Pneumercator ETD1000 Instruction Manual - page 17
ETD1000 Inst
ruction Manual - 20
17-07-
01.docx
Page 17 of 28
July
1,
2017
2.2.2.6 TX1064-1 Wiring Detail
See Figure 2.2.
2.6-1 below.
Figure 2.2.2.6-1 TX
1064-1 Wiring Detail
NOTES:
1. THE 115/230 VAC SWITCH MUST BE SET TO 115V FOR 115 VAC OPERATION OR 230V FOR 230 VAC OPERATION.
2. THIS NOTE APPLIES TO ETD1000 INTERFACE WITH TX1064-1 ONLY: FOR PROPER OPERATION, THE TX1064-1 UNIT
MUST BE POWERED UP EITHER PRIOR TO OR SIMULTANEOUSLY WITH THE ETD. THIS CAN BE ACHIEVED
AUTOMATICALLY BY POWERING THE TX1064-1 UNIT FROM THE SAME CIRCUIT BREAKER AS THE ETD.
3. THE TX1064-1 IS TYPICALLY INSTALLED BESIDE THE ETD (WITHIN 50 FEET). CONSULT FACTORY FOR
INSTALLATION ABOVE 50 FEET.
SHIELD
CH. B (-)
CH. A (+)
RS-485 COMMS.
I
N
O
U
T
OFF
ON
CLK
DATA
GND
SHD
T
X
1
0
6
4
Ø1.375/Ø35 MM
HOLE FOR 1" NPT
OR EQUIVALENT
CONDUIT FITTING
GRN
RED
BLK & WHT
SHIELD
SH
D
GN
D
DA
T
A
CL
K
TX1064-1
- EXPANSION MODULE (SEE NOTE 3)
115V
HOT
GND
NEUTRAL
AC
IN
SEE NOTE 1
RELAY
CARD INSTALLED HERE
RELAY I/Os
O
PEN
2
3
4
1
SW1
IA0-3
IA1-3
IA2-3
SPARE
SPARE
IA2-3
IA1-3
IA0-3
SW1
14
3
2
OP
EN
DIP SWITCH
FACTORY
SETTINGS
CLOSED
CLOSED
CLOSED
OPENED
ETD1000
(PARTIALLY SHOWN)
22 AWG/.762 MM 4-CONDUCTOR
SHIELDED TWISTED PAIRS CABLE
BELDEN P/N 8723 (PVC JACKET) OR EQUIV.
PROVIDED BY CUSTOMER, SEE NOTE 3
115/230 VAC
50/60Hz
(SEE NOTE 2)
SH
D
GN
D
DA
T
A
CL
K
GRN
RED
BLK & WHT
SHIELD
Ø.875/Ø22 MM HOLE FOR
1/2" NPT OR EQUIVALENT
CONDUIT FITTING
TYP. 3 PLS.