5 Set up with the display and adjustment module
VEGAFLEX 86 • 4 … 20 mA/HART - two-wire
47615-EN-150102
measurement. We generally recommend a false signal suppres-
sion.
The sensor measures the distance from the sensor (reference plane)
to the product surface.
4
5
3
1
2
Fig.9:Measuringranges-VEGAFLEX86
1 Reference plane
2 Probe length L
3 Measuring range (default setting refers to the measuring range in water)
4 Upper dead band (in this area no measurement is possible)
5 Lower dead band (in this area no measurement is possible)
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
otherdistances,forexample,10%and90%isalsopossible.Starting
pointforthesedistancespecificationsisalwaysthesealsurfaceof
thethreadorflange.
1. In the menu "Additional settings", menu item "Damping" you can
adjust the requested damping of the output signal.
2. Select the parameter of the current output and the output charac-
teristics in the menu item "Currentoutput".
Parameterization example
Further steps