Vega VEGAFLEX 81 Quick Setup Manual - page 15
15
5 Set up with the display and adjustment module
VEGAFLEX 81 • Foundation Fieldbus
47589-EN-140324
Max. adjustment
Inthismenuitem,youcanenterthemax.adjustmentforthelevel.
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
referenceplane(sealsurfaceoftheprocessfitting).Keepinmindthat
themax.levelmustliebelowthedeadband.
Min. adjustment
In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.
distancefromtheflangetotheprobeend)correspondingtotheper-
centage value. The distance refers tot he sensor reference plane (seal
surfaceoftheprocessfitting).
Dielectric constant - upper medium
Inthismenuitem,youcandefinethetypeofmedium(product).
Max. adjustment
Inthismenuitem,youcanenterthemax.adjustmentforthelevel.
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
referenceplane(sealsurfaceoftheprocessfitting).Keepinmindthat
themax.levelmustliebelowthedeadband.
Min. adjustment
In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.
distancefromtheflangetotheprobeend)correspondingtotheper-
centage value. The distance refers tot he sensor reference plane (seal
surfaceoftheprocessfitting).
Max. adjustment - Interface
Carryoutthemax.adjustmentfortheinterface.
To do this, enter the percentage value and the suitable distance value
in m for the full vessel.
Min. adjustment - Interface
Carry out the min. adjustment for the interface.
To do this, enter the percentage value and the suitable distance value
in m for the empty vessel.
Interface measurement