Vega VEGABAR 66 Operating instructions manual

Manual is about: 4...20 mA/HART

Summary of VEGABAR 66

  • Page 1

    Operating instructions submersible pressure transmitter with certec ® measuring cell vegabar 66 foundation fieldbus document id: 36740

  • Page 2: Contents

    2 contents vegabar 66 • foundation fieldbus 36740-en-141001 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group ........................................................

  • Page 3

    3 contents vegabar 66 • foundation fieldbus 36740-en-141001 7.1 connect the pc .............................................................................................................. 44 7.2 parameter adjustment with pactware .......................................................................

  • Page 4: 1  About This Document

    4 1 about this document vegabar 66 • foundation fieldbus 36740-en-141001 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification.Pleasereadthi...

  • Page 5: 2  For Your Safety

    5 2 for your safety vegabar 66 • foundation fieldbus 36740-en-141001 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device...

  • Page 6

    6 2 for your safety vegabar 66 • foundation fieldbus 36740-en-141001 2.5 safety label on the instrument the safety approval markings and safety tips on the device must be observed. 2.6 ce conformity thisdevicefulfillsthelegalrequirementsoftheapplicableecguide- lines.Byattachingthecemark,vegaprovides...

  • Page 7: 3  Product Description

    7 3 product description vegabar 66 • foundation fieldbus 36740-en-141001 3 product description 3.1 configuration the scope of delivery encompasses: • vegabar 66 pressure transmitter with suspension cable • strainingclamp(optionallyavailablewithscrewedfitting) • external electronics • or vegabar 66 p...

  • Page 8

    8 3 product description vegabar 66 • foundation fieldbus 36740-en-141001 1 2 3 4 4 5 6 fig. 1: example of a vegabar 66 with suspension cable (left) and connection tube (right) 1 housing with integrated electronics 2 suspension cable 3 connection tube 4 threaded fitting 5 transmitter 6 protective cap...

  • Page 9

    9 3 product description vegabar 66 • foundation fieldbus 36740-en-141001 2 1 13 10 5 4 3 6 7 8 9 11 12 14 fig. 2: layout of the type label (example) 1 instrument type 2 product code 3 approvals 4 electronics 5 protection rating 6 measuring range 7 process and ambient temperature, process pressure 8 ...

  • Page 10

    10 3 product description vegabar 66 • foundation fieldbus 36740-en-141001 instrumentswithhygienicfittingareequippedwithagap-freeform seal. Power is supplied via the h1 fieldbus. A two-wire cable according to fieldbusspecificationservesascarrierofbothpoweranddigitaldata for multiple sensors. This cab...

  • Page 11

    11 3 product description vegabar 66 • foundation fieldbus 36740-en-141001 the delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con- cealed defects must be appropriately dealt with. Uptothetimeofinstallation,thepackagesmustbel...

  • Page 12

    12 3 product description vegabar 66 • foundation fieldbus 36740-en-141001 youcanfindadditionalinformationintheoperatinginstructions "mounting accessory pressure"(document-id43478). The protective cover protects the sensor housing against soiling and intense heat from solar radiation. Youwillfindaddi...

  • Page 13: 4 Mounting

    13 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 4 mounting 4.1 general instructions make sure that all parts of the instrument coming in direct contact with the process, especially the sensor element, process seal and processfitting,aresuitablefortheexistingprocessconditions,such as p...

  • Page 14

    14 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 2 1 2 1 2 1 1 2 fig. 4: position of the filter element 1 filter element 2 blind plug caution: duetothefiltereffect,thepressurecompensationistimedelayed. When opening/closing the housing cover quickly, the measured value can change for a ...

  • Page 15

    15 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 fig. 5: mounting example: version with connection tube in an open vessel fig. 6: mounting example: version with suspension cable in a pump shaft.

  • Page 16

    16 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 4.3 mounting steps with straining clamp 2 3 1 fig. 7: straining clamp 1 suspension cable 2 suspension opening 3 clamping jaws mount vegabar 66 with straining clamp as follows: 1. Hang the straining clamp on a suitable wall hook 2. Lower ...

  • Page 17

    17 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 4.4 mounting steps with screwed connection 1 2 3 4 5 6 fig. 8: threaded fitting 1 suspension cable 2 sealing screw 3 cone bushing 4 seal cone 5 threaded fitting 6 seal mount vegabar 66 with screwed connection as follows: 1. Weld the weld...

  • Page 18

    18 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 4.5 mountingstepswithlockfitting 1 3 2 4 5 fig. 9: lock fitting 1 upper hexagon 2 fixing screw 3 washer disk 4 lower hexagon 5 fixing screw mountvegabar66withlockfittingasfollows: 1. Weld the welded socket g1½ or 1½ npt to the vessel top...

  • Page 19

    19 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 4.6 mounting steps with housing and thread fig. 10: housing and thread 1 housing 2 seal 3 thread mount vegabar 66 with housing and thread in the following way: 1. Weld the welded socket g1½ or 1½ npt to the vessel top 2. Insert the trans...

  • Page 20

    20 4 mounting vegabar 66 • foundation fieldbus 36740-en-141001 90 mm (3.54") r 3,5 mm (0.14" ) 3mm (0.12") 70 mm (2.76") 8 mm (0.32") 93 mm (3.66" ) 110 mm (4.33" ) fig. 11: drilling template - wall mounting plate tip: mount the wall mounting plate so that the cable entry of the socket housing point...

  • Page 21

    21 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 5 connecting to power supply 5.1 preparing the connection always keep in mind the following safety instructions: • connect only in the complete absence of line voltage • if overvoltage surges are expected, overvoltage a...

  • Page 22

    22 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 low frequency potential equalisation currents are thus suppressed, buttheprotectiveeffectagainsthighfrequencyinterferencesignals remains. The total capacitance of the cable and of all capacitors must not exceed 10 nf in...

  • Page 23

    23 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 fig. 12: connection steps 6 and 7 proceed as follows: 1. Loosen the four screws on the housing base with an allen key size4 2. Remove the mounting plate from the housing socket 3 2 1 fig. 13: components of the external ...

  • Page 24

    24 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 3. Loop the connection cable through the cable entry on the housing base 2) information: the cable gland can be mounted in three positions each displaced by 90°. Simply exchange the cable gland against the blind plug in...

  • Page 25

    25 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 i2c display 1 1 2 5 6 7 8 fig. 15: wiring plan, single chamber housing 1 voltage supply, signal output 5.4 wiring plan, double chamber housing the following illustrations apply to the non-ex as well as to the ex-ia vers...

  • Page 26

    26 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 1 2 3 display 1 2 i2c fig. 17: terminal compartment, double chamber housing 1 spring-loaded terminals for voltage supply 2 plug connector for vegaconnect (i²c interface) 3 ground terminal for connection of the cable scr...

  • Page 27

    27 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 5.5 wiring plan, double chamber housing ex d i²c 2 3 1 display typ: 1 2 5 6 7 8 bus sim. Fig. 19: electronics compartment, double chamber housing 1 simulation switch ("on" = simulation mode) 2 connection for vegaconnect...

  • Page 28

    28 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 1 1 2 fig. 21: wiring plan, ex-d-ia double chamber housing 1 voltage supply, signal output 5.6 wiring plan - version ip 66/ip 68, 1 bar 1 2 fig. 22: wire assignment, connection cable 1 brown (+) and blue (-) to power su...

  • Page 29

    29 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 5.7 wiring plan, external housing with version ip 68 fig. 23: vegabar 66 in ip 68 version 25 bar, non-ex and axial cable outlet, external housing i²c display typ: 1 2 5 6 7 8 bus sim. 4 5 6 1 2 3 fig. 24: electronics an...

  • Page 30

    30 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 61 3 cable gland to the sensor 4 ground terminal for connection of the cable screen 5 spring-loaded terminals for foundation fieldbus connection 6 simulation switch ("on" = simulation mode) 1 2 3 4 6 3 4 1 2 5 fig. 25: ...

  • Page 31

    31 5 connecting to power supply vegabar 66 • foundation fieldbus 36740-en-141001 1 2 3 4 6 3 4 1 2 5 fig. 26: connection of the sensor in the housing base 1 brown 2 blue 3 yellow 4 white 5 shielding 6 breather capillaries 5.8 switch-on phase after vegabar 66 is connected to voltage supply or after v...

  • Page 32: Module Plicscom

    32 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 6 set up with the display and adjustment module plicscom 6.1 short description the display and adjustment module is used for measured value display, adjustment and diagnosis. It can be mounte...

  • Page 33

    33 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 fig. 27: insert display and adjustment module note: ifyouintendtoretrofittheinstrumentwithadisplayandadjustment module for continuous measured value indication, a higher cover with an inspect...

  • Page 34

    34 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 – move to the menu overview – confirmselectedmenu – edit parameter – save value • [->] key to select: – menu change – select list entry – select editing position • [+] key: – change value of ...

  • Page 35

    35 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 the display and adjustment module enables the adjustment without fillingorpressure.Thankstothis,youcancarryoutyoursettings already in the workshop without the instrument having to be installe...

  • Page 36

    36 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 5. Select the requested unit, e.G. Kg/dm³ with [->]andconfirmwith [ok],thesubmenu"density"appears. Unitofmeasurement density 0001000 kg/dm³ 6. Enter the requested density value with [->] and ...

  • Page 37

    37 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 information: foranadjustmentwithfilling,simplyentertheactualmeasuredvalue indicated at the bottom of the display. Iftheadjustmentrangesareexceeded,themessage"outside param- eter limits"appear...

  • Page 38

    38 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 youcanfindthedataonthetypelabelontheinstrumentorinthe menuitemsofthezero/spanadjustment. The display and adjustment module enables the adjustment without fillingorpressure.Thankstothis,youcan...

  • Page 39

    39 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 4. Activate the selection with [ok] and select the requested unit with [->] (in the example mbar). 5. Confirmwith[ok] and move to position correction with [->]. The adjustment unit is thus sw...

  • Page 40

    40 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 iftheadjustmentrangesareexceeded,themessage"outside param- eter limits"appears.Theeditingprocedurecanbeabortedwith[esc] or the displayed limit value can be accepted with [ok]. Proceed as foll...

  • Page 41

    41 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 reset select reset? ▼ reset basic adjustment peak value, measured value peak value, temperature basic adjustment the"reset""basic adjustment"resetsthevaluesofthefollowing menu items: menu sec...

  • Page 42

    42 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 6.5 menu schematic information: depending on the version and application, the highlighted menu windows may not always be available. Basic adjustment ▶ basic adjustment 1 display diagnostics s...

  • Page 43

    43 6 set up with the display and adjustment module plicscom vegabar 66 • foundation fieldbus 36740-en-141001 service basic adjustment 4 display diagnostics ▶ service info simulation 4.2 start simulation ▼ reset 4.3 select reset ▼ language 4.3 german copy sensor data 4.4 copy sensor data? Pin 4.5 ena...

  • Page 44: Adjustment Programs

    44 7 set up with pactware and other adjustment programs vegabar 66 • foundation fieldbus 36740-en-141001 7 set up with pactware and other adjustment programs 7.1 connect the pc 3 1 2 fig. 29: connection of the pc via vegaconnect directly to the sensor 1 usb cable to the pc 2 vegaconnect 3 sensor 1 2...

  • Page 45

    45 7 set up with pactware and other adjustment programs vegabar 66 • foundation fieldbus 36740-en-141001 • vegaconnect • power supply unit or processing system 7.2 parameter adjustment with pactware further setup steps are described in the operating instructions manual"dtm collection/pactware"attach...

  • Page 46

    46 8maintenanceandfaultrectification vegabar 66 • foundation fieldbus 36740-en-141001 8 maintenanceandfaultrectification 8.1 maintenance if the instrument is used properly, no special maintenance is required in normal operation. Insomeapplications,productbuilduponthediaphragmcaninfluence the measuri...

  • Page 47

    47 8maintenanceandfaultrectification vegabar 66 • foundation fieldbus 36740-en-141001 error cause rectification instrument does not appear during connection setup profibusdpcable pole-reversed check cable and correct, if necessary incorrect termi- nation check termination at the beginning and end po...

  • Page 48

    48 8maintenanceandfaultrectification vegabar 66 • foundation fieldbus 36740-en-141001 product temperature 40 °c, reference temperature 20 °c vegabar 66 with measuring range 0.2 bar deviation calculationΔt:Δt=40°c-20°c=20k calculation of the set turn down: td = 200 mbar/147 mbar, td = 1.4 basic accur...

  • Page 49

    49 8maintenanceandfaultrectification vegabar 66 • foundation fieldbus 36740-en-141001 ordering and exchange are possible with or without sensor serial number. The electronics module with serial number includes order- specific data such as factory setting, seal material etc. These are not included in...

  • Page 50

    50 8maintenanceandfaultrectification vegabar 66 • foundation fieldbus 36740-en-141001 8.6 how to proceed if a repair is needed youcanfindarepairformaswellasdetailedinformationonhowto proceed at www.Vega.Com/downloadsand"forms and certificates". By doing this you help us carry out the repair quickly ...

  • Page 51: 9 Dismount

    51 9 dismount vegabar 66 • foundation fieldbus 36740-en-141001 9 dismount 9.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Takenoteofchapters"mounting"and...

  • Page 52: 10 Supplement

    52 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 10 supplement 10.1 technical data general data measured variable level measuring principle ceramic-capacitive, dry measuring cell communication interface i²c bus materials and weights material 316l corresponds to 1.4404 or 1.4435 mate...

  • Page 53

    53 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 Ʋ ohmic contact betweengroundterminal,processfittingandtransmitter Ʋ connection cable between ip 68 housing and external electronics pur,fep,pe Ʋ type label support with ip 68 version on cable pe hard weight approx. Ʋ basic weight 0.7...

  • Page 54

    54 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 adjustmentrangeofthezero/spanadjustmentrelatingtothenominalmeasuringrange: Ʋ zero -20 … +95 % Ʋ span -120 … +120 % 10) Ʋ differencebetweenzeroandspan max. 120 % of the nominal range recommended max. Turn down 10 : 1 nominalmeasuringra...

  • Page 55

    55 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 nominalrange overload capacity, max. Pressure overload capacity, min. Pres- sure 0 … +350 psig +1900 psig -15 psig 0 … +900 psig +2900 psig -15 psig absolute pressure 0 … 15 psi 500 psi 0 psi 0 … 35 psi 700 psi 0 psi 0 … 70 psi 900 ps...

  • Page 56

    56 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 thermal change, current output (-40 … +176 °f) 0,3 % -0,15 % -40°c -20°c 20°c 40°c 60°c 80°c 0,15 % -0,3 % fig. 31: thermal change, current output long-termstability(accordingtodin16086andiec60770-1) applies to digital hart interface ...

  • Page 57

    57 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 product temperature, suspension cable/measuring cell seal Ʋ pe/fkm -20 … +60 °c (-4 … +140 °f) Ʋ pe/epdm -20 … +60 °c (-4 … +140 °f) Ʋ pur/fkm -20 … +80 °c (-4 … +176 °f) Ʋ pur/epdm -20 … +80 °c (-4 … +176 °f) Ʋ fep/fkm -20 … +100 °c ...

  • Page 58

    58 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 Ʋ double chamber housing – 1 x cable entry m20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind plug m20 x 1.5; plug m12 x 1 for the external display and adjustment unit (optional) or: – 1 x closing cap ½ npt, 1 x blind plug ½ npt, plug m12 x 1 f...

  • Page 59

    59 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 electromechanical data - version ip 68 cable entry/plug 18) Ʋ external housing – 1 x cable gland m20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind plug m20 x 1.5 or: – 1 x closing cap ½ npt, 1 x blind plug ½ npt or: – 1␣xplug(dependingonthever...

  • Page 60

    60 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 Ʋ ex d instrument 16 … 32 v dc operating voltage with illuminated display and adjustment module Ʋ non-ex instrument 12 … 32 v dc Ʋ ex-ia instrument 12 … 24 v dc Ʋ ex d instrument 20 … 32 v dc power supply by/max. Number of sensors Ʋ f...

  • Page 61

    61 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 t i simulat e alarms out pv field-value mode & status pvf-time lo w -c ut o ff l-typ e out-scal e pv-scale direct indirect indirect sqrt bar % lin% primary value secondary value 1 secondary value 2 sensor mounting correction ai 2 ai 3...

  • Page 62

    62 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 – bar, psi, …, m, ft, …; in case of length type engineering unit and access to parameters the cor- responding values will be converted by density factor • secondary_value_2 – valueaftermin/max-adjustment.Selectedasinputtoaifbbysetting...

  • Page 63

    63 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 – write access resets to current value • cal_point_hi – highest calibrated value. For calibration of the high limit point you give the high measurement value(pressure)tothesensorandtransferthispointashightothetransmitter.Unitderives f...

  • Page 64

    64 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 plastic housing ~ 69 mm (2.72") ø 79 mm (3.11") 112 mm (4.41" ) m20x1,5/ ½ npt ~ 84 mm (3.31") m16x1,5 112 mm (4.41" ) m20x1,5/ ½ npt 1 2 ø 79 mm (3.11") 1 single chamber version 2 double chamber version aluminium housing 2 1 ø 86 mm ...

  • Page 65

    65 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 stainless steel housing ~ 69 mm (2.72") ø 79 mm (3.11") 117 mm (4.61" ) m20x1,5/ ½ npt ~ 59 mm (2.32") ø 80 mm (3.15") 112 mm (4.41" ) m20x1,5/ ½ npt ~ 87 mm (3.43") ø 86 mm (3.39") 120 mm (4.72" ) m20x1,5/ ½ npt m16x1,5 3 2 1 1 singl...

  • Page 66

    66 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 external housing with ip 68 version 1 2 3 4 5 82 mm (3.23") 80 mm (3.15" ) 108 mm (4.25" ) 41,6 mm (1.64") ~ 66 mm (2.60") 59 mm (2.32" ) 110 mm x 90 mm (4.33" x 3.54") 110 mm x 90 mm (4.33" x 3.54") 51 mm (2.01" ) 41,6 mm (1.64") fig...

  • Page 67

    67 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 1 2 3 68 mm (2.68") 68 mm (2.68" ) 92 mm (3.62" ) 42mm (1.65") 40mm (1.57") 110 mm x 90 mm (4.33" x 3.54") 51 mm (2.01" ) fig. 40: external housing - stainless steel version 1 lateral cable outlet 2 axial cable outlet 3 seal 2 mm (0.0...

  • Page 68

    68 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 vegabar66,standardversion 1 2 3 4 5 175 mm (6 57 / 64 ") 52 mm (2 3 / 64 ") 132 mm (5 13 / 64 ") ø 8 mm ( 5 / 16 ") ø 21,3 mm ( 27 / 32 ") ø 44 mm (1 47 / 64 ") ø 40 mm (1 37 / 64 ") 48-52 mm (1 57 / 64 " - 2 3 / 64 ") 22 mm ( 55 / 64...

  • Page 69

    69 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 vegabar66,transmitter32mm 1 2 3 4 5 175 mm (6 57 / 64 ") 52 mm (2 3 / 64 ") 178 mm (7 1 / 64 ") ø 8 mm ( 5 / 16 ") ø 21,3 mm ( 27 / 32 ") ø 32 mm (1 17 / 64 ") 48-52 mm (1 57 / 64 " - 2 3 / 64 ") 22 mm ( 55 / 64 ") 14 mm ( 35 / 64 ") ...

  • Page 70

    70 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 vegabar66,pvdfversion 1 2 l l 20 mm ( 25 / 32 ") 22 mm ( 55 / 64 ") 40 mm (1 37 / 64 ") sw 46 mm (1 13 / 16 ") g1½a / 1½”npt sw 46 mm (1 13 / 16 ") g1½a / 1½”npt fig. 43: vegabar 66, pvdf version 1 with threaded fitting g1½ (1½ npt) 2...

  • Page 71

    71 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 vegabar66,flangeconnection 2 43 / 64 " 3 15 / 32 " 4 1 / 64 " 5 7 / 16 " 6 3 / 8 " 3 5 / 64 " 5 / 64 " 5 / 64 " 1 / 8 " 1 / 8 " 1 / 8 " 1 / 8 " 4xø 35 / 64 " 4xø 45 / 64 " 4xø 45 / 64 " 4xø 45 / 64 " 8xø 45 / 64 " 8xø 55 / 64 " 4 21 /...

  • Page 72

    72 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 vegabar66,hygienicfittings ø 78 mm (3 5 / 64 ") ø 92 mm (3 5 / 8 ") 51 mm (2 1 / 64 ") l 51 mm (2 1 / 64 ") l ø 64 mm (2 33 / 64 ") ø 40 mm (1 37 / 64 ") ø 8 mm ( 5 / 16 ") 132 mm (5 13 / 64 ") 1 2 fig. 45: vegabar 66, hygienic fittin...

  • Page 73

    73 10 supplement vegabar 66 • foundation fieldbus 36740-en-141001 10.4 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamil...

  • Page 74: Index

    74 index vegabar 66 • foundation fieldbus 36740-en-141001 index a accessories – display and adjustment module 11 – external display and adjustment unit 11 – flanges 11 – interface adapter 11 – measuring instrument holder 11 – protective cap 12 application area 9 c check signal 46 connection vegaconn...

  • Page 75

    75 notes vegabar 66 • foundation fieldbus 36740-en-141001.

  • Page 76

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 36740-en-141001 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...