6. Control panel with LCD.
6.1.
Control panel.
Fig. 10.
Control panel view.
Key
Function
Description
SELECT key
UPS on bypass mode, the output voltage,
frequency and bypasss enabling/disabling can
be selected by pressing the key SELECT and
validated with ENTER.
ENTER key
OFF
UPS shutdown
Press for more than 1 sec. the key OFF.
The inverter is shutdown and the output is
transferred over the bypass. If there is power
supply and bypass is activated (code «1»), the
outputs (schuko outlets and specific terminals)
supplies voltage direct from mains through the
static bypass.
Consider by default that the bypass is
deactivated from factory (code «0»), so in this
conditions when pressing the key OFF, there
will not be voltage at the output.
With this key an alarm can also be deactivated
on bypass mode.
ON
MUTE
UPS start up
Press for more than 1 sec. the key ON. An
automatic battery test is done and then the
inverter is started up.
Each time that the inverter is started up, an
automatic battery test is done.
Acoustic alarm
silencer
With the equipment started up, the acoustic
alarm on battery mode can be silenced, by
pressing the over the key ON, of double function,
in this case as MUTE. It doesn’t disable the
alarm permanently, because when any alarm is
activated again, including the silenced on, the
acoustic alarm is activated again.
Battery test
When pressing this key, the equipment can
make the battery test, on line mode, on ECO
mode or on converter mode.
Table 4.
Functionality of the buttons or keypad from control panel.
•
The UPS has a control panel, which includes the following
parts:
Four buttons or keys, see table 4.
A LCD panel.
Display
Function
Input information
V
AC
It displays the input voltage value, which will be showed
from 0 to 999 Vac
Hz
It displays the frequency value of the input voltage, which
will be showed from 0 to 99 Hz
H
It displays that the input voltage is higher than the SPEC
range and the UPS runs on battery mode.
L
It displays that the input voltage is lower than the SPEC
range and the UPS runs on battery mode.
Output information
V
AC
(*1)
It displays the output voltage value, which will be showed
from 0 to 999 Vac.
Hz
It displays the frequency value of the output voltage,
which will be showed from 0 to 99 Hz.
Load information
It displays the % of the load in W or VA, the maximum
value will be showed from 0 to 199% only.
SHORT
It displays that the output is short-circuited and the UPS
could be shutdown.
OVERLOAD
It displays that the load overcomes the SPEC range.
Battery information
V
DC
It displays the battery voltage value, which will be
showed from 0 to 999 Vdc.
It displays the % of the battery capacity, which will be
showed from 0 to 199%
OVER CHARGE
It displays that the battery is overcharged, and the UPS
could transfer to battery mode.
LOW
It displays that the battery is low and the UPS could be
shutdown shortly.
Information of Mode/Fault/Warning codes
It displays the UPS operating mode. It will show the
Mode/Fault/Warning codes, which are identified in table
6 this section.
Inverter operating information
It displays that the inverter is running.
Bypass operating information
It displays that the bypass is activated.
Information of output voltage and frequency and status of bypass
208V
AC
220V
AC
230V
AC
240V
AC
They are the eight selectable output voltage values with
the UPS on standby or bypass mode. One of them can
be activated at the same time only.
50 Hz
60 Hz
They are the two selectable frequency values of the
output voltage with the UPS on standby or bypass mode.
One of them can be activated at the same time only.
Bypass disable
Bypass enable
Selection of bypass enabled/disabled with the UPS on
standby or bypass mode. One of them can be activated
at the same time only.
(*1) Screen that UPS, ECO or CVF can be selected as operating
modes of the equipment, where:
UPS: Setting of normal inverter (Line mode).
ECO: Setting of Economy mode (Standby mode).
CVF: Setting of the equipment as frequency converter.
The detailed illustration of the three modes and operation of the
configuration are described next.
Table 5.
LCD panel messages and their functions.