Radionics D8024 Operator's Manual - page 10
D8024 Operator’s Guide
35394B 11/98 Page 9 © 1998 Radionics, Inc. All rights reserved.
LEDs Test
•
Select the first option,1) LEDs, by pressing the1 Key. The panel will flash all LEDs on the LED Display and step
through all the Alarm and Trouble LEDs in the ZONE/AREA Display. On completion of the test, press No to return
the display to Main Menu.
LCD Test
•
Select the second option, 2) LCD, from the Test Menu by pressing the 2 Key. The Alphanumeric Display will flash all
characters in all spaces on the alphanumeric display and return to Main Menu.
Zones Test
•
Select the third option, 3) Zones, from the Test Menu by pressing the 3Key. The Zones Test allows the operator to
test devices on the polling circuit(s) and peripheral device circuit(s) without having to reset the panel after each
device is tested.
If no action is taken within one minute, the display reverts to the normal display. Press the > Key
to restore the test display.
•
The panel displays Zone Test Menu One.
Figure 11: Zone Test Menu One
•
Press the YesKey to activate notification appliances briefly as each device is tested, or press the No Key to bypass
the indicator test. The panel displays Zone Test Menu Two.
Figure 12: Zone Test Menu Two
•
Enter the number of the first zone to be tested. The panel displays Zone Test Menu Three. If, for example, “12”
were keyed in, the display would show:
Figure 13: Zone Test Menu Three
•
If “15” were keyed in, the panel would display the Walk Test Mode as follows:
Figure 14: Zone Test Menu Four
•
The “w” moving across the lower line alternates with a “Press NO to EXIT” message.
Once the display indicates the panel is in the Walk Test Mode, the display will not revert to normal.
The panel will terminate the test and sound the panel buzzer if there is no activity for a 20-minute
period.
•
The operator may test devices within the zone parameters shown on the display. The panel responds to each test
by:
•
Displaying an activation message on the Alphanumeric Display
•
Entering the activation in the Event Log
•
Lighting the Alarm LED in the ZONE/AREA Display