Salicru UPS SLC TWIN PRO series User Manual - page 25
25
SALICRU
6.3. Settings through the LCD panel of the
synoptic.
Output voltage and frequency, bypass status, ECO mode and Con-
verter mode can be set through the LCD panel of the UPS directly.
Output voltage can be set to 208 V, 220 V, 230 V and 240 V. Output
frequency can be set to 50 Hz or 60 Hz. The UPS operating mode
can be set among line mode, ECO mode and converter mode. The
Bypass can be enabled or disabled. Nevertheless, the settings can
only be done with the UPS on Bypass or no output modes.
On Bypass mode or no output mode, press the button « » (Se-
lect) of the LCD panel for more than one second and the black
dot will blink beside the figure «208 V» of the LCD panel. If the
button « » (Select) is pressed again, the black dot will be moved
through the rest of figures with each pulsation: «220V», «230V»,
«240V», «50Hz», «60Hz», «Bypass disable», «Bypass enable»,
«UPS», «ECO», «CVF» and finally will return back to the initial
point «208 V». If the key «
» (Enter) is pressed for more than
second when the black dot is over the figure to select, the black
dot will not blink and the setting of the output voltage or frequency
or the bypass status or the operating mode will be set to the new
selected figure. If during the next 10 seconds or more, it is not
pressed any key, even the button «
» (Enter) or the button «
» (Select), the black dot will disappear without doing any setting.
One voltage or frequency values can be selected only, and their
values will be changed once the UPS is started up through the
button «ON».
The UPS will change to bypass mode after several seconds that
the «bypass enable» has been selected, as well as no output
voltage mode some seconds later that the «bypass disable» op-
tion is selected. The mode change will only be active when the
UPS is started up through the button «ON».
Example for changing the output voltage from 220V to 230V
through the LCD panel:
Step 1: A blinking black dot appears beside the 208V figure after
pressing the key « » (Select) of the LCD panel, for more than 1
sec..
Step 2: The blinking black dot is shown beside the 230V after
pressing the key « » (Select) twice.
Step 3: When pressing over the key «
» (Enter) for more than
1 second, the new selected value is confirmed.
Step 4: The output voltage is set to 230 V after starting up the
UPS.
Fig. 16.
Steps 1 to 4: Example of how to set the figures of an equip-
ment.