3 Mounting
VEGAFLEX 86 • 4 … 20 mA/HART - two-wire
47615-EN-150102
3 Mounting
3.1 General instructions for use of the instrument
Protect your instrument against moisture ingress through the following
measures:
•
Use the recommended cable (see chapter "Connectingtopower
supply")
•
Tighten the cable gland
•
Whenmountinghorizontally,turnthehousingsothatthecable
gland points downward
•
Loop the connection cable downward in front of the cable gland
This applies particularly to:
•
Outdoor mounting
•
Installationsinareaswherehighhumidityisexpected(e.g.through
cleaning processes)
•
Installations on cooled or heated vessels
3.2 Mounting instructions
During operation, the probe must not touch any installations or the
vessel wall. If necessary, fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
nearly down to the lowest point of the bottom. Keep in mind that
measurement all the way down to the tip of the probe may not be pos-
sible.Theexactvalueofthemin.distance(lowerdeadband)isstated
in chapter "Technicaldata".
Fig. 2: Vessel with conical bottom
Protection against mois-
ture
Installation position