Vantage Hearth CC-STAT Installation Manual - page 14
SECTION TWO - Setup & Testing
CC-STAT
©Vantage, 41184 / IS-1308191-A
page 12 of 23
SECTION TWO – SETUP & TESTING
This thermostat has the option of being used
in heat pump or heat/cool systems. Switch
SW1 located on the back of the thermostat’s
face to select the proper operation. This
setting can also be verified (but not set) in
the Installer Setup menu system settings
under Equipment Type.
Note: Thermostat reboots within 10 seconds
after switch position is changed.
Installer Setup Menu
HOW TO ENTER THE INSTALLER SETUP MENU TO CHANGE SYSTEM SETTINGS:
Press [MODE] to set system to OFF.
Press [MENU] to enter main menu.
Press and hold [SETUP] for seven seconds,
[INSTALL SETUP] appears.
Press [INSTALL SETUP] to enter installer
setup menu.
Press [NEXT] or [BACK] to page through
the settings.
Press
or
to adjust the setting.
Press [DONE] to save and exit, or
[CANCEL] to exit without saving.
The thermostat will discard changes and exit
if nothing is pressed within 60 seconds.
To reset the installer settings to the default,
reset* the thermostat by pressing the
[RESET] button inside the battery cover.
*CAUTION: Thermostat power must be
cycled after a reset for the CC-WLINT or
CC-RLINT stations to operate correctly.
Equipment Type Selection Switch (SWS1)