6.1 Technical data
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Cable entry
Ʋ M20x1.5
1xcableglandM20x1.5(cable:ø6…12mm),1x
blindplugM20x1.5
Ʋ ½ NPT
1xblindplugNPT,1xclosingcap(red)½NPT
Wire cross-section (spring-loaded terminals)
Ʋ Massive wire, stranded wire
0.2 … 2.5 mm² (AWG 24 … 14)
Ʋ Stranded wire with end sleeve
0.2 … 1.5 mm² (AWG 24 … 16)
Voltage supply
Operating voltage
Ʋ Non-Exinstrument,Ex-dinstrument
9.6 … 35 V DC
Ʋ Ex-iainstrument
9.6 … 30 V DC
Ʋ Ex-d-iainstrument
15 … 35 V DC
Operating voltage with illuminated display and adjustment module
Ʋ Non-Exinstrument,Ex-dinstrument
16 … 35 V DC
Ʋ Ex-iainstrument
16 … 30 V DC
Ʋ Ex-d-iainstrument
20 … 35 V DC
Reverse voltage protection
Integrated
Permissibleresidualripple-Non-Ex,Ex-iainstrument
Ʋ Frequency
16…400Hz
Ʋ for 12 V< U
N
< 18 V
≤0.7V
eff
Ʋ for 18 V< U
N
< 35 V
≤1.0V
eff
Permissibleresidualripple-Ex-d-iainstrument
Ʋ Frequency
16…400Hz
Ʋ for 18 V< U
N
< 35 V
≤1.0V
eff
Load resistor
Ʋ Calculation
(U
B
- U
min
)/0.0215 A
Ʋ Example-Non-Exinstrumentwith
U
B
= 24 V DC
(24V-9.6V)/0.0215A=670Ω