Samlexpower SeC-1215UL Owner's Manual - Section 6 |
16 | SAMLEX AMERICA INC.
seCtIOn 6 |
troubleshooting
Ac Side Fuse Blows As Soon As
Power is turned on
TheACinputisselectedfor120VACbut
theunitispluggedinto230VAC.Always
checkthatthechargerissetforthecor-
rectACmainsvoltage.IftheACinput
voltageiscorrect,thechargerisdefective.
CallTechnicalSupport.
Dc Side Fuse Blows As Soon
As the Battery is connected
Wrongpolarityofthebatteryconnection.
EnsurePositiveofthebatteryisconnected
tothePositiveofthechargerandthe
Negativeofthebatteryisconnectedto
theNegativeofthecharger.
SYMPtoMS wHen tHe cHARgeR
iS PoweReD AnD iS Being USeD
AS A Dc PoweR SUPPlY/UPS
the Voltage Drops when load is Switched on
Theloadistryingtodrawcurrentmore
thanthecurrentlimitvalueofthecharger
(thecurrentlimitvalueisthemaximum
specifiedchargingAmps).Oncetheload
currentreachesthecurrentlimitvalue,
thecurrentlimitcircuitisactivatedand
theoutputvoltagedrops.Someloads
likemotors,compressors,incandescent
lamps,halogenlamps,heatingelements,
relays,coils,capacitorsetc.drawverylarge
inrush/startingcurrentswhichmayreach
up to 10 times their normal operating
currents.Ensurethatthestarting/inrush
currentorthemaximumoperatingcur-
rentoftheloadislowerthanthecurrent
limitvalueofthecharger.