NAPCO Gemini GEM-P3200 Installation Instructions Manual

Manual is about: CONTROL PANEL/COMMUNICATOR

Summary of Gemini GEM-P3200

  • Page 1

    Installation instructions hardwire wireless g e m - p 3 2 0 0 control panel/communicator wi817f 10/05 © napco 2005 r for use with "classic" keypads (gem-rp1cae2, gem-rp2ase2, gem-rp3dgtl and gem-rp4rfc/gem-rp4c) and with "k series" keypads (gem-k1ca, gem-k2as, gem-k3dgtl, and gem-k4rf/gem-k4) public...

  • Page 2

    Changes from previous edition the following changes have been made to this manual (wi817f) since the last edition (wi817e). This version of the manual reflects the addition of two new napco products: • the access control system (acm), which provides integrated access control to the burglary alarm fu...

  • Page 3: Important Note

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 3 important note this manual supports the keypad programming of the gem-p3200 control panel with the napco "classic" gem- rp1cae2, gem-rp2ase2, gem-rp3dgtl and gem-rp4rfc/gem-rp4c keypads as well as the gem-k1ca, gem- k...

  • Page 4

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 4 table of contents refer to accompanying gem-p3200 programming instructions (wi818 and wi1184) for programming information. Changes from previous edition ........................ 2 important note .........................

  • Page 5

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 5 introduction general description napco's gemini gem-p3200 is a state-of-the-art microcomputer-based burglary and residential fire alarm control panel of modular design. Integrally an 8-zone panel, it will support up t...

  • Page 6

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 6 800 event log. Overview mode permits monitoring and control of total system from one keypad. Two programmable entry delay times. Two interior-zone groups (when used with gem-rp1cae2 / gem-k1ca keypads). Dynamic batter...

  • Page 7

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 7 specifications gem-p3200 panel dimensions: 12 3/8" x 13 7/8" x 3 ½" (h x w x d) without cover operating temperature: 0-49°c (32-120°f) input power: 16.5vac via class 2 plug-in 40va or 50va transformer loop voltage: 10...

  • Page 8

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 8 optional accessories and peripherals eol130: 2-wire fire zone resistor, 130w, 3w eol2.2k: end-of-line resistor assy., 2.2k ft2200: end-of-line relay/resistor supervisory module gem-acm1d: access control module for doo...

  • Page 9

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 9 summary of ul requirements residential recognized limited-energy cable for initiating, indicating and supplementary circuits. Initiating loops supervised if longer than 3 feet ft2200 end-of-line relay for fire (if usi...

  • Page 10

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 10 installation mounting control panel choose a mounting location accessible to (a) a continuously-powered ac source, (b) system ground, a steel or copper ground rod, ideally no further away than 10 feet, and (c) teleph...

  • Page 11

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 11 wiring wire keypad(s), zones, expansion zone modules and output devices as shown on the wiring diagram. Note that the wiring diagram contains important information not available elsewhere in this manual. Adding expan...

  • Page 12

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 12 ul commercial-burglary installations the gem-p3200m can be used as part of a ul central station grade c, b, or a installation. Normally, a digital communicator is classified as grade c and may be classi- fied grade b...

  • Page 13

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 13 testing the system after installation is completed, test the system as follows. 1. Call the central station to inform them of the test. 2. Initiate an alarm, preferably on a zone that activates a steady siren, and ve...

  • Page 14

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 14 wiring connections auxiliary alarm output auxiliary output can be activated depending on the programming options selected (see gem- p3200 programming instructions). Connect the device controlled by the programmable o...

  • Page 15

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 15 earth ground note: do not use a gas pipe, plastic pipe or ac ground connections. Connect the control panel earth ground screw through a no. 16 awg. Or larger wire to a metal cold-water pipe. Do not use a gas pipe, pl...

  • Page 16

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 16 basic zone configuration the basic zone configuration for the gem-p3200 is 8 zones. Connect as shown above to terminals 16-27. Normally closed (n.C.) devices may be wired in series or normally open (n.O.) devices may...

  • Page 17

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 17 4-wire smoke detectors 4-wire smoke detector wiring the gem-p3200 can use conventional 12 vdc 4-wire smoke detectors. To use them, select fire zone programming option and do not select 2-wire smoke detector program- ...

  • Page 18

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 18 connect the model 368 cord as follows: 30 (red = telco tip), 31 (green = telco ring), 32 (gray = home tip) and 33 (brown = home ring). Insert the modular plug into an approved usocrj31x jack (or a ca31a jack for cana...

  • Page 19

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 19 keypad configuration mode this section will focus on configuring the gem-rp1cae2/gem-k1ca and gem-rp2ase2/gem-k2as keypads. If there is more than one keypad in the system, only keypad no. 1 may be used for programmin...

  • Page 20

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 20 compatibility number the compatibility number is a 4-digit security code that, if programmed into both the control panel and each gem-rp1cae2 keypad, dedicates the keypad to only that panel. That is, (a) similar keyp...

  • Page 21

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 21 configuring the gem-rp2ase2/gem-k2as and gem-rp3dgtl/gem-k3dgtl keypads up to 7 gem-rp2ase2/gem-k2as and/or gem-rp3dgtl/gem-k3dgtl keypads may be connected to the panel (keypads 1–7). Each must be configured for a ke...

  • Page 22

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 22 basic operation b a sic oper a t io n this section provides a brief overview of system operation. For detailed operation, refer to the user's guide furnished with the keypad (see page 8 for a complete listing) and to...

  • Page 23

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 23 to move cursor right. Press b to move cursor left. Press 0 through 9 and g to select letters. The first press will display the first character, the next press will display the next character. (roughly note the order ...

  • Page 24

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 24 arming in stay mode stay mode provides partial protection by allowing free movement within the premises, while still protecting the perimeter zones. Exit/entry doors are provided with exit/entry delays. A "classic" s...

  • Page 25

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 25 3. Arm or disarm the selected area using your user code (the user code must be valid for that area). 4. To return the keypad to its "home" area, press the g button, then the u or d button. Note: if the "home" keypad ...

  • Page 26

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 26 alarm indication if programmed to silence an alarm, enter a valid user code and press the u button. The keypad must have permission to disarm the alarm (alarm, pulse alarm, fire output, reset output or auxiliary out-...

  • Page 27

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 27 display op/cl napco's pcd-windows quickloader software offers a comprehensive array of programmable opening and clos- ing suppression windows, by area, for all days of the week, for both normal and holiday schedules....

  • Page 28

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 28 activate locate this feature will help the user find zone troubles and indicate when they are repaired. When accessed, the sounder will come on and the display will read "locate", then scroll through the zones in tro...

  • Page 29

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 29 function), or autoarming may be canceled by arming and disarming the panel. Activate program at keypad no. 1, press the yes button to activate the user program (program-1) mode or dealer program (program-2) mode, dep...

  • Page 30

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 30 keypad messages the gem-rp1cae2/gem-k1ca keypad can display the following messages. The gem-rp2ase2 and gem-k2as keypads will dis- play similar abbreviated messages that may scroll through two screens. System ready c...

  • Page 31

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 31 glossary note: displayed messages shown are for the gem-rp1cae2 and gem-k1ca keypads. Gem-rp2ase2/gem-k2as and gem-rp3dgtl/gem-k3dgtl messages are similar but abbreviated. Refer to the appropriate gem-p3200 programmi...

  • Page 32

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 32 alarm outputs (see wiring diagram for ul requirements.) the gem-p3200 has three form-c relay outputs: burglary, auxiliary and reset. Each has a related jumper (b, a, and c, respectively) that may be cut for dry conta...

  • Page 33

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 33 answer on ring number see callback-method download answering machine pickup without line seizure see callback-method download anti-jam time if the communicator does not detect a dial tone within 12 seconds, the anti-...

  • Page 34

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 34 backup reporting telco # 1 / telco #2 if backup reporting is selected and the communicator does not reach the first telephone number after two attempts, seven at- tempts will be made to reach the second telephone num...

  • Page 35

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 35 chime on lug e4 the e4 lug can now serve as an output that follows the chime sounder. This can be used where a remote sounder is needed to follow the keypad sounder. This feature can be found on the options page of t...

  • Page 36

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 36 zone 1 is “e,1”. The communicator will send “123 e” (account no. 123 restored); followed by “eee 1” (restored, zone 1). Modem formats. Modem formats (sia, point id, express, 4/3/1, modem 2) are preset and automatic b...

  • Page 37

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 37 cessed. Arming and disarming will turn off the watch mode. If report trouble is selected, a trouble on a day zone will be reported only when the watch mode is on. Dealer security code see master security code dial-to...

  • Page 38

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 38 disable callback download see callback-method download disable code required for ez bypass see selective bypass (do not program in ul installations) disable code required for function mode level 1 intended primarily ...

  • Page 39

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 39 enable burg output warning on entry causes the burglary output to “chirp” if the entry door is opened within 60 seconds after exit time has elapsed. This feature may be useful in cases where a keypad is not within au...

  • Page 40

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 40 entry delay may be canceled by pressing and holding the p button prior to arming, however it will be restored automatically upon disarming. (when armed with instant protection, an “i” will appear at the right side of...

  • Page 41

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 41 indicating that only partial protection will be provided upon arming. To temporarily restore interior protection, press e ; the “ bypass ” reminder will go out upon arming, denoting full protection, however interior ...

  • Page 42

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 42 ( access on aux. Output ) into the aux. 1 or aux. 2 option locations. Also program the option access control on auxiliary output , and a time into the auxiliary output access control duration. If an access control fr...

  • Page 43

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 43 when a fire zone is bypassed the panel will go into a fire trouble condition. It will also transmit the fire trouble to the cs, if programmed to do so. Zones 1-9 are entered as 01 - 09. Loop response (750ms required ...

  • Page 44

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 44 and opening codes must be entered for either opening report. Program opening report only after alarm report to report only when disarming after an alarm report. This feature may be used by the central station to veri...

  • Page 45

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 45 receiver format the communicator can be programmed to transmit to any standard central-station receiver. A receiver format must be entered for each telephone number used, but a different format may be assigned to eac...

  • Page 46

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 46 reset relay see alarm outputs resound on wireless smoke low battery if a wireless smoke detector low battery is detected, it will re-sound the trouble at the keypad every 4 hours when disarmed and every 12 hours when...

  • Page 47

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 47 1. Program the selected zone(s) (1–6) for 2-wire smoke detec- tors and fire. 2. Cut out the 2700Ω resistor (color code: red/violet/red) associ- ated with the selected zone(s). See table below. 3. Install a 130Ω resis...

  • Page 48

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 48 subscriber identification numbers if reporting openings and/or closings, program subscriber opening/closing identification numbers for each area for each tele- phone number used. If reporting events, program subscrib...

  • Page 49

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 49 telemetry trouble if any device connected to the on-board serial port (such as a home automation system or aes radio) fails to respond to a poll by the control panel, a telemetry trouble system trouble will result. O...

  • Page 50

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 50 time selection the following times are programmable: any timeout up to those shown in the foregoing table may be programmed. Note that each of the above times is pro- grammed in two locations. The first location has ...

  • Page 51

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 51 lcd. Keypad indications are reset by the c button unless reset day zone with arm/disarm is selected. Trouble on a fire zone will be indicated by the “fire/trbl” reminder and the sounder. An open circuit (trouble) wil...

  • Page 52

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 52 zone anding, groups 1–2 (not for ul installations); enable local alarm on first zone “and” trip (not for ul installations) up to 2 groups of at least two zones each can be “and”ed, wherein the system will go into ala...

  • Page 53

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 53 standby-battery calculation worksheet use the procedure given below to determine the required standby battery capacity in ampere-hours (ah). Note: it is not totally ac- curate to merely multiply the combined standby ...

  • Page 54

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 54 wiring legend should removal of the circuit board be necessary, use this wiring legend to relocate wire leads to their proper terminals. Enter wire identification number or color code in wire number column and enter ...

  • Page 55

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 55 keypad programming modes note: 1. Functions that are not active, not programmed and/or not applicable to user’s authority level will be suppresses and will not display. 2. Due to space constraints, gem-rp2ase2/gem-k2...

  • Page 56

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 56 keyp a d progr a m m ing m o des note: 1. Functions that are not active, not programmed and/or not applicable to user’s authority level will be suppresses and will not display. 2. Due to space constraints, gem-rp2ase...

  • Page 57

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 57 easy menu program mode (a) minimum level required to access function (b) level 3 code with appropriate option (c) requires dealer code (d) not available in gem-rp2ase2/gem-k2as keypads (e) initial configuration only;...

  • Page 58: Notes

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 58 notes.

  • Page 59

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 59 keypad configuration mode press a button enter factory code: 11123 configure: • keypad beep on/off • entry sounder • keypad address 01 • new compat# 0000 ** • ezm address 00 • zone response 00 • program control messa...

  • Page 60

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 60 gem-p3200 wiring diagram.

  • Page 61

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 61 cp-01 quick reference chart--sia false alarm reduction feature description programming address location cp-01 features are enabled with one global selection in the panel. Enabled in ez programming exit delay. Minimum...

  • Page 62

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 62 duress code. The panel will not allow duplicate user codes to be programmed. Every user program code may now be selected as an ambush code for area 1 or area 2 by entering a _5 in the area 1 options or area 2 options...

  • Page 63

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 63 gem-p3200 factory default description the factory program of the gem-p3200 will change with the release of the new version that complies with security industry as- sociation false alarm reduction control panel-01 sta...

  • Page 64

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 64 statement for canadian models notice: the canadian department of communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, o...

  • Page 65

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 65 fcc statement this equipment generates and uses radio-frequency energy and, if not installed and used properly, that is, in strict ac- cordance with the manufacturer's instructions, may cause interference to radio an...

  • Page 66: Notes:

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 66 notes:.

  • Page 67: Notes:

    L napco security systems x gem-p3200 installation instructions wi817f 10/05 page 67 notes:.

  • Page 68

    X gem-p3200 installation instructions l napco security systems wi817f 10/05 page 68 napco security systems, inc. (napco) warrants its products to be free from manufacturing defects in ma- terials and workmanship for thirty-six months following the date of manufacture. Napco will, within said period,...