Pacific Energy BROADWAY Installation And Operating Instructions Manual - Gas Supply
7
161204-24
# 5055.6591
The vent terminal must be sealed in place to prevent
water from entering the existing chimney.
6) Remove the two screws located on top of the
unit that retains the vent connector plate on the
appliance. Attach ends of the fl ex liners to the
collars on top of the connector plate. Make sure
the marked inlet pipe is attached to the inlet side
(marked "I"), and the unmarked pipe is attached
to the outlet side (marked "E") of the connector
plate.
7) Seal and secure inlet pipe with sealant and screws
provided.
8) Slip the 3 1/2" pipe clamp loosely over the end of the
fl ex fl ue pipe. Slide the pipe over the collar (marked
"E") of the vent connector plate and clamp tightly
in place. Secure in place with screws provided.
No additional seal is required.
9) Position vent connector plate over top of unit as the
Insert is pushed into the fi replace. Clip connector
plate at the back of the unit, tip down into position
and attach in place with screws previously removed.
Leave the Insert extending a couple of inches out
of the fi replace temporarily to allow for proper
surround placement.
Fig # 9
Gas Supply
Caution: The gas line should be installed by a
qualifi ed service person in accordance with all
building codes. Consult local and/or national
building codes before proceeding.
The gas valve is fi tted with a 90° street elbow for
easy gas connectio. The fi tting may be removed
or replaced with other fi ttings if required. Correct
gas line diameter must be used to assure proper
operation.
The gas control is equipped with a capture screw type
pressure test port, therefore it is not necessary to
provide an 1/8 inch N.P.T. plugged tapping pressure
port for checking gas pressure immediately upstream
of the gas supply connection to the appliance.
A knockout is provided at the bottom right rear of the
appliance for a gas supply line. To use this entrance,
remove the knockout and install the plastic bushing
supplied into the hole.
An optional 24" long fl exible connector (part # GASC.
GASCON) may be used for easy gas connection.
Correct Gas Pressure Requirement:
Natural
Gas Propane
Min. Pressure
5.0" wc
12.5" wc
(For purpose of input adjustment)
Max. Pressure
10.5" wc
13.0" wc
Manifold Pressure
3.8" wc
11.0" wc