1.2 Display Data
The seven-segment LED display shows the selected Tank ID along with the selected tank data as
defined in the table below. User-selected tanks and display modes may be enabled or disabled. Refer
to Section 3.2 Front Panel Programming for details on this feature.
Display Mode
Data Format*
Display Units
Gallons
DDDDDDD
Gallons (Liters)
Net Gallons
DDDDDDD
Gallons (Liters)
Percent Gallons
DDD.d
% of Capacity
Ullage
DDDDDDD
Gallons (Liters)
Product Level
DDDD.d
Inches (mm)
Water Level
uDDDD.d
Inches (mm)
Product Temperature
sDDD.d
F (C)
*Where: d = Tenths, s = Signed Data, u = Water Symbol
1.3 Display Messages
The seven-segment display indicates a limited number of messages as follows;
Display Message
Description
-No data-
No communications with TMS
nn Lo Prod
Tank level below gaugeable limit
nn ------
Probe timeout or sync error
tank name
User-selected Tank Name
where nn = Tank ID
The “tank name” message is displayed when the MODE pushbutton is momentarily activated, as
described in Section 4.0 ETD1000 Front Panel Operation
1.4 Alarm LEDs
Alarm LEDs are provided to annunciate tank-related alarms as follows;
Alarm LED
Description
Leak
In-Tank Leak Test Failure
SP1
Product Setpoint #1 (HighHigh 95%)
SP2
Product Setpoint #2 (High 90%)
SP3
Product Setpoint #3 (Low 20%)
Water
Water Setpoint (Above 2”/51mm)
Factory default values in ( )