700
400
178 / 90
0,40 / 0,16
4 6 8
1400 / 900 / 700
230
311 / 217 / 170
1,52 / 1,32 / 1,00
4 6
1400 / 900
400
394 / 294
0,85 / 0,58
6 8
900 / 700
400
176 / 118
0,48 / 0,23
4 6 8
1400 / 900 / 700
230
439 / 370 / 300
1,93 / 2,02 / 1,53
4 6
1400 / 900
400
703 / 471
1,49 / 0,85
6 8
900 / 700
400
304 / 191
0,88 / 0,39
4 6 8
1400 / 900 / 700
230
750 / 450 / 360
3,50 / 2,50 / 1,90
4 6
1400 / 900
400
1300 / 860
2,49 / 1,37
6 8
900 / 700
400
488 / 340
0,90 / 0,58
6 8 10
900 / 700 / 550
230
540 / 440 / 370
2,60 / 2,30 / 2,00
6 8
900 / 700
400
540 / 417
1,18 / 0,69
6 8 10
900 / 700 / 550
230
620 / 470 / 380
2,80 / 2,30 / 2,00
AREO 52-53-54
AREO 62-63-64
AREO 12-13-14
AREO 22-23-24
AREO 32-33-34
AREO 42-43-44
The single-phase motor has an internal thermal cutout that acts directly on
the windings: therefore, NO EXTERNAL THERMAL OVERLOAD PROTECTION
IS NECESSARY.
Make the electrical connections with the power supply disconnected, in
accordance with current safety regulations. All the wiring must be done by
qualified personnel.
Check that the mains electricity supply is compatible with the voltage shown
on the unit rating plate.
Scrupulously follow the wiring diagram provided, according to the type of
installation.
Each unit requires a switch (IL) on the feeder line with a distance of at least
3 mm between the opening contacts, and a suitable safety fuse (F).
If, in case of single-phase motors with microprocessor control, power
input is higher than the values specified in the following figures (for
controls), use the IPM power interface.
14
WIRING DIAGRAMS
Delta connection to terminal block of 400/400 V - Y
motors, high speed
W2
U2
V2
U1
V1
W1
R
S
T
11
12
KLIXON
W2
U2
V2
U1
V1
W1
R
S
T
11
12
KLIXON
Star connection to terminal block of 400/400 V - Y
motors, low speed