Salicru UPS SLC TWIN PRO series User Manual - page 17
17
SALICRU
–
The own module.
–
1 trunk with Anderson connectors at its ends in order to
do the connection between the battery module and the
equipment.
–
1 connection cable for the earth protection, to joint
between the equipment and module.
•
Once the reception is finished, it is advisable to pack the UPS
again till its commissioning in order to protect it against me-
chanical shocks, dust, dirt, etc...
4.2.2. Storage.
•
Storage of the equipment will be done in a dry place, safe-
guard from rain, protected from dust, water jets or chemical
agents, never outdoors. It is advisable to keep the equipment
and the battery pack/s, into their original packages, which
have been designed to assure the maximum protection
during the transport and storage.
•
In general and other than in special cases, the UPS
has sealed lead-calcium batteries and should not be
stored for more than 12 months (see the date of the last
charge of the batteries, noted on the label adhered to the
device packaging or on the battery unit).
•
After this time, connect the equipment to mains and together
with battery unit, if any, start it up according to the instructions
described in this manual and charge them for 2 hours from
floating level.
•
Finally, shutdown the equipment, disconnect it and fit the UPS
and batteries in their original packaging, noting the new bat-
tery charge date on each respective label.
•
Do not store the devices where the ambient temperature
exceeds above 50ºC or below –15ºC, otherwise it may de-
grade the electrical characteristics of the batteries.
4.2.3. Unpacking.
•
The packaging of the equipment has a cardboard enclosure,
expanded polystyrene (EPS) or polyethylene foam (EPE) cor-
ners, plastic bag and polyethylene strip, all materials a re recy-
clable; so if you are going to dispose them, do it in accordance
with the regulations in force. It is recommended to keep the
packaging in case it were needed in future.
•
Proceed as follows:
Cut the strips of the cardboard enclosure, in those models
with strips.
Take out the accessories (cables, documentation, ... )
Take out the equipment or battery module from the
packaging, considering the help of a second person de-
pending on the weight of the model.
Remove the protection corners of the packaging and the
plastic bag.
Keep out of reach of children the plastic bag, due
to the risks that it involves.
Inspect the equipment before continuing and in case
damages are confirmed, contact with the supplier or in
lack of him with out firm.
4.2.4. Transport to location.
•
Although the weight of the equipments is not so high, it is
recommended to move the UPS by the use of a forklift, pallet
truck or by means of the most suitable means of transport by
evaluating the remoteness of the location point.
If the distance is high, it is recommended to move the equip-
ment still packaged till the installation place and unpack it
later.
4.3. Connection.
•
Cross cable section used in the power supply of the
equipment and loads to feed, will be sized according
to the nominal current stated in the nameplate sticked on the
equipment, by respecting the Low Voltage Electrotechnical
Regulations or norms of the corresponding country.
•
Installation will have the suitable input protections sized to
the current of the equipment and stated in the nameplate of
the equipment (residual current devices type B and circuit
breaker with C characteristic or any other equivalent one).
Overload conditions are considered as a nonpermanent an
exceptional operating mode, so these currents will not be
kept in mind when sizing the protections.
•
Output protection will be done with a circuit breaker of C char-
acteristic or any other equivalent one.
•
The equipments can be installed and used by per-
sonnel with not specific training, just with only help of
this «Manual», less those ones with power blocks have to be
installed by qualified personnel.
•
In the hard wired models, is needed to remove the fixing
screws of the protection cover and the own cover, to proceed
to the parallel connection.
When finalising the corresponding tasks the cover/s and their
fixing screws will be fitted back.
•
To insert the option cards, it is needed to remove the fixing
screws of the smart slot and the own cover.
When finalising the corresponding tasks the cover/s and their
fixing screws will be fitted back.
•
It is recommended to use pointed terminals in all ends of the
cables connected to the power blocks (input and output).
•
Check the correct torque in the screws of the power blocks.
4.3.1. Connection of input .
•
As this is a device with class I protection against
electric shocks, it is essential to install a protective
earth conductor (connect earth(
)). Connect the con-
ductor to the terminal, before connecting the power supply
to the input UPS.
•
Equipments with IEC inlet (all models less the B1 version of
3kVA):
Toke the power cord with schuko plug and IEC connector.
Connect the IEC connector to the UPS inlet.
Insert the schuko plug in to the wall AC outlet.
•
In equipments with terminal blocks (3 kVA model B1).
Connect the power supply cables to input power blocks R (L)
and N, by respecting the rotation of phase and neutral
stated in the labelling of the equipment and in this manual.
If this rotation is not respected there could be fault/s and/or
anomalies.
Pay attention to the correct connection of the input ter-
minals, including the earth, by observing the labelling
of the equipment.
When discrepancies exist between the labelling and the in-
structions of this manual, the labelling will always prevail.