Samlexpower SeC-1215UL Owner's Manual - Section 5 |
10 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 11
seCtIOn 5 |
Installation & Charger Operation
plugtomatewiththe230VACout-
let.cAUtion: the new plug should
have 3 poles i.e. line (l) , neutral(n)
and earth ground. color code for the
power cord conductors is:
- line (l) - Black
- neutral (n) - white
- earth ground - green
Preparing the charger For
operation: Selecting the type
of Battery And charging Stages
TheFloatVoltageandBoostVoltage(Also
calledAbsorptionorOverchargeVoltage)
ofdifferenttypesofLeadAcidBatteries
aredifferent.Also,whenachargerisused
to charge a battery and simultaneously
supplyaload,theBoostStageisrequired
tobedisabledtopreventoverchargingof
thebattery.ADIPSwitchisprovidedon
topoftheoutputterminalsforselecting
thebatterytypeandfordisablingthe
BoostStagewhenchargingloadedbatter-
ies.Thefollowingselectionscanbemade
withthehelpoftheDIPSwitch.
cAUtion! Do not change the DiP Switch
setting when the charger is operating. Al-
ways change the DiP Switch setting when
the charger is off, i.e. after disconnecting
the charger from the Ac input power.
note: the voltages are for a temperature
of 80°F.
cAUtion! Please ensure that the position
no. 4 of the DiP switch (S1-on & S2-on) is
neVeR selected.
DIPSWITCHSETTINGS:SEC-1215UL/SEC-1230UL
S1
S2
float
boost
battery
Type
Charging
Stages
off *
ON*
13.5V*
14.4V*
flooded /
AGM*
3 Stages
(Stages1,2,3)
ON*
off
13.5V
14.0V
GelCell
3 Stages
(Stages1,2,3)
off
off
13.5V
Disabled
Batterywith
Load
2 Stages
(Stages1,3)
ON
ON
caution! Do not use this setting
* factory pre-set in this position
DIPSWITCHSETTINGS-SEC-2415UL
S1
S2
float
boost
BatteryType
Charging
Stages
off *
ON*
27V*
28.8V*
flooded /
AGM*
3 Stages
(Stages1,2,3)
ON
off
27V
28.0V
GelCell
3 Stages
(Stages1,2,3)
off
off
27V
Disabled
Batterywith
load
2 Stages
(Stages1,3)
ON
ON
caution! Do not use this setting
* factory pre-set in this position