Vantage Hearth CC-STAT Installation Manual - page 10
SECTION ONE - Installation
CC-STAT
©Vantage, 41184 / IS-1308191-A
page 8 of 23
Vantage Integration
CC-STAT-WL-KIT / CC-STAT-RL-KIT Setup And Configuration
CC-WLINT, WireLink™ or the CC-RLINT, RadioLink® thermostat interface stations provide bi-
directional communication between the Vantage control system and the HVAC system. Any
button or time control using InFusion Design Center can be programmed to change Setpoints,
Mode, Fan, Network Override (formerly Occupied/Unoccupied mode), etc., on any thermostat.
Setpoints, Indoor/Outdoor temperatures, Mode, Fan (status) and Occupied/Unoccupied (status)
may be displayed on Vantage LCD TPT stations, etc. A Vantage CC-WLINT or CC-RLINT station
and a Vantage thermostat are used together to control HVAC systems. Typically when a
thermostat is ordered the interface station, CC-WLINT, WireLink or the CC-RLINT, RadioLink, is
included (KIT part numbers above).
Backward Compatibility
The CC-STAT thermostat will not work with the Q-ETS3-WireLink or STHERR101-RadioLink
interface stations. However, an existing Vantage system (InFusion or Q Systems), with an older
thermostat and Q-ETS3 or STHERR101, can be updated by simply: 1) replacing the old thermostat
with a new CC-STAT, 2) replacing the old interface station with a new CC-WLINT or CC-RLINT,
3) replacing the serial number of the old Q-ETS3 or STHERR101 with the new serial number of the
CC-WLINT or CC-RLINT in the project file and finally, 4) updating the controller. No additional
programming is required unless the installer wants to take advantage of the new thermostat
features. The Project must be an InFusion System to take advantage of the new thermostat
features. To take advantage of the new thermostat features please follow these steps:
add the new thermostat to the project file,
use the Replacement Wizard (select Edit from the menu bar) to convert most tasks to the new
thermostat,
o in the Replacement Wizard select the old thermostat (only select one) and click Next>,
o select the new thermostat (NOTE: A list of supported tasks is displayed – the list for this
object is not editable),
o click on Finish, the tasks for the old thermostat will now control the new thermostat,
thermostat Objects in TPT screens are not updated by the Replacement Wizard,
o in Touchscreen Designer, edit each TPT thermostat object and manually select the new
thermostat,
Repeat this process for each thermostat.
CC-WLINT & CC-RLINT Specifications
Each Vantage thermostat requires a CC-WLINT or CC-RLINT:
Specifications
CC-WLINT WireLink
CC-RLINT RadioLink
Dimensions HWD
1.875” x 1.5” x 0.375”
47.6mm x 38mm x 10mm
1.875” x 1.5” x 0.5”
114mm x 38mm x 19mm
Weight
0.8oz - 23g
1.4oz - 40g
Station Power
connections
24Volt AC from thermostat base
24Volt AC from thermostat base
Station Count Design
Center
0.36W on IC-24V
0.54W on IC-36V*
1 RadioLink Station
Station Count QLink
1 WireLink Station
1 RadioLink Station
Status LED Indicator
Yes
Yes
I/O LED Indicators
Yes
Yes
Ambient Operating
Temperature
32-95°F -or- 0-35°C
Ambient Operating
Humidity
5-95% non-condensing
Software/Firmware
Vantage’s new thermostat and interface stations are compatible with InFusion Design Center
software version 3.0.56 software or higher and controller firmware 3.0.50 or higher, however, as
stated above, the new thermostat parts may be “dropped-in” with only a serial number change.
For new projects it is recommended that firmware and software be kept to the most current
release.