Pneumercator ETD1000 Instruction Manual - page 20
ETD1000 Instruction Manual - 2017-07-01.docx
Page 20 of 28
July 1, 2017
3.1.2 Dipswitch Settings – S4
Audible Shutoff Delay: If set to NONE, audible alarm will continue until acknowledged on front panel
pushbuttons. If set to ONE MINUTE, audible alarm will continue until acknowledged on front panel
pushbuttons or one minute has elapsed, whichever comes first.
Front Panel (FP) Acknowledge Settings: If set to LOCAL, front panel acknowledgement will only
silence local ETD1000 audible alarm. If set to LOCAL and TMS, both ETD1000 and TMS audible
alarms will be silenced.
Audible Alarm Mode: If DISABLED, audible will not activate for any condition. If set to DISPLAYED
TANK ONLY, audible alarm will activate only if unacknowledged alarms apply to the currently
displayed tank. If set to ALL TANKS, audible alarm will activate for unacknowledged alarms from
any enabled tank.
Decimal Point Control: This setting controls placement of decimal points for U.S. and METRIC units
of measure. It does not perform conversions. This switch should be set to correspond to the TMS
units of measure and the overlay insert on the ETD1000 front panel.
Motion Symbol Display: The MOTION symbol “_” appears directly to the right of the tank ID to
indicate movement of product in the displayed tank. This status is detected by the TMS and sent to
the ETD1000 for display, if enabled. Refer to the TMS Operations Manual for more information.
Loss of Communications Alarm: When ENABLED, an audible alarm accompanies the “No data”
message if communications between the TMS and ETD1000 has failed for more than 10 seconds.
Front Panel Configuration Edit: This switch must be set to ENABLE if front panel programming is
required. Once programming is complete, the user can DISABLE editing and close the ETD1000,
thereby reducing the possibility of unauthorized changes.
DRAWING NO. 20036 REV. A
D. PT. CTL
MOTION DSP
COMMALARM
OPE
N
8
7
6
5
4
3
2
1
S4
EDIT ENABLE
CONTROL
AUDIBLE
TMS FP ACK
AUTO OFF
2
3
4
5
1
7
8
6