Quick setup guide pressure transmitter with metallic measuring cell vegabar 83 4 … 20 ma document id: 46312.
2 contents vegabar 83 • 4 … 20 ma 46312-en-160705 contents 1 for your safety 1.1 authorised personnel ....................................................................................................... 3 1.2 appropriate use ...........................................................................
3 1 for your safety vegabar 83 • 4 … 20 ma 46312-en-160705 1 for your safety 1.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the requi...
4 1 for your safety vegabar 83 • 4 … 20 ma 46312-en-160705 1.6 permissible process pressure the permissible process pressure is specified on the type label with "process pressure", see chapter " configuration ". For safety reasons, this range may not be exceeded. This applies even if a measuring cel...
5 2 product description vegabar 83 • 4 … 20 ma 46312-en-160705 2 product description 2.1 configuration the type label contains the most important data for identification and use of the instrument: 2 1 13 14 12 10 11 5 3 6 4 7 8 9 fig. 1: layout of the type label (example) 1 instrument type 2 field f...
6 3 mounting vegabar 83 • 4 … 20 ma 46312-en-160705 3 mounting 3.1 general instructions for use of the instrument protect your instrument against moisture ingress through the following measures: • use the recommended cable (see chapter " connecting to power supply " of the operating instructions) • ...
7 4 connecting to power supply vegabar 83 • 4 … 20 ma 46312-en-160705 4 connecting to power supply 4.1 connecting the voltage supply and signal output are connected via the spring- loaded terminals in the housing. Connection to the display and adjustment module or to the interface adapter is carried...
8 4 connecting to power supply vegabar 83 • 4 … 20 ma 46312-en-160705 you can find further information on the max. Wire cross-section under " technical data - electromechanical data " 7. Check the hold of the wires in the terminals by lightly pulling on them 8. Connect the screen to the internal gro...
9 5 set up with the display and adjustment module vegabar 83 • 4 … 20 ma 46312-en-160705 5 set up with the display and adjustment module 5.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor and removed again at any time. You can choose any one of...
10 5 set up with the display and adjustment module vegabar 83 • 4 … 20 ma 46312-en-160705 carry out the following steps in the below sequence. You can find " extended adjustment " in the next sub-chapter. 1. Measurement loop name in the first menu item you assign a suitable measurement loop name. Pe...
11 5 set up with the display and adjustment module vegabar 83 • 4 … 20 ma 46312-en-160705 6. Min. Adjustment in this menu item you carry out the min. Adjustment for level enter the percentage value and the corresponding value for the min. Level. The quick setup is finished. 5.3 parameter adjustment ...
12 5 set up with the display and adjustment module vegabar 83 • 4 … 20 ma 46312-en-160705 menu - setup menu item parameter default setting measurement loop name sensor application application level units unit of measure- ment mbar (with nominal measuring range ≤400 mbar) bar (with nominal measuring ...
13 5 set up with the display and adjustment module vegabar 83 • 4 … 20 ma 46312-en-160705 menu item parameter default setting peak value pressure actual measured value temperature actual temperature values from meas- uring cell, electronics simulation pressure menu - additional adjustments menu item...
14 6 supplement vegabar 83 • 4 … 20 ma 46312-en-160705 6 supplement 6.1 technical data note for approved instruments the technical data in the respective safety instructions are valid for approved instruments (e.G. With ex approval). These data can differ from the data listed herein, for example reg...
15 6 supplement vegabar 83 • 4 … 20 ma 46312-en-160705 Ʋ for u n 24 v dc (18 v b ≤ 1.0 v eff (16 … 400 hz) permissible residual ripple - ex-d-ia instrument Ʋ for u n 24 v dc (18 v b ≤ 1 v eff (16 … 400 hz) load resistor Ʋ calculation (u b - u min )/0.022 a Ʋ example - non-ex instrument with u b = 24...
Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 46312-en-160705 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...