Radionics D8024 Operator's Manual - page 9
D8024 Operator’s Guide
© 1998 Radionics, Inc. All rights reserved. Page 8 35394B 11/98
Figure 8: Level Two Controls
Alarm Signal Response
•
Press the Alarm Silence Key to turn off notification appliances external to the panel. TheAlarm Silenced LED will
light. Pressing the Alarm Silence Key again turns on the external notification appliances.
•
Press the Trouble Silence Key to turn off the panel buzzer. The amber Trouble Silenced LED will light.
•
Press theSystem Reset Key to reset the system. The Alarm and Trouble Silenced LEDs will go out and the
Alphanumeric Display will return to normal.
The panel will not accept a reset from an Alarm condition until the notification appliances have
been silenced.
•
To return the system to Level One, press the Shift Key, and select 5) Disable from the Alphanumeric Display. Select
3) Keys from the display. The panel will briefly display the Level Two Entry Menu Two and then revert to the normal
display (alternating between a time and date display and a system status message). Press the Fire Drill Key to
verify that the keys are disabled.
8.4
System Operation
•
Pressing the Shift Key from the normal display will open Main Menu on the Alphanumeric Display. The first option, 1
Commission, is not available to Level Two Operators. See the Programmer’s Guide for commissioning and
programming information. The other options on the Main Level permit tests and the setting, enabling, and disabling
of various system functions.
Figure 9: Main Menu
System Tests
•
Select the second option, 2) Test, from the Main Menu to open the Test Menu. This allows the operator to test:
•
The LEDs on the Front Panel Display
•
The alphanumeric (Liquid Crystal) display
•
Detection and alarm initiating devices connected to the polling circuit
•
Notification Appliance and other alarm condition devices connected to the system.
Figure 10: Test Menu
•
If no action is taken, the display reverts to the normal display after one minute.