Radionics D8024 Operator's Manual - page 11
D8024 Operator’s Guide
© 1998 Radionics, Inc. All rights reserved. Page 10 35394B 11/98
•
Sounding the panel buzzer
•
Lighting the LED at the device in alarm.
•
After a few seconds, the panel will automatically reset and turn off the device LED. The panel allows up to one
minute for smoke devices to clear. The operator may now test the next device.
•
If the panel detects an alarm condition in a zone other than those being tested, all notification appliances and relays
will activate as programmed. Notification appliances will continue to operate until silenced from the panel.
•
Terminate the Walk Test by pressing the NoKey. The display will return to Main Menu.
Figure 15: Main Menu
•
The fourth option on the Test Menu, 4) Outputs, is not available to Level Two.
Time Setting
•
Change the time displayed in the normal Alphanumeric Display by selecting option three, 3) Time, from the
Operator’s Menu, Main Level.
Enable/Disable Functions
•
Select option four, 4) Enable, from the Operator’s Menu, Main Level, to open the Enable Menu. Select option five, 5)
Disable, to open the Disable Menu.
Figure 16: Enable/Disable Menus
•
The Content of the two menus is identical, allowing the operator to enable or disable:
•
Zones
•
Individual devices (input)
•
Panel keys
•
Day Modes
•
Outputs: Notification Appliances (Sounders) and Relays
•
Notification appliances cannot be enabled or disabled from Level Two.
Enable/Disable by Zone
•
To enable or disable input signals from devices by zone, select option one, 1) Zone, from the Enable or Disable
Menu. The display will prompt for the zone number. Key in the zone number and press the Enter Key. The display
will repeat the zone number and ask “OK?” Press the Yes Key to confirm. The panel will enable or disable all the
input devices in the selected zone.
Any disabled circuit-driven device or relay on a circuit will still operate on output as programmed.
Only the input signal will be disabled.