Salicru SLC CUBE 3+ User Manual - page 8
8
SALICRU
Measures
Alarms
Status - Control
Rated Values
Plots
Advanced
Serial Number
DSP SW Version
MCU SW Version
Unit Status
Back
Information
BM628 / Screen
1234567890
Ver. 4.5 J
V. C 5.0 Y
010 / 10
Board ID
105
Shutdown
Output Status
Bypass
System
Standalone
Parallel Unit Status
-
Fig. 8.
Information screen.
Below the «Lock», «Help» and «Information» buttons, it is
displayed a chart with the connected load in each phase and
total of the equipment, in a numerical and bar way (see Fig. 9).
Output load
L1 F. R: 80.2 %
L2 F. S: 83.5 %
L3 F. T: 81.9 %
TOTAL: 81.8 %
Fig. 9.
Side panel in the start menu.
3.3. SETTING.
The «Setting» buttons are located in the right top corner of
«Title» categorie.
When pressing over the «Setting» section, there is access
to its menu. The side menu shows the different options
«Time and Date», «Language» and «Communication». The
end-user may access to the contents of each one of them
when touching the respective field in the touch screen.
3.3.1. Time and date.
Time & Date
This menu shows a panel with different
programmable fields, like: hour, minute, day, year,
month and week day.
Time & Date
Hour
Minute
Month
Week Day
Day
Year
Fig. 10.
Time and date setting of the equipment.
1.
The «Drop-down» button allows, depending on the field,
opening the menu and selecting one of the proposed vari-
ables or entering a value by means of the pop up keyboard,
to change it. When touching on any field, there will be a
“Pop up” screen, which allows any of these two options.
The date format can be set between «Day/Months/
Year» and «Year/Month/Day».
2.
DD/MM/
YYYY
The «Day/Month/Year» button allows setting
the date, making the first character displayed is
the day, then the month and year.
3.
YYYY/
MM/DD
The «Year/Month/Day» button allows setting
the date, making the first character displayed is
the year, then the month and finally the day.
3.3.2. Language.
Language
In the «Language» section, the end-user can choose
between one of the available languages, by clicking
its respective icon to change the descriptive in the
screen.
Section 1 states the available languages and their
constraints to display them in the control panel.
3.3.3. Communication.
Communication
In the «Communication» menu, the end-user can set
the parameters of the «Slot port» and «Port 0» of
the system like: modbus address, baude rate, parity,
stop bits and protocol.
3.3.3.1. Slot port.
Slot Port
The «Slot Port» key allows selecting this
communication channel to change its parameters,
if available.
The available variable are the same as the ones
shown in Fig. 11 for «Port 0».
3.3.3.2. Port 0.
Port 0
The «Port 0» key allows selecting this communication
channel to change its parameters, by setting the
following five parameters (see Fig. 11).
It allows setting the Modbus Address.
Address range between 1 and 247.
Baudrate (communication speed in Bauds).
Options: 1200, 2400, 4800, 9600 or 19200.
Communication parity.
Options: No parity, Even or Odd.
Stop bits.
Options: 1 and 2
Communication protocol.
Options: SEC or MODBUS 2